ZURN Model NR3XL Water Pressure Reducing Valve with Integral By-Pass Check Valve and Strainer

Application

Ideal for use where Lead-Free* valves are required. Designed for installation on potable water lines to reduce high inlet pressure to a lower outlet pressure. The integral strainer makes this device most suitable for residential and commercial water systems that require frequent cleaning of sediment and debris. The direct acting integral by-pass design prevents buildup of excessive system pressure caused by thermal expansion. The balance piston design enables the regulator to react in a smooth and responsive manner to changes in system flow demand, while at the same time, providing protection from inlet pressure changes. The sealed cage washer and stainless steel adjustment bolt and nut improve corrosion resistance for all applications including below-ground pit installation.

Standards Compliance

Materials

Component Material
Main valve body Low Lead Cast bronze ASTM B 584
Bell housing UV resistant polymer composite
Internals Stainless steel, 300 Series
Stem Low Lead Brass
Elastomers EPDM (FDA approved)
Cartridge Buna nitrile (FDA approved)
Springs Delrin ™, 302 Stainless Steel
Strainer screen 300 Series Stainless Steel

Features

Dimensions & Weights (do not include pkg.)

SIZE CONNECTIONS DIMENSIONS (approximate) WEIGHT
in. mm A in. B in. C in. D in. lbs. kg
1/2 15 SINGLE UNION 4 3/8 6 1/4 1 1/8 2 1/2 64 3 1.5
1/2 15 ROUGH IN 3 3/4 95 SAME AS LESS UNION
1/2 15 LESS UNION 3 1/2 89 6 1/4 1 1/8 29 2 1/2 64 3 1.5
1/2 15 DOUBLE UNION 5 1/4 133 6 1/4 1 1/8 29 2 1/2 64 3 1.5
3/4 20 SINGLE UNION 4 7/16 113 6 1/4 1 1/8 29 2 1/2 64 3 1.5
3/4 20 ROUGH IN 3 3/4 95 SAME AS LESS UNION
3/4 20 LESS UNION 3 1/2 89 6 1/4 1 1/8 29 2 1/2 64 3 1.5
3/4 20 DOUBLE UNION 5 3/8 137 6 1/4 1 1/8 29 2 1/2 64 3 1.5
3/4 20 DOUBLE MALE METER 3 5/8 92 6 1/4 1 1/8 29 2 1/2 64 3 1.5
1 25 SINGLE UNION 4 15/16 125 6 1/4 1 1/8 29 2 1/2 64 4 2
1 25 ROUGH IN 4 1/4 108 SAME AS LESS UNION
1 25 LESS UNION 4 102 6 1/4 1 1/8 29 2 1/2 64 3.5 1.6
1 25 DOUBLE UNION 5 15/16 151 6 1/4 1 1/8 29 2 1/2 64 4 2.0
1 25 DOUBLE MALE METER 4 102 7 3/4 197 1 3/16 30 3 76 4.5 2.1
1 1/4 32 SINGLE UNION 6 3/16 157 7 3/4 197 1 3/16 30 3 76 5.5 2.5
1 1/4 32 ROUGH IN 5 1/4 133 SAME AS LESS UNION
1 1/4 32 LESS UNION 5 127 7 3/4 197 1 3/16 30 3 76 4.5 2.1
1 1/4 32 DOUBLE UNION 7 3/8 187 7 3/4 197 1 3/16 30 3 76 5.5 2.5
1 1/2 40 SINGLE UNION 6 5/16 160 8 1/2 216 1 3/4 45 3 3/4 95 5 2.3
1 1/2 40 ROUGH IN 5 1/4 133 SAME AS LESS UNION
1 1/2 40 LESS UNION 5 127 8 1/2 216 1 1/2 40 3 3/4 95 5.5 2.5
2 50 SINGLE UNION 6 1/4 159 8 1/2 216 1 3/4 45 3 3/4 95 5.5 2.5
2 50 ROUGH IN 5 1/4 133 SAME AS LESS UNION
2 50 LESS UNION 5 127 8 1/2 216 2 51 3 3/4 95 6.7 3

Diagram showing dimensions A, B, C, and D for various NR3XL models.

Options (Suffixes can be combined)

Accessories

Flow Characteristics

Flow curves are based on a 50 psi pressure differential.

MODEL NR3XL 1/2", 3/4" & 1" (STANDARD & METRIC)

Graph showing Pressure Loss (PSIG) vs. Flow Rates (GPM and l/s) for 1/2", 3/4", and 1" NR3XL valves.

MODEL NR3XL 1-1/4", 1-1/2" & 2" (STANDARD & METRIC)

Graph showing Pressure Loss (PSIG) vs. Flow Rates (GPM and l/s) for 1-1/4", 1-1/2", and 2" NR3XL valves.

Typical Installation

Local codes shall govern installation requirements. Unless otherwise specified, the assembly shall be mounted in accordance with the latest edition of the Uniform Plumbing Code. The Model NR3XL may be installed in any position. The assembly shall be installed with sufficient side clearance for testing and maintenance. Multiple installations are recommended for wide demand variations or where the desired pressure reduction is more than 4 to 1 (ie: 200 psi inlet reduced to 50 psi outlet). CAUTION: Anytime a reducing valve is adjusted, a pressure gauge must be used downstream to verify correct pressure setting. Do not bottom adjustment bolt on bell housing.

Diagram illustrating an outdoor installation with a water meter, shut-off valve, and the NR3XL regulator.
Diagram illustrating NR3XLDUPEX installation with a water meter, shut-off valve, expansion tank, T&P valve, water heater, and the NR3XL regulator.
Diagram illustrating a typical installation with a hose bibb, strainer, vacuum breaker, and the NR3XL regulator.

Specifications

The Water Pressure Reducing Valve shall be certified to NSF/ANSI 61 and ASSE® Listed 1003, available with single union, double union and less union end connections. The main body shall be low lead cast bronze (ASTM B 584) alloy. The bell shall be composite plastic. The cartridge shall be acetal and incorporate an integral seat. The seat disc elastomer shall be EPDM. The assembly shall be accessible for maintenance without removing the device from the line. The Water Pressure Reducing Valve shall be a ZURN WILKINS Model NR3XL.

Models: NR3XL Pressure Reducing Valve, NR3XL, Pressure Reducing Valve, Reducing Valve, Valve

File Info : application/pdf, 2 Pages, 453.35KB

PDF preview unavailable. Download the PDF instead.

69eb8cc4-80d5-4d6e-9744-0e69d104c991

References

Adobe PDF Library 15.0 Adobe InDesign 16.1 (Windows)

Related Documents

Preview Zurn Wilkins 500XLFC Water Pressure Reducing Valve Technical Specifications
Detailed technical specifications for the Zurn Wilkins Model 500XLFC Water Pressure Reducing Valve, designed for industrial and commercial potable water systems. Features include bronze construction, flanged connections, and balanced piston design.
Preview Zurn NR3XL Lead-Free Pressure Reducing Valve: Installation, Maintenance, and Repair Guide
Comprehensive guide for the Zurn NR3XL Lead-Free Pressure Reducing Valve, covering installation, inspection, maintenance, repair procedures, and troubleshooting. Includes product specifications and warranty information.
Preview ZURN Model 350AST Double Check Valve Assembly: Specifications and Application
Comprehensive technical details for the ZURN Model 350AST Double Check Valve Assembly, covering its application in potable water systems, materials, compliance standards, dimensions, weights, flow characteristics, and installation guidelines.
Preview Zurn Wilkins ZW209FP Pressure Reducing Valve Assembly: Installation, Operation, and Maintenance
Comprehensive guide to the Zurn Wilkins ZW209FP fire protection pressure reducing valve assembly, covering installation, start-up, operation, flow characteristics, and maintenance procedures. Includes detailed instructions for main valve and PV-PRD pilot valve.
Preview Zurn Wilkins Model 720A Pressure Vacuum Breaker Assembly Specifications and Installation
Detailed information on the Zurn Wilkins Model 720A Pressure Vacuum Breaker Assembly, including its application, standards compliance, materials, features, dimensions, weights, flow characteristics, and installation guidelines for both indoor and outdoor use.
Preview Zurn ZEMS6003PL-ULF Hardwired Automatic Sensor Valve for 0.125 GPF Urinals
Technical specifications and features for the Zurn ZEMS6003PL-ULF, a hardwired automatic sensor flushometer valve for 0.125 GPF urinals. Includes engineering specifications, accessories, and power supply options.
Preview Zurn Z6003 Exposed Flush Valve for Urinals - Specifications and Options
Detailed specifications, features, and configuration options for the Zurn Z6003 Exposed Flush Valve for Urinals, including architectural and engineering details, flow options, and compliance certifications.
Preview ZURN AquaSense® ZG6913 & ZG6915 Series Sensor-Operated Faucets: Installation, Operation, Maintenance, and Parts Manual
Comprehensive guide for ZURN AquaSense® ZG6913 and ZG6915 sensor-operated faucets, covering installation, operation, maintenance, troubleshooting, and parts. Features battery-powered, hardwired, and connected options.