0 to 25% Manual Fresh Air Damper

Precedent™ Packaged Rooftop Units 12.5 to 25 Tons

Model Numbers: FIADMPR003*

Used With: Precedent D cabinet units (Digit 39 = D)

Safety Warnings

WARNING: Only qualified personnel should install and service the equipment. The installation, starting up, and servicing of heating, ventilating, and air-conditioning equipment can be hazardous and requires specific knowledge and training. Improperly installed, adjusted or altered equipment by an unqualified person could result in death or serious injury. When working on the equipment, observe all precautions in the literature and on the tags, stickers, and labels that are attached to the equipment.

Warnings, Cautions, and Notices

Read this manual thoroughly before operating or servicing this unit. Safety advisories appear throughout this manual as required. Your personal safety and the proper operation of this machine depend upon the strict observance of these precautions.

The three types of advisories are defined as follows:

  • WARNING: Indicates a potentially hazardous situation which, if not avoided, could result in death or serious injury.
  • CAUTION: Indicates a potentially hazardous situation which, if not avoided, could result in minor or moderate injury. It could also be used to alert against unsafe practices.
  • NOTICE: Indicates a situation that could result in equipment or property-damage only accidents.

Important Environmental Concerns

Scientific research has shown that certain man-made chemicals can affect the earth's naturally occurring stratospheric ozone layer when released to the atmosphere. In particular, several of the identified chemicals that may affect the ozone layer are refrigerants that contain Chlorine, Fluorine and Carbon (CFCs) and those containing Hydrogen, Chlorine, Fluorine and Carbon (HCFCs). Not all refrigerants containing these compounds have the same potential impact to the environment. Trane advocates the responsible handling of all refrigerants.

Important Responsible Refrigerant Practices

Trane believes that responsible refrigerant practices are important to the environment, our customers, and the air conditioning industry. All technicians who handle refrigerants must be certified according to local rules. For the USA, the Federal Clean Air Act (Section 608) sets forth the requirements for handling, reclaiming, recovering and recycling of certain refrigerants and the equipment that is used in these service procedures. In addition, some states or municipalities may have additional requirements that must also be adhered to for responsible management of refrigerants. Know the applicable laws and follow them.

WARNING: Proper Field Wiring and Grounding Required!

Failure to follow code could result in death or serious injury. All field wiring MUST be performed by qualified personnel. Improperly installed and grounded field wiring poses FIRE and ELECTROCUTION hazards. To avoid these hazards, you MUST follow requirements for field wiring installation and grounding as described in NEC and your local/state/national electrical codes.

WARNING: Personal Protective Equipment (PPE) Required!

Failure to wear proper PPE for the job being undertaken could result in death or serious injury. Technicians, in order to protect themselves from potential electrical, mechanical, and chemical hazards, MUST follow precautions in this manual and on the tags, stickers, and labels, as well as the instructions below:

  • Before installing/servicing this unit, technicians MUST put on all PPE required for the work being undertaken (Examples; cut resistant gloves/ sleeves, butyl gloves, safety glasses, hard hat/bump cap, fall protection, electrical PPE and arc flash clothing). ALWAYS refer to appropriate Safety Data Sheets (SDS) and OSHA guidelines for proper PPE.
  • When working with or around hazardous chemicals, ALWAYS refer to the appropriate SDS and OSHA/GHS (Global Harmonized System of Classification and Labeling of Chemicals) guidelines for information on allowable personal exposure levels, proper respiratory protection and handling instructions.
  • If there is a risk of energized electrical contact, arc, or flash, technicians MUST put on all PPE in accordance with OSHA, NFPA 70E, or other country-specific requirements for arc flash protection, PRIOR to servicing the unit. NEVER PERFORM ANY SWITCHING, DISCONNECTING, OR VOLTAGE TESTING WITHOUT PROPER ELECTRICAL PPE AND ARC FLASH CLOTHING. ENSURE ELECTRICAL METERS AND EQUIPMENT ARE PROPERLY RATED FOR INTENDED VOLTAGE.

WARNING: Follow EHS Policies!

Failure to follow instructions below could result in death or serious injury.

  • All Trane personnel must follow the company's Environmental, Health and Safety (EHS) policies when performing work such as hot work, electrical, fall protection, lockout/tagout, refrigerant handling, etc. Where local regulations are more stringent than these policies, those regulations supersede these policies.
  • Non-Trane personnel should always follow local regulations.

WARNING: R-454B Flammable A2L Refrigerant!

Failure to use proper equipment or components as described below could result in equipment failure, and possibly fire, which could result in death, serious injury, or equipment damage. The equipment described in this manual uses R-454B refrigerant which is flammable (A2L). Use ONLY R-454B rated service equipment and components. For specific handling concerns with R-454B, contact your local representative.

Copyright ©2024 Trane. This document and the information in it are the property of Trane, and may not be used or reproduced in whole or in part without written permission. Trane reserves the right to revise this publication at any time, and to make changes to its content without obligation to notify any person of such revision or change.

Trademarks: All trademarks referenced in this document are the trademarks of their respective owners.

General Information

Carefully review installation instructions. The manual fresh air adjustment panel with the hood is designed to provide up to 25 percent outside air. Once the adjustable panel is set and the hood is installed, a fixed quantity of outside air can be introduced into the conditioned space.

Inspection

  1. Unpack all components of the kit.
  2. Check carefully for shipping damage. If any damage is found, report it immediately, and file a claim against the transportation company.

Installation

WARNING: Hazardous Voltage w/Capacitors!

Failure to disconnect power and discharge capacitors before servicing could result in death or serious injury. Disconnect all electric power, including remote disconnects and discharge all motor start/run capacitors before servicing. Follow proper lockout/tagout procedures to ensure the power cannot be inadvertently energized. Verify with a CAT III or IV voltmeter rated per NFPA 70E that all capacitors have discharged.

  1. Open the unit disconnect switch.
  2. Remove screws securing the fresh air adjustment panel to the unit end panel. Do not discard screws; they will be used in Step 8.
  3. Adjust the amount of fresh air by changing the position of the fresh air adjustment panel. Based on the operating return static pressure. See Table 1 to determine the correct opening for the specified amount of fresh air.
  4. Secure the fresh air adjustment panel to the unit end panel with two screws. Remaining screws will be used in Step 8.
  5. Using the provided screws, assemble the fresh air hood, as illustrated in Figure 1.
  6. Install the filter/mist eliminator into the fresh air hood and secure it in place using three screws in each side. See Figure 1.

Figure 1. Damper assembly

[Diagram Description: The diagram shows the Unit End Panel, Fresh Air Adjustment Panel, Damper Adjustment Screws (2), Mist Eliminator Retaining Screws (Three per Side), and Mist Eliminator. The Mist Eliminator should be installed with the arrow pointing in the direction of airflow. It can be removed for cleaning by unscrewing the retaining screws.]

Note: Install the filter/mist eliminator with the arrow pointing in the direction of the airflow. The filter/mist eliminator can be taken out for cleaning by removing the screws installed in Step 6.

  1. Install the provided gasket onto the hood mounting flange.
  2. Install the fresh air hood onto the end panel of the unit using the six screws removed in Step 2. See Figure 1.
  3. Close the unit disconnect switch.

WARNING: Live Electrical Components!

Failure to follow all electrical safety precautions when exposed to live electrical components could result in death or serious injury. When it is necessary to work with live electrical components, have a qualified licensed electrician or other individual who has been properly trained in handling live electrical components perform these tasks.

Important: Measure the full load amps of the supply fan motor. If the amperage exceeds the motor nameplate value, system CFM may be too high.

  1. In order to lower the motor amperage to the nameplate value, adjust the fresh air damper or fan RPM.

Airflow Data

Table 1. T/YS*180-300, T/YH*150-300 and W/D/G**150-300 manual fresh air accessory airflow

Inches W/OpenReturn Static -- inch W. G. -0.1-0.2-0.3-0.4-0.5-0.6-0.7-0.8-0.9-1.0
180159197221277292352383378438
2197296361415498511586636656717
3318432528610720731819890933997
44315696948049419501053114312111276
5471680830959108611741289140114581573
65117919651113123113981525165917051870
759891010951268142215921731188619582115
W/Open 707105812581462166118351989217022752422

* Before utilizing CFM's listed in this area, refer to Table 2 for maximum allowable fresh air for the unit.

Table 2. Maximum fresh air CFM

UnitMax CFM
T/YH*150, W/D/G**1501250
T/YS*180, T/YH*180, W/D/G**1801500
T/YS*210, T/YH*210, W/D/G**2101750
T/YS*240, T/YH*240, W/D/G**2402000
T/YS*300, T/YH*300, W/D/G**3002500

Trane and American Standard create comfortable, energy efficient indoor environments for commercial and residential applications. For more information, please visit trane.com or americanstandardair.com.

Trane and American Standard have a policy of continuous product and product data improvement and reserve the right to change design and specifications without notice. We are committed to using environmentally conscious print practices.

ACC-SVN285A-EN 15 Sep 2024 (NEW)

Models: FIADMPR003, FIADMPR003 Packaged Rooftop Units, FIADMPR003, Packaged Rooftop Units, Rooftop Units, Units

PDF preview unavailable. Download the PDF instead.

ACC-SVN285A-EN 09152024 Acrobat Distiller 24.0 (Windows)

Related Documents

Preview Trane SWUD Commercial Self-Contained Units: Installation, Operation, and Maintenance Guide (20-110 Tons)
Comprehensive guide to installing, operating, and maintaining Trane SWUD Commercial Self-Contained Units (20-110 Tons) with R-454B refrigerant. Covers safety, installation, operation, maintenance, and troubleshooting.
Preview Trane Precedent Electric Heaters Installation Instructions for Rooftop Units (3-25 Tons)
Comprehensive installation guide for Trane Precedent™ electric heaters integrated into packaged rooftop units, covering models from 3 to 25 tons. Includes safety warnings, component identification, step-by-step installation procedures for various cabinet types (A.0, B.0/C.0, D.0/D.1), wiring, configuration, and temperature rise data.
Preview Trane RAUJ Split System Cooling Condensers and Remote Chillers Product Catalog
Explore the Trane RAUJ series of Split System Cooling Condensers and Remote Chillers, available from 20 to 120 tons. This comprehensive product catalog details advanced features, technical specifications, performance data, and essential application considerations for efficient and reliable HVAC solutions.
Preview Trane Foundation Series Packaged Rooftop Units: Cooling and Gas/Electric 15-25 Tons Quick Reference
A quick reference guide for Trane Foundation Series packaged rooftop units, covering cooling and gas/electric models from 15 to 25 tons. Includes specifications, options, and compatibility data.
Preview Trane Precedent High Efficiency Rooftop Units: Quick Reference Guide
A quick reference guide for Trane Precedent High Efficiency 3 to 5 Tons Packaged Rooftop Units, covering cooling and gas/electric performance, electrical data, and dimensional information.
Preview Trane Water Source Heat Pump Axiom GEH/V Catalog
Explore the Trane Axiom Water Source Heat Pump (WSHP) catalog, featuring GEH and GEV models. This document details specifications, features, and benefits of these efficient comfort solutions, ranging from 0.5 to 25 tons, designed for various applications.
Preview Trane Water Source Heat Pump Axiom GEH/V Installation, Operation, and Maintenance Manual
Comprehensive guide for the installation, operation, and maintenance of Trane's Axiom™ Horizontal/Vertical Water Source Heat Pump (GEH/V*) models, covering units from 0.5 to 25 Tons, 50/60 Hz. Includes safety warnings, environmental considerations, model number descriptions, and detailed operational procedures.
Preview Installation Instructions: Symbio™ 700 Fresh Air Options Module for Trane Precedent™ Rooftop Units
Comprehensive installation guide for the Symbio™ 700 Fresh Air Options Module, designed for Trane and American Standard Precedent™ Packaged Rooftop Units (3 to 25 Tons). Includes safety warnings, parts list, specifications, and step-by-step installation procedures.