Infinity Living Submittal Data Sheet
Indoor Unit Model#: EZ-24W-HP230B
Outdoor Unit Model#: EZ-24Z-HP230B
System: 24K DIYCOOL R454B Std. Heat Mini-Split System
Efficiency Ratings
Cooling | Heating | |
---|---|---|
SEER2 | 18.9 | HSPF2-4 8.7 |
EER2 | 9.7 | COP 3.20 |
Cooling Performance
Parameter | Value |
---|---|
Rated Capacity | 24000 Btu/hr |
Min/Max Capacity | 6000 ~ 26500 Btu/hr |
Moisture Removal (L/h) | 3.11 |
Standard Operating Range (°F/°C) | -13 ~ 75 (-15 ~ 50) |
Conditions | Indoor: 80°F DB/67°F WB Outdoor: 95°F DB/75°F WB |
Heating Performance
Parameter | Value (Btu/hr) |
---|---|
1. @ 47°F Rated Capacity | 25000 |
1. @ 47°F Min/Max Capacity | 6200 ~ 28300 |
2. @ 17°F Rated Capacity | 16300 |
3. @ 5°F Rated Capacity / COP | 17000 / 2.08 |
3. @ 5°F Max Capacity | 16100 |
Standard Operating Range (°F/°C) | -13 ~ 122 (-25 ~ 24) |
1. Conditions | Indoor: 70°F DB/60°F WB Outdoor: 47°F DB/43°F WB |
2. Conditions | Indoor: 70°F DB/60°F WB Outdoor: 17°F DB/15°F WB |
3. Conditions | Indoor: 70°F DB/60°F WB Outdoor: 5°F DB/5°F WB |
Indoor Unit Specifications
Parameter | Value |
---|---|
Indoor Air Flow (Turbo/H/M/L/Si) (CFM) | 729.9 / 547.4 / 400.2 / 329.6 / NA |
Indoor Noise Level (Turbo/H/M/L/Si) (dBA) | 51.5 / 45.5 / 40.5 / 26.5 / 21.5 |
Dimension (W×D×H) | 42.60 x 9.21 x 13.27 inch 1082 x 234 x 337 mm |
Package (W×D×H) | 45.47 x 16.34 x 12.40 inch 1155 x 415 x 315 mm |
Net/Gross Weight | 35.49 / 49.60 lbs 16.1 / 22.5 kg |
Outdoor Unit Specifications
Parameter | Value |
---|---|
Compressor Type | ROTARY |
Compressor Model | KTM240D46UKT2 |
Refrigerant | R454B |
Refrigerant Oil Charge (mL) | 620 |
Refrigerant Oil | VG74 |
Outdoor Air Flow (Max) (CFM) | 3000 |
Outdoor Noise Level (dBA) | 61 |
Dimension (W×D×H) | 35.04 x 13.46 x 26.50 inch 890 x 342 x 673 mm |
Package (W×D×H) | 39.17 x 15.67 x 29.13 inch 995 x 398 x 740 mm |
Net/Gross Weight | 95.90 / 117.73 lbs 43.5 / 53.4 kg |
Electrical Specifications
Parameter | Value |
---|---|
Power Supply | 208/230V, 60Hz, 1Ph |
System MCA | 19 |
Connection Wiring | 14#x4 |
System MOCP | 20 |
Compressor RLA | 13.8 |
Outdoor Fan Motor RLA | 0.8 |
Outdoor Fan Motor W | 80 |
Indoor Fan Motor RLA | 0.6 |
Indoor Fan Motor W | 58 |
System Power Input @ Cooling (W) | 2474 (540 ~ 2800) |
System Power Input @ Heating (W) | 2290 (410 ~ 2600) |
Refrigerant Piping Specifications
Parameter | Value |
---|---|
Throttle type (Indoor) | N/A |
Throttle type (Outdoor) | Throttle valve |
Liquid Size | 9.52mm (3/8in) |
Gas Size | 15.9mm (5/8in) |
Max. Piping Length (ft/m) | 164 (50) |
Max. Height Difference (ft/m) | 82 (25) |
Max. Pre-charged Length (ft/m) | 24.6 (7.5) |
Refrigerant Pre-charged Amount (oz/g) | 50.44 (1.43) |
Additional Charge of Refrigerant ((oz/ft)/(g/m)) | 0.32 (30) |
Connection Method | Connector |
Indoor Unit Dimensions
The indoor unit has dimensions W (width), D (depth), and H (height). The diagram shows the unit with specific measurements:
- Width (W): 42.60 inches (1082 mm)
- Depth (D): 9.21 inches (234 mm)
- Height (H): 13.27 inches (337 mm)
A table provides specific dimensions for different capacity models:
Capacity | Body Code | W (inch/mm) | D (inch/mm) | H (inch/mm) |
---|---|---|---|---|
9K | A | 28-3/4in/729mm | 7-7/8in/200mm | 11-1/2in/292mm |
12K | B | 31-5/8in/802mm | 7-7/8in/200mm | 11-5/8in/295mm |
18K | C | 38-1/4in/971mm | 9in/228mm | 12-5/8in/321mm |
24K | D | 42-5/8in/1082mm | 9-1/4in/234mm | 13-1/4in/337mm |
Installation Notes:
Location Selection: The unit's position relative to the mounting plate determines the piping exit direction. Four options are available: left-hand side, right-hand side, left-rear, and right-rear.
Wall Hole Size: When the gas side connective pipe is 5/8in (16mm) or larger, the wall hole should be 3-1/2in (90mm).
Outdoor Unit Dimensions
The outdoor unit is shown from front, side, and top views with various dimensions labeled (W, W1, W2, W3, D, D1, H, H1, H2, A, A1, A2, B1, B2). Key overall dimensions are:
- Width (W3): 35-1/4in (895mm)
- Depth (D1): 13-3/4in (348mm)
- Height (H): 26-1/8in (663mm)
Installation Clearance Requirements:
- Front and sides: 20 inches (500mm) or more clearance required when front and sides of the unit are clear.
- Sides (left/right) and rear: 20 inches (500mm) or more clearance required when any 2 sides of left, right, and rear of the unit are clear.
- Rear: 14 inches (350mm) or more clearance required.
- Sides: 4 inches (100mm) or more clearance required.
The unit meets all spatial requirements shown in the installation clearance requirements.
Features
- Indoor unit TU1 copper coil
- Humidity control
- 1~100% fan speed setting
- WiFi capability: through WiFi dongle or wired controller with built-in WiFi
- OTA (Over-The-Air updates via WiFi dongle)
- Multiple control options available:
- Two-way communication wired controller: 120N(X6)
- Two-way communication wired controller with built-in WiFi: 120N(X6W)
- Infrared wired controller: 120L
- Wireless remote controller
- Third-Party 24V Thermostat*
*24V interface is required.