Installation guide

Back up power module

Type EKE 2U

UKCA Icon

Introduction

EKE 2U module is an optional energy storage device. The module can provide enough energy during power failure to the stepper controller to ensure closure of the electronic valves. It can be used with one or two controllers depending on the application.
State of Health (SOH) function of EKE 2U gives feedback to controllers to detect the status of the backup module and lets the controller know if the backup is Ready to use, Charging or Failed.
Power Failure signal (PF): This signal should be connected to controller only if the controller cannot detect power failure by itself. Not required for EKE controllers.
Load Switch, EKE 2U can deliver power backup for 2 valves. While using more than 1 valve the load switch can be changed to deliver more energy.
Compatible Controllers: Danfoss EKE series and MCX controllers. For other controllers, please contact Danfoss.

Danfoss 080G5555 Back up Power Module - QR CodeMore info

Wiring Diagram

Danfoss 080G5555 Back up Power Module - 1

  1. LOAD SWITCH
  2. SoH communication (optional)

Info for UK customers only: Danfoss Ltd., 22 Wycombe End, HP9 1NB, GB

Danfoss 080G5555 Back up Power Module - Bar Code 080R9346

Danfoss logo5

Dimensions in mm
EKE 2U

Danfoss 080G5555 Back up Power Module - 2

Weight: 233 gram

Technical specifications
Nominal input voltage 24 V DC / 24 V AC
Input voltage range 20 – 40 V DC, 19 – 29 V AC
Frequency DC / AC 50 … 60 Hz + /-10%
Overvoltage capability < 42 V DC
< 30 V AC
Nominal input power DC: 15 VA, AC: 25 VA
Protection class II
Inrush current < 15 A
Standby current @ 24 V DC ~ 0.1 A
Nominal output voltage (UNOM) 24.0 V DC ± 2%
Nominal output current (INOM) 2 A
Maximum output current on standby 30 mA
Current limiting 2.5 A ± 10%
Parallel connection for time increase yes
Series connection no
Capacitor charging current @ 24 V DC < 1 A
Charging time ~ 2.5 min from fully discharged state
Max Voltage / current at X2 (open collector) 24V / 8.5 mA
Ambient temperature during operation TAMB = -25 °C – + 60 °C
Storage temperature – 30 °C – + 70 °C
Humidity < 90 % rH, no condensation.
Environmental pollution Type 2
Protection degree IP 20
Altitude Up to 2000 m
Immunity to voltage Surges EN 61000-4-5 Level 3 in/out
Level 2 signals
Assembly On DIN rail
Overvoltage protection Category II
Lifespan >90000 hours (10 years) @ 35 °C and >3 years @ 50 °C
MTBF > 500.000 h @ 25 °C according to IEC 61709 / SN 29500

Recommended Load Switch Position

Valve Type Number of valves
1 Valve 2 Valves
ETS 5M / ETS 6 POS B POS A
ETS Colibri POS B POS B
ETS 12.5 to 100, ETS 250, ETS 400 POS B POS B
KVS 15/42 POS B POS B
CCMT / CCM POS B POS A

Caution Icon 15 Important Notes :

  • Load switch POS A and POS B defines the max energy supplied by the EKE 2U as power backup.
  • POS A delivers more energy than POS B. Using at POS B further increases lifetime of EKE 2U.
  • Load switch has default position POS A and POS A will work throughout all combinations.
State of Health (SOH) Function LEDs
Ready Backup is ready and controller can start operating valves. Green on
Red off
Charge Backup module is charging. Controller must not operate valves. Green flashing.
1 Hz Red off
Replace Backup module needs to be replaced. But valves can be operated. Green: Ready or Charge
Red on.
Failure Backup module does not work. Controller can still operate valves. But at a power loss no guarantee that the valves can close. Green off
Red flashing. 1Hz
Cable length

EKE 2U supports the following max. cable length.

Cable length
[m]
Wire size min. / max.
[mm²]
Power supply Input max. 5 0.2 / 1.5
Backup output max. 5 0.2 / 1.5
Digital outputs max. 5 0.2 / 1.5
Cable and wiring
  • Keep power and battery backup cable separate from SOH cable
General features and warnings
Plastic housing features

-DIN rail mounting
-Self-extinguishing V0

Other features

-Operating conditions CE: -25T60, 90% RH non-condensing
-Storage conditions: -30T70, 90% RH non-condensing
-Max duty-cycle Charge/Discharge at nominal load 15min ON / 10s OFF
-To be integrated in Class I and/or II appliances
-Index of protection: IP 20
-Period of electric stress across insulating parts: long
-Suitable for using in a normal pollution environment
-Immunity against voltage surges: category II

Safety and approvals

This product is designed to comply with the following standards:
-EN61000-6-1, EN61000-6-3 (immunity for residential, commercial and light-industrial environments)
-EN61000-6-2, EN61000-6-4 (immunity and emission standard for industrial environments)
-UL 61010
-IEC 61010-2-201:2013

General warnings

-Every use that is not described in this manual is considered incorrect and is not authorized by the manufacturer
-Verify that the installation and operating conditions of the device respect those specified in the manual, especially concerning the supply voltage and environmental conditions
-This device contains live electrical components. All service and maintenance operations must therefore be performed by qualified personnel
-The device must not be used as a safety device
-Liability for injury or damage caused by the incorrect use of the device lies solely with the user
-The manufacture’s guarantee expires in the event of improper use

Caution Icon 15 Installation warnings

-Intended mounting position: vertical
-Installation must comply with local standards and legislation
-Before working on the electrical connections, disconnect the device from the main power supply
-Before carrying out any maintenance operations on the device, disconnect all electrical connections
-For safety reasons the appliance must be fitted inside an electrical panel with no live parts accessible
-Do not expose the device to continuous water sprays or to a relative humidity greater than 90%
-Avoid exposure to corrosive or pollutant gases, natural elements, environments where explosives or mixes of flammable gases are present, dust, strong vibrations or shock, large and rapid fluctuations in ambient temperature that might cause condensation in combination with high humidity, strong magnetic and/or radio interference (e.g. transmitting antennae)
-When connecting loads be aware of the maximum current for each relay and connector
-Use cable ends suitable for the corresponding connectors. After tightening connector screws, tug the cables gently to check their tightness
-Use appropriate data communication cables. Refer to the EKE data sheet for the kind of cable to be used and setup recommendations
-Minimize the length of probe and digital input cables as much as possible and avoid spiral routes around power devices. Separate from inductive loads and power cables to avoid possible electromagnetic noises
-Avoid touching or nearly touching the electronic components fitted on the board to avoid electrostatic discharges
-Use copper cables for operating temperatures >75 °C (ambient temperature ≤ 60 °C)

Product warnings
  • Use a class II category transformer for 24 V AC power supply
  • Connecting any output signals to mains voltage will permanently damage the controller

Danfoss 080G5555 Back up Power Module - 3

DIN rail mounting / demounting

The unit can be mounted onto a 35 mm DIN rail simply by snapping it into place and securing it with a stopper to prevent sliding. It is demounted by gently pulling the stirrup located in the base of the housing.

Danfoss 080G5555 Back up Power Module - 4 Danfoss 080G5555 Back up Power Module - 5

Sharing Power supply and SOH signal
  • Power sharing is allowed between EKE 2U power backup module and EKE SH controllers provided power supply is DC.
  • Max 2 EKE controller should be connected to 1 EKE 2U
  • SOH signal should not be shared. It should be connected to only one EKE controller and the readouts should be taken from this controller.

Danfoss 080G5555 Back up Power Module - 6

SHARING EKE 2U WITH 2 CONTROLLERS

  1. DC Power supply­
  2. Danfoss
    80G295.10
  3. SoH Signal
Quick guide for parameter selection in EKE controllers

Start : Main switch= Off

Make sure that main switch is OFF before changing the settings. The setting will depend on the system requirement.
Parameter: R012 Main Switch

Danfoss - Blue Arrow

Select DI2 configuration

Set DI2 to PWR backup status. This should be used only if EKE 2U SOH is connected to DI2 of EKE 1.
Enables EKE 1to read SOH signal.
Parameter: O022 DI2 configuration

Danfoss - Blue Arrow

Battery Alarm

Battery alarm function must be set ON/OFF depending on the signal needed. If set to On then EKE 1 will send alarm if EKE 2U battery is low.
Parameter: A034 Battery alarm

Danfoss - Blue Arrow

Actual battery voltage read out

Using parameter U101 actual battery voltage of EKE 2U can be read through EKE 1.
Parameter: U101 Actual battery voltage

Danfoss - Blue Arrow

Power backup status readout

Using parameter U115. Power backup status of EKE 2U can be read from EKE 1. Only applicable if SOH is connected to DI2.
Parameter: U115 PWR Backup status

Danfoss - Blue Arrow

Dl1=ON

Set main switch back to ON status to start the controller.
Parameter: R012 Main switch

Related products
Power Supply EKE series controllers Stepper motor valves
Danfoss 080G5555 Back up Power Module - Danfoss 080G5555 Back up Power Module - 8 Danfoss 080G5555 Back up Power Module - 9
AK-PS
Input: 100 – 240 V AC, 45 – 65 Hz
Output: 24 V DC: available with 18 VA, 36 VA and 60 VAACCTRD
Input: 230 V AC, 50 – 60 Hz
Output: 24 V AC, available with 12 VA, 22 VA and 35 VA
EKE series preprogrammed superheat controllers/ drivers for controlling electric expansion valves. EKE is compatible with Danfoss stepper motor valves i.e Danfoss ETS 6, ETS, KVS,ETS Colibri®, KVS colibri®, CTR, CCMT

© Danfoss | Climate Solutions | 2021.09           AN325741621547en-000803

Documents / Resources

Danfoss 080G5555 Back up Power Module [pdf] Installation Guide
Type EKE 2U, 080R9346, 080G5555, 080G5555 Back Up Power Module, Back Up Power Module, Power Module

References

Leave a comment

Your email address will not be published. Required fields are marked *