Quick Reference Guide
Packaged Rooftop Units Foundation™
Cooling and Gas/Electric
15 to 25 Tons
List of Options
Note: Most Factory Installed Options are available for downflow air discharge units only. Verify with ordering system for availability.
Table 1. List of options
Factory Installed Options | Field Installed Options | ||
Barometric Relief (a),(b) | 2-in MERV 13 Pleated Filters | ||
Complete Coat™ Microchannel Condenser Coil | Crankcase Heater (25 Tons) | ||
Condensate Overflow Switch | |||
Economizer - Standard/Downflow(b) | Economizer - Standard/Horizontal | ||
Economizer - Low Leak/Downflow(b) | Economizer - Low Leak/Horizontal | ||
Electric Heaters | Hail Guard | ||
Manual Outside Air Damper | High Altitude Kit | ||
Motorized Outside Air Damper | High and Low Static Drive Kit | ||
Multi-Speed Oversized Motor | LP Conversion Kit | ||
Reference or Comparative Enthalpy Economizer | Powered Exhaust | ||
Model Number: ECC | Used With: Cooling Only (Electric Heat Optional) | Stainless Steel Heat Exchanger with 10 Year Warranty | Remote Potentiometer |
Model Number: GCC | Used With: Gas Heat Unit | Through the Base Electrical Access | Roof Curb |
Through the Base Gas Piping | Thermostat | ||
Unit Mounted Non-Fused Disconnect Switch(c) | |||
(a) Requires an economizer. | |||
(b) Some field set up required. | |||
(c) Must be ordered with Through-the-Base Electrical option. |
December 2022
RT-PRC069F-EN
Table 2. 15 to 25 ton packaged rooftop performance data (gas or electric heat)
Nominal Size (Ton) Cooling Performance(a) | 15 | 17.5 | 20 | 25 | |||||
ECC | GCC | ECC | GCC | ECC | GCC | ECC | GCC | ||
Gross Cooling Capacity (MBh) | 180,000 | 206,000 | 244,000 | 268,000 | 268,000 | ||||
AHRI Net Cooling Capacity (MBh) | 171,000 | 194,000 | 214,000 | 252,000 | 280,000 | 280,000 | |||
Nominal Airflow CFM/AHRI Rated CFM | 5,400 | 6,650 | 7,000 | 8,000 | 8,000 | ||||
EER | 11 | 11 | 10 | 13.2 | 10 | 13.2 | 9.8 | 13.2 | |
IEER (Multi-Speed Fan) | 14.2 | 14.2 | 13.2 | 13.2 | 9.2 | 13.2 | |||
Gas Heating Performance(b) | |||||||||
Low Heat (Input/Output) - (MBh) | 240,0/194,0 | 240,0/194,0 | 240,0/194,0 | 240,0/194,0 | |||||
Medium Heat (Input/Output) - (MBh) | 320,0/259,0 | 320,0/259,0 | 320,0/259,0 | 320,0/259,0 | |||||
High Heat (Input/Output) - (MBh) | 380,0/308,0 (Downflow), 350,0/284,0 (Horizontal)(c) | 380,0/308,0 (Downflow), 350,0/284,0 (Horizontal)(c) | 380,0/308,0 (Downflow), 350,0/284,0 (Horizontal)(c) | 380,0/308,0 (Downflow), 350,0/284,0 (Horizontal)(c) | |||||
Other Information | |||||||||
Net Weight (Lbs) - Gas Heat | 2013 | 2028 | 2025 | 2061 | |||||
Net Weight (Lbs) - Electric Heat | 1850 | 1855 | 1860 | 1896 | |||||
Filters - Type Furnished Number and Size | Throwaway (8) 20x25x2 | Throwaway (8) 20x25x2 | Throwaway (8) 20x25x2 | Throwaway (8) 20x25x2 | |||||
(a) Cooling Performance is rated at 95°F ambient, 80°F entering dry bulb, 67°F entering wet bulb. | |||||||||
(b) Verify option availability in product data catalog. | |||||||||
(c) For 17.5T high heat option, input rate will de-rate from downflow to horizontal. |
Table 3. Unit MCA and MOP electrical data (standard indoor fan motor - cooling or gas heat)
E/GCC | Volts | MCA(a) | MOP | |
208-230/3 | 79 | 100 | ||
460/3 | 36 | 45 | ||
575/3 | 30 | 35 | ||
208-230/3 | 92 | 110 | ||
210 | 460/3 | 40 | 50 | |
575/3 | 33 | 40 | ||
208-230/3 | 101 | 125 | ||
240 | 460/3 | 50 | 60 | |
575/3 | 39 | 50 | ||
208-230/3 | 133 | 175 | ||
300 | 460/3 | 58 | 70 | |
575/3 | 46 | 60 | ||
(a) Values do not include Power Exhaust accessory. |
Table 4. Unit indoor fan data
E/GCC | Volts | Standard HP - RPM | Oversized HP - RPM | ||
208-230/3 | |||||
460/3 | 3-1750 | 5-3450 | 7.5-3450 | ||
180 | 575/3 | 5-3450 | |||
208-230/3 | |||||
460/3 | 5-3450 | 7.5-3450 | |||
210 | 575/3 | ||||
208-230/3 | |||||
460/3 | 5-3450 | 7.5-3450 | |||
240 | 575/3 | ||||
208-230/3 | |||||
300 | 460/3 | 7.5-3450 | 10-1750 | ||
575/3 |
Table 5. Unit dimensional data
15 to 25 Ton | |
Unit Length UL | 123 1/8 |
Unit Width UW | 86 15/16 |
Unit Height UH | 58 5/8 |
Clearance C1 | 60 |
Clearance C2 | 48 |
Clearance C3 | 36 |
Clearance C4 | 68 |
Clearance C5 | 72 |
Curb Length CL | 117 3/16 |
Curb Width CW | 81 |
Supply Length SL(a) | 28 9/16 |
Supply Width SW(a) | 69 1/2 |
Return Length RL(a) | 22 1/4 |
Return Width RW(a) | 77 |
(a) Dimensions are for curb openings and not duct inserts. Reference the product catalog for duct insert dimensions. |
Diagram showing dimensions: C1, C2, C3, C4, C5, CL, CW, RL, RW, SL, SW, UL, UW, UH.
Table 6. Curb compatibility matrix - gas heat(a)
Tons | Foundation Model No. | Voyager Light Commercial Model No. | Carrier Model No. |
15 | G*C180 | YCD180E, YCD180F, YSD180F, YHD180F, YCD181B, YCD181C, YCD181E, YCD181F, YSD180G, YSH180G, YHD180G, YHH180G | 48TJD016, 48TJE016, 48TJF016, 48HJD017, 48HJF017, 48TMD016, 48TMF016, 48DP016, 48DR016 |
17½ | G*C210 | YCD210A, YCD210B, YCD210E, YCD210F, YSD210F, YHD210F, YCD211B, YCD211C, YCD211E, YCD211F, YSD210G, YSH210G, YHD210G, YHH210G | 48TJD020, 48TJF020, 48TMD020, 48TMF020, 48DP020 |
20 | G*C240 | YCD240A, YCD240B, YCD240E, YCD240F, YSD240F, YHD240F, YCD241B, YCD241C, YCD241E, YCD241F, YSD240G, YSH240G, YHD240G, YHH240G | 48TJD024, 48TJE024, 48TJF024, 48TMD025, 48TMF025, 48HJD025, 48HJF025 |
25 | G*C300 | YCD300B, YCD300E, YCD300F, YSD300F, YHD300F, YCD301C, YCD301E, YCD301F, YSD300G, YSH300G, YHD300G, YHH300G | 48TJD028, 48TJE028, 48TJF028, 48TMD028, 48TMF028 |
(a) Data is subject to change. Data pulled from publicly available data via competitive websites. |
Table 7. Curb compatibility matrix - electric heat(a)
Tons | Foundation Model No. | Voyager Light Commercial Model No. | Carrier Model No. |
15 | E*C180 | TCD180E, TCD180F, TSD180F, THD180F, TCD181B, TCD181C, TCD181E, TCD181F, TSD180G, TSH180G, THD180G, THH180G | 50TJ016, 50TM016, 50DP016, 50HJ017 |
17½ | E*C210 | TCD210A, TCD210B, TCD210E, TCD210F, TSD210F, THD210F, TCD211B, TCD211C, TCD211E, TCD211F, TSD210G, TSH210G, THD210G, THH210G | 50DP020, 50TJ020, 50TM020 |
20 | E*C240 | TCD240A, TCD240B, TCD240E, TCD240F, TSD240F, THD240F, TCD241B, TCD241C, TCD241E, TCD241F, TSD240G, TSH240G, THD240G, THH240G | 50TJ024, 50TM025, 50HJ025 |
25 | E*C300 | TCD300B, TCD300E, TCD300F, TSD300F, THD300F, TCD301C, TCD301E, TCD301F, TSD300G, TSH300G, THD300G, THH300G | 50TJ028, 50TM028 |
(a) Data is subject to change. Data pulled from publicly available data via competitive websites. |
Trane and American Standard create comfortable, energy efficient indoor environments for commercial and residential applications. For more information, please visit trane.com or americanstandardair.com.
Trane and American Standard have a policy of continuous product and product data improvement and reserve the right to change design and specifications without notice. We are committed to using environmentally conscious print practices.
RT-PRC069F-EN 03 Dec 2022
Supersedes RT-PRC069E-EN (Jun 2020)
©2022
File Info : application/pdf, 2 Pages, 987.35KB
DocumentDocumentReferences
Acrobat Distiller 22.0 (Windows)Related Documents
![]() |
Trane Precedent High Efficiency Rooftop Units: Quick Reference Guide A quick reference guide for Trane Precedent High Efficiency 3 to 5 Tons Packaged Rooftop Units, covering cooling and gas/electric performance, electrical data, and dimensional information. |
![]() |
Trane RAUJ Split System Cooling Condensers and Remote Chillers Product Catalog Explore the Trane RAUJ series of Split System Cooling Condensers and Remote Chillers, available from 20 to 120 tons. This comprehensive product catalog details advanced features, technical specifications, performance data, and essential application considerations for efficient and reliable HVAC solutions. |
![]() |
Trane Water Source Heat Pump Axiom GEH/V Catalog Explore the Trane Axiom Water Source Heat Pump (WSHP) catalog, featuring GEH and GEV models. This document details specifications, features, and benefits of these efficient comfort solutions, ranging from 0.5 to 25 tons, designed for various applications. |
![]() |
Trane Water Source Heat Pump Axiom GEH/V Installation, Operation, and Maintenance Manual Comprehensive guide for the installation, operation, and maintenance of Trane's Axiom™ Horizontal/Vertical Water Source Heat Pump (GEH/V*) models, covering units from 0.5 to 25 Tons, 50/60 Hz. Includes safety warnings, environmental considerations, model number descriptions, and detailed operational procedures. |
![]() |
Trane Foundation™ Packaged Rooftop Air Conditioners Installation, Operation, and Maintenance Guide This comprehensive manual provides essential guidance for the installation, operation, and maintenance of Trane Foundation™ Packaged Rooftop Air Conditioners. Designed for cooling-only applications with electric heat, these units are available in capacities ranging from 15 to 25 tons, operating at 60 Hz. |
![]() |
Installation Instructions: Trane Manual Fresh Air Damper for Precedent Rooftop Units Step-by-step installation guide for the Trane FIADMPR003* Manual Fresh Air Damper, designed for Precedent™ Packaged Rooftop Units (12.5 to 25 Tons). Includes safety warnings, inspection procedures, installation steps, and airflow data tables. |
![]() |
Trane Foundation Packaged Rooftop Units: 15-25 Ton Cooling & Gas/Electric Specifications Comprehensive quick reference guide for Trane Foundation™ packaged rooftop units (15-25 tons) covering cooling and gas/electric performance, electrical data, fan specifications, dimensions, clearances, and curb compatibility. |
![]() |
Trane Precedent Packaged Rooftop Air Conditioners Installation, Operation, and Maintenance Manual Comprehensive guide for the installation, operation, and maintenance of Trane Precedent Electric/Electric Packaged Rooftop Air Conditioners, covering models from 5 to 10 Tons, 50 Hz. Includes safety warnings, model number descriptions, general information, pre-installation procedures, unit dimensions, and detailed operational instructions. |