Zurn Wilkins Model 500XLFC Water Pressure Reducing Valve

With Flanged Connections

Application

The Zurn Wilkins Model 500XLFC is engineered for installation on potable water lines to reduce high inlet pressure to a lower outlet pressure. Its high flow capacity makes it ideal for industrial water lines and commercial water systems. The balanced piston design ensures smooth and responsive reaction to system flow demand changes, while also protecting against inlet pressure fluctuations.

Approvals

Materials

Features

Dimensions & Weights

(Does not include packaging)

SIZECONNECTIONSABCD (approx.)WEIGHT
in.mmin.mmin.mmlbs.kg.
2" (50)FLANGED10 3/8263153813766 1/2" (165)3013.5
2 1/2" (65)FLANGED10 3/8263153813 1/2898" (203)3616.5
3" (80)FLANGED1127917 3/44513 3/4958" (203)5022.5

Diagram shows valve with dimensions labeled A, B, C, and D.

Options

(Suffixes can be combined)

Accessories

Flow Characteristics

The graph displays flow characteristics for the Model 500XLFC (2" thru 3") in standard and metric units. It plots Fall Off (kPa and PSIG) against Flow Rates (GPM and l/s). The graph shows distinct curves for 2" (50mm), 2 1/2" (65mm), and 3" (80mm) sizes. A note indicates that flow curves are based on a 50 psi pressure differential.

Diagram: Flow Characteristics Graph.

Typical Installation

Installation must comply with local codes, manufacturer's instructions, and the Uniform Plumbing Code. Ensure sufficient side clearance for testing and maintenance. The Model 500XLFC can be installed in any position. For pit or vault installations, or indoor applications, specify the "SC" sealed cage option. Multiple installations are recommended for wide demand variations or when pressure reduction exceeds a 4:1 ratio (e.g., 200 psi inlet to 50 psi outlet). CAUTION: Always use a pressure gauge downstream when adjusting the valve to verify the correct pressure setting. Do not bottom the adjustment bolt on the bell housing.

Diagrams illustrate Parallel, Vertical, and Horizontal installation orientations, showing optional pressure gauge and "Y" strainer.

Specifications

The Pressure Reducing Valve is certified to NSF/ANSI/CAN 61. It features a bronze body and bell housing with flanged connections. The valve includes a separate access cover for the plunger and a bolt for adjusting downstream pressure. It utilizes a balanced piston design to reduce pressure in both flow and no-flow conditions. The bronze bell housing and access cap are threaded to the body and do not require ferrous screws. The Pressure Reducing Valve is a ZURN WILKINS Model 500XLFC.

Manufacturer Information

Zurn Industries, LLC | Wilkins
1747 Commerce Way, Paso Robles, CA U.S.A. 93446
Phone: 855-663-9876 | Fax: 805-238-5766
In Canada | Zurn Industries Limited
7900 Goreway Drive, Unit 10, Brampton, Ontario L6T 5W6
Phone: 877-892-5216
Website: www.zurn.com

Document Revision E, Date: 11/19

Document No. REG-500XLFC | Product No. Model 500XLFC

Page 1 of 2, Page 2 of 2 (content combined)

Models: 500XLFC, Water Pressure Reducing Valve with Flanged Connections

File Info : application/pdf, 2 Pages, 534.04KB

PDF preview unavailable. Download the PDF instead.

ZRN3-510XLFC SpecSheet

References

Adobe PDF Library 15.0

Related Documents

Preview Zurn NR3XL Lead-Free Pressure Reducing Valve: Installation, Maintenance, and Repair Guide
Comprehensive guide for the Zurn NR3XL Lead-Free Pressure Reducing Valve, covering installation, inspection, maintenance, repair procedures, and troubleshooting. Includes product specifications and warranty information.
Preview Zurn NR3XL Water Pressure Reducing Valve with Integral By-Pass Check Valve and Strainer
Detailed specifications and installation guide for the Zurn NR3XL, a water pressure reducing valve designed for potable water lines. Features include an integral strainer, by-pass check valve, and low lead cast bronze body. Suitable for residential and commercial applications.
Preview Zurn Wilkins ZW209FP Pressure Reducing Valve Assembly: Installation, Operation, and Maintenance
Comprehensive guide to the Zurn Wilkins ZW209FP fire protection pressure reducing valve assembly, covering installation, start-up, operation, flow characteristics, and maintenance procedures. Includes detailed instructions for main valve and PV-PRD pilot valve.
Preview ZURN Model 350AST Double Check Valve Assembly: Specifications and Application
Comprehensive technical details for the ZURN Model 350AST Double Check Valve Assembly, covering its application in potable water systems, materials, compliance standards, dimensions, weights, flow characteristics, and installation guidelines.
Preview Zurn Carrier Systems: Specification Drainage Engineering Guide
Comprehensive guide to Zurn's Carrier Systems, detailing specifications, product illustrations, installation instructions, options, and technical data for water closet, urinal, and lavatory carriers. Features EZCarry™ technology and various model numbers.
Preview Zurn Wilkins Model 720A Pressure Vacuum Breaker Assembly Specifications and Installation
Detailed information on the Zurn Wilkins Model 720A Pressure Vacuum Breaker Assembly, including its application, standards compliance, materials, features, dimensions, weights, flow characteristics, and installation guidelines for both indoor and outdoor use.
Preview Zurn ZEMS6003PL-ULF Hardwired Automatic Sensor Valve for 0.125 GPF Urinals
Technical specifications and features for the Zurn ZEMS6003PL-ULF, a hardwired automatic sensor flushometer valve for 0.125 GPF urinals. Includes engineering specifications, accessories, and power supply options.
Preview Zurn Z6003 Exposed Flush Valve for Urinals - Specifications and Options
Detailed specifications, features, and configuration options for the Zurn Z6003 Exposed Flush Valve for Urinals, including architectural and engineering details, flow options, and compliance certifications.