Packaged Rooftop Units Foundation™

Cooling and Gas/Electric

15 to 25 Tons

List of Options

Note: Most Factory Installed Options are available for downflow air discharge units only. Verify with ordering system for availability.

Table 1. List of options

Factory Installed Options Field Installed Options
Barometric Relief (a),(b) 2-in MERV 13 Pleated Filters
Complete Coat™ Microchannel Condenser Coil Crankcase Heater (25 Tons)
Condensate Overflow Switch
Economizer - Standard/Downflow(b) Economizer - Standard/Horizontal
Economizer - Low Leak/Downflow(b) Economizer - Low Leak/Horizontal
Electric Heaters Hail Guard
Manual Outside Air Damper High Altitude Kit
Motorized Outside Air Damper High and Low Static Drive Kit
Multi-Speed Oversized Motor LP Conversion Kit
Reference or Comparative Enthalpy Economizer Powered Exhaust
Model Number: ECC Used With: Cooling Only (Electric Heat Optional) Stainless Steel Heat Exchanger with 10 Year Warranty Remote Potentiometer
Model Number: GCC Used With: Gas Heat Unit Through the Base Electrical Access Roof Curb
Through the Base Gas Piping Thermostat
Unit Mounted Non-Fused Disconnect Switch(c)
(a) Requires an economizer.
(b) Some field set up required.
(c) Must be ordered with Through-the-Base Electrical option.

December 2022

RT-PRC069F-EN

Table 2. 15 to 25 ton packaged rooftop performance data (gas or electric heat)

Nominal Size (Ton) Cooling Performance(a) 15 17.5 20 25
ECC GCC ECC GCC ECC GCC ECC GCC
Gross Cooling Capacity (MBh) 180,000 206,000 244,000 268,000 268,000
AHRI Net Cooling Capacity (MBh) 171,000 194,000 214,000 252,000 280,000 280,000
Nominal Airflow CFM/AHRI Rated CFM 5,400 6,650 7,000 8,000 8,000
EER 11 11 10 13.2 10 13.2 9.8 13.2
IEER (Multi-Speed Fan) 14.2 14.2 13.2 13.2 9.2 13.2
Gas Heating Performance(b)
Low Heat (Input/Output) - (MBh) 240,0/194,0 240,0/194,0 240,0/194,0 240,0/194,0
Medium Heat (Input/Output) - (MBh) 320,0/259,0 320,0/259,0 320,0/259,0 320,0/259,0
High Heat (Input/Output) - (MBh) 380,0/308,0 (Downflow), 350,0/284,0 (Horizontal)(c) 380,0/308,0 (Downflow), 350,0/284,0 (Horizontal)(c) 380,0/308,0 (Downflow), 350,0/284,0 (Horizontal)(c) 380,0/308,0 (Downflow), 350,0/284,0 (Horizontal)(c)
Other Information
Net Weight (Lbs) - Gas Heat 2013 2028 2025 2061
Net Weight (Lbs) - Electric Heat 1850 1855 1860 1896
Filters - Type Furnished Number and Size Throwaway (8) 20x25x2 Throwaway (8) 20x25x2 Throwaway (8) 20x25x2 Throwaway (8) 20x25x2
(a) Cooling Performance is rated at 95°F ambient, 80°F entering dry bulb, 67°F entering wet bulb.
(b) Verify option availability in product data catalog.
(c) For 17.5T high heat option, input rate will de-rate from downflow to horizontal.

Table 3. Unit MCA and MOP electrical data (standard indoor fan motor - cooling or gas heat)

E/GCC Volts MCA(a) MOP
208-230/3 79 100
460/3 36 45
575/3 30 35
208-230/3 92 110
210 460/3 40 50
575/3 33 40
208-230/3 101 125
240 460/3 50 60
575/3 39 50
208-230/3 133 175
300 460/3 58 70
575/3 46 60
(a) Values do not include Power Exhaust accessory.

Table 4. Unit indoor fan data

E/GCC Volts Standard HP - RPM Oversized HP - RPM
208-230/3
460/3 3-1750 5-3450 7.5-3450
180 575/3 5-3450
208-230/3
460/3 5-3450 7.5-3450
210 575/3
208-230/3
460/3 5-3450 7.5-3450
240 575/3
208-230/3
300 460/3 7.5-3450 10-1750
575/3

Table 5. Unit dimensional data

15 to 25 Ton
Unit Length UL 123 1/8
Unit Width UW 86 15/16
Unit Height UH 58 5/8
Clearance C1 60
Clearance C2 48
Clearance C3 36
Clearance C4 68
Clearance C5 72
Curb Length CL 117 3/16
Curb Width CW 81
Supply Length SL(a) 28 9/16
Supply Width SW(a) 69 1/2
Return Length RL(a) 22 1/4
Return Width RW(a) 77
(a) Dimensions are for curb openings and not duct inserts. Reference the product catalog for duct insert dimensions.

Diagram showing dimensions: C1, C2, C3, C4, C5, CL, CW, RL, RW, SL, SW, UL, UW, UH.

Table 6. Curb compatibility matrix - gas heat(a)

Tons Foundation Model No. Voyager Light Commercial Model No. Carrier Model No.
15 G*C180 YCD180E, YCD180F, YSD180F, YHD180F, YCD181B, YCD181C, YCD181E, YCD181F, YSD180G, YSH180G, YHD180G, YHH180G 48TJD016, 48TJE016, 48TJF016, 48HJD017, 48HJF017, 48TMD016, 48TMF016, 48DP016, 48DR016
17½ G*C210 YCD210A, YCD210B, YCD210E, YCD210F, YSD210F, YHD210F, YCD211B, YCD211C, YCD211E, YCD211F, YSD210G, YSH210G, YHD210G, YHH210G 48TJD020, 48TJF020, 48TMD020, 48TMF020, 48DP020
20 G*C240 YCD240A, YCD240B, YCD240E, YCD240F, YSD240F, YHD240F, YCD241B, YCD241C, YCD241E, YCD241F, YSD240G, YSH240G, YHD240G, YHH240G 48TJD024, 48TJE024, 48TJF024, 48TMD025, 48TMF025, 48HJD025, 48HJF025
25 G*C300 YCD300B, YCD300E, YCD300F, YSD300F, YHD300F, YCD301C, YCD301E, YCD301F, YSD300G, YSH300G, YHD300G, YHH300G 48TJD028, 48TJE028, 48TJF028, 48TMD028, 48TMF028
(a) Data is subject to change. Data pulled from publicly available data via competitive websites.

Table 7. Curb compatibility matrix - electric heat(a)

Tons Foundation Model No. Voyager Light Commercial Model No. Carrier Model No.
15 E*C180 TCD180E, TCD180F, TSD180F, THD180F, TCD181B, TCD181C, TCD181E, TCD181F, TSD180G, TSH180G, THD180G, THH180G 50TJ016, 50TM016, 50DP016, 50HJ017
17½ E*C210 TCD210A, TCD210B, TCD210E, TCD210F, TSD210F, THD210F, TCD211B, TCD211C, TCD211E, TCD211F, TSD210G, TSH210G, THD210G, THH210G 50DP020, 50TJ020, 50TM020
20 E*C240 TCD240A, TCD240B, TCD240E, TCD240F, TSD240F, THD240F, TCD241B, TCD241C, TCD241E, TCD241F, TSD240G, TSH240G, THD240G, THH240G 50TJ024, 50TM025, 50HJ025
25 E*C300 TCD300B, TCD300E, TCD300F, TSD300F, THD300F, TCD301C, TCD301E, TCD301F, TSD300G, TSH300G, THD300G, THH300G 50TJ028, 50TM028
(a) Data is subject to change. Data pulled from publicly available data via competitive websites.

Trane and American Standard create comfortable, energy efficient indoor environments for commercial and residential applications. For more information, please visit trane.com or americanstandardair.com.

Trane and American Standard have a policy of continuous product and product data improvement and reserve the right to change design and specifications without notice. We are committed to using environmentally conscious print practices.

RT-PRC069F-EN 03 Dec 2022

Supersedes RT-PRC069E-EN (Jun 2020)

©2022

Models: RT-PRC069F-EN Precedent Rooftop Units, RT-PRC069F-EN, Precedent Rooftop Units, Rooftop Units

File Info : application/pdf, 2 Pages, 987.35KB

PDF preview unavailable. Download the PDF instead.

RT-PRC069F-EN 12032022

References

Acrobat Distiller 22.0 (Windows)

Related Documents

Preview Trane Precedent High Efficiency Rooftop Units: Quick Reference Guide
A quick reference guide for Trane Precedent High Efficiency 3 to 5 Tons Packaged Rooftop Units, covering cooling and gas/electric performance, electrical data, and dimensional information.
Preview Trane RAUJ Split System Cooling Condensers and Remote Chillers Product Catalog
Explore the Trane RAUJ series of Split System Cooling Condensers and Remote Chillers, available from 20 to 120 tons. This comprehensive product catalog details advanced features, technical specifications, performance data, and essential application considerations for efficient and reliable HVAC solutions.
Preview Trane Water Source Heat Pump Axiom GEH/V Catalog
Explore the Trane Axiom Water Source Heat Pump (WSHP) catalog, featuring GEH and GEV models. This document details specifications, features, and benefits of these efficient comfort solutions, ranging from 0.5 to 25 tons, designed for various applications.
Preview Trane Water Source Heat Pump Axiom GEH/V Installation, Operation, and Maintenance Manual
Comprehensive guide for the installation, operation, and maintenance of Trane's Axiom™ Horizontal/Vertical Water Source Heat Pump (GEH/V*) models, covering units from 0.5 to 25 Tons, 50/60 Hz. Includes safety warnings, environmental considerations, model number descriptions, and detailed operational procedures.
Preview Trane Foundation™ Packaged Rooftop Air Conditioners Installation, Operation, and Maintenance Guide
This comprehensive manual provides essential guidance for the installation, operation, and maintenance of Trane Foundation™ Packaged Rooftop Air Conditioners. Designed for cooling-only applications with electric heat, these units are available in capacities ranging from 15 to 25 tons, operating at 60 Hz.
Preview Installation Instructions: Trane Manual Fresh Air Damper for Precedent Rooftop Units
Step-by-step installation guide for the Trane FIADMPR003* Manual Fresh Air Damper, designed for Precedent™ Packaged Rooftop Units (12.5 to 25 Tons). Includes safety warnings, inspection procedures, installation steps, and airflow data tables.
Preview Trane Foundation Packaged Rooftop Units: 15-25 Ton Cooling & Gas/Electric Specifications
Comprehensive quick reference guide for Trane Foundation™ packaged rooftop units (15-25 tons) covering cooling and gas/electric performance, electrical data, fan specifications, dimensions, clearances, and curb compatibility.
Preview Trane Precedent Packaged Rooftop Air Conditioners Installation, Operation, and Maintenance Manual
Comprehensive guide for the installation, operation, and maintenance of Trane Precedent Electric/Electric Packaged Rooftop Air Conditioners, covering models from 5 to 10 Tons, 50 Hz. Includes safety warnings, model number descriptions, general information, pre-installation procedures, unit dimensions, and detailed operational instructions.