Trane Precedent High Efficiency Rooftop Units
Quick Reference Guide
Cooling, Gas/Electric, 3 to 5 Tons Packaged Rooftop Units
Copyright and Trademarks
This document and the information within are the property of Trane and may not be used or reproduced without written permission. Trane reserves the right to revise this publication and make changes to its content without obligation to notify any person. All trademarks referenced are the trademarks of their respective owners.
Revision History
Removed single phase from tables 3 and 4.
Unit Identification
Model Number: THC, YHC
Used With: High Efficiency Cooling Only (Electric Heat Optional), High Efficiency Gas Heat Unit
Publication Date: September 2023
Document Code: RT-PRC074G-EN
Factory Installed Options
The following is a list of factory installed options:
Option | Description |
0-50% Motorized Outside Air Damper | Hot Gas |
Air-Fi® Wireless Communication Interface | Hail Guard |
BACnet® Communication Interface (BCI-R) | Hinged Access Panels |
Barometric Relief | Human Interface - 5-inch Color Touchscreen |
Belt Drive Motor | LonTalk® Communication Interface (LCI) |
Clogged Filter Switch | Manual outside air damper |
Complete Coat™™ (Microchannel Condenser Coil) | MERV 8 Filters |
Condensate Overflow Switch | MERV 13 Filters |
Dehumidification | Powered Convenience Outlet |
Demand Control Ventilation Wiring | ReliaTel™™ Controls |
Discharge Air Temperature Sensing Kit | Stainless Steel Drain Pan |
Economizer - Comparative Enthalpy | Stainless Steel Heat Exchanger |
Economizer - Dry Bulb | Supply, Return, and Plenum Air Smoke Detectors |
Economizer - Low Leak, Dry Bulb | Through-the-Base Electric Provision |
Economizer - Reference Enthalpy | Through-the-Base Gas Provision |
Fan Failure Switch | Unit Mounted Circuit Breaker |
Fault Detection and Diagnostics (FDD); Meets CA Title 24 Requirements | Unit Mounted Non-fused Disconnect |
Frostat ™™ | Unpowered Convenience Outlet |
(a) Verify option availability in ordering system.
Performance Data
Table 2: High efficiency, 3 to 5 tons packaged rooftop performance data (cooling or gas)
Nominal Size (Tons) | Cooling Performance | Gas Heating Performance(d) | ||||||
Supply Air (cfm)(a) | Tot/ Sens Cap (MBh)(b), (c) | SEER/EER | SEER2/EER2(d) | IEER | Low Heat (Input/output) - (MBh) | Medium Heat (Input/output) - (MBH) | High Heat (Input/output) - (MBh) | |
3 | 1,200 | 37.6/27.9 | 15.0 | 14.1/11.7 | N/A | 60.0/48.0 | 80.0/64.0 | 120.0/96.0 |
4 | 1,600 | 49.9/37.0 | 15.0 | 14.7/11.7 | N/A | 60.0/49.0 | 80.0/64.0 | 120.0/97.2 |
5 | 2,000 | 61.0/45.4 | 15.0 | 14.7/11.7 | N/A | 60.0/49.0 | 80.0/64.0 | 130.0/104.0 |
Other Information
Item | 3 Ton | 4 Ton | 5 Ton |
Net Weight (lbs) - Gas Heat | 532 | 711 | 755 |
Net Weight (lbs) - Electric Heat | 480 | 642 | 679 |
Roof Curb | BAYCURB042* | BAYCURB043* | BAYCURB043* |
Unit Cabinet Size | B | C | C |
Filters(e) - Type Furnished | Throwaway | Throwaway | Throwaway |
Number Size Recommended | (2) 20x30x2 | (2) 16x25x2 | (4) 16x25x2 |
(a) Nominal cfm.
(b) Cooling performance is rated at 80/67/95.
(c) All units listed utilize 3-phase voltage.
(d) EER2 and SEER2 are rated at AHRI conditions and calculated in accordance with AHRI Standard 210/240-2023. Airflow and net cooling capacity not shown.
(e) Optional 2-inch MERV 8 and MERV 13 filters also available.
Table 3: Unit MCA and MOP electrical data (standard indoor fan motor) (cooling or gas(a))
T/YHC | Volts | MCA | MOP |
036 | 208-230/3 | 21.0 | 30 |
036 | 460/3 | 12.0 | 15 |
036 | 575/3 | 10.0 | 15 |
048 | 208-230/3 | 26.0 | 35 |
048 | 460/3 | 13.0 | 15 |
048 | 575/3 | 11.0 | 15 |
060 | 208-230/3 | 30.0 | 45 |
060 | 460/3 | 14.0 | 20 |
060 | 575/3 | 11.0 | 15 |
(a) For MCA/MOP of units with electric heat, refer to ordering system.
Table 4: Unit indoor fan data (cooling or gas)
T/YHC | Volts | Standard - HP - RPM | Oversize - HP - RPM |
036 | 208-230/3 | 1 - FIXED | - |
036 | 460/3 | 1 - FIXED | - |
036 | 575/3 | 1 - FIXED | - |
048 | 208-230/3 | 1 - FIXED | - |
048 | 460/3 | 1 - FIXED | - |
048 | 575/3 | 1 - FIXED | - |
060 | 208-230/3 | 1 - FIXED | - |
060 | 460/3 | 1 - FIXED | - |
060 | 575/3 | 1 - FIXED | - |
Table 5: Unit dimensional data
Dimension | B | C |
Unit Length UL | 69 7/8 | 88 5/8 |
Unit Width UW | 44 1/4 | 53 1/4 |
Unit Height UH | 36 1/4 | 40 7/8 |
Clearance C1 | 48 | 48 |
Clearance C2 | 36 | 36 |
Clearance C3 | 36 | 36 |
Clearance C4 | 36 | 36 |
Clearance C5 | 72 | 72 |
Curb Length CL | 65 13/16 | 84 1/2 |
Curb Width CW | 41 7/16 | 50 3/8 |
Supply Length SL(a) | 16 3/4 | 18 1/2 |
Supply Width SW(a) | 17 7/8 | 34 3/8 |
Return Length RL(a) | 14 9/16 | 18 1/4 |
Return Width RW(a) | 25 3/16 | 34 3/8 |
(a) Dimensions are for curb openings and not duct inserts. Reference the product catalog for duct insert dimensions.
About Trane
Trane and American Standard create comfortable, energy efficient indoor environments for commercial and residential applications. For more information, please visit trane.com or americanstandardair.com.
Trane and American Standard have a policy of continuous product and product data improvement and reserve the right to change design and specifications without notice. They are committed to using environmentally conscious print practices.