LUTRON-LOGO

LUTRON CNT10176 Push Button Boost Timer

LUTRON-CNT10176-Push-Button-Boost-Timer-PRODUCT

Specifications
  • Model Numbers: CNT10176 (PBT), CNT10175 (PBL), CNT10174 (PTL)
  • Control Types: Push Button Boost Timer (PBT), Push Button
    Point-of-Use Control (PBL), Percent Timer Control (PTL)
  • Compatibility: Works with ERV units
  • Operating Time Options: 20, 40, or 60 minutes
  • Wiring Size: Maximum 18 gauge solid wire
  • Cover Plate: Lutron DecoraTM cover plate included

Product Usage Instructions

Push Button Point-of-Use Control (PBL) Operation
The PBL control works in conjunction with Percentage Timer  Control (PTL) or Push Button Timer (PBT) to operate the ERV unit.

  1. Press the logo button to operate the ERV for 20 minutes.
  2. Press the logo button again to extend the operation to 40 minutes.
  3. A third press will provide 60 minutes of operation.

The indicator light on the PBL control indicates the ERV operation status.

Percentage Timer Control (PTL) Operation
The PTL control is the primary control for the ERV unit, offering proportional runtime control.

  • The PTL can be set to operate the ERV for an adjustable amount of time each hour.
  • The Runtime % light indicates when the PTL is signaling the ERV to operate.
  • The PTL can also be set to turn off the ERV or keep it running constantly.

Installation Instructions

  1. Properly wire and connect the controls following the wiring diagram provided.
  2. Attach wires to the back of the control units as instructed.
  3. Use Lutron DecoraTM cover plate for a neat finish.
FAQ
  • Q: What should I do if my ventilator is running even when not intended?
    A: Check that none of the controls are calling for unitoperation. If necessary, consult a professional electrician to ensure correct wiring and control settings.

WARNING: HAZARDOUS VOLTAGE – DISCONNECT POWER BEFORE SERVICING

ALL phases of this installation must comply with NATIONAL, STATE AND LOCAL CODES

IMPORTANT — This Document is customer property and is to remain with this unit. Please return to service information pack upon completion of work.

REPLACEMENT INSTALLER’S GUIDE

ELECTRICAL CONTROLS

WARNING
HAZARDOUS VOLTAGE – DISCONNECT POWER BEFORE SERVICING

Note: Proper Wiring Size Selection and Wiring Installation Is The Responsibility of the Electrical Contractor.

Push Button Boost Timer Point-of-Use Control (PBT)  OPERATION

The Push Button Boost Timer (PBT) point-of-use control with indicator light is compatible with the ERV unit. The PBT will operate your ERV for either 20, 40, or 60 minutes based upon how many times the logo button has been pushed. The indicator light on the front of the PBT control is on whenever the ERV is operating, unless operating due to an additional control wired directly to your ERV. 20-40-60 Minute Ventilation Control:

  •  Press the logo and your ventilator will run for 20 minutes. Press again and the unit will run 40 minutes. A third press provides for 60 minutes of operation.
  • You can cancel a cycle at anytime. Just press the logo for a fourth time.
  • You can start another cycle by pressing the logo.

NOTE: For ERV systems with more than one control: Another control other than the push button may be causing your ventilator to run. If you wish to keep your ventilator from running, check that none of your
controls are calling for unit operation.

INSTALLATION

  1. To hook the PBT up to the unit, expose the ends of two wires, and push one into the ‘R’ terminal and one into the ‘C’ terminal. Wire Size: 18–22 gauge, no more than 500 feet. Wiring is non-polar.
  2. Install control in a standard 2″ x 4″ electrical box, with a minimum depth of 1.5″, with the two screws provided.
  3. To add a PBL Control, two wires should be attached to the ‘PB’ positions on the terminal block on the back of the PBT. Connect ‘PB’ wires in a similar fashion as ‘R’ and ‘C’ terminal wires.
  4. LUTRON-CNT10176-Push-Button-Boost-Timer- (1)For two PBL controls, one wire from each can be twisted together and inserted into a single position on the terminal block on the PBT. The wires must be a maximum 18 gauge solid wire. If more than two PBL controls are attached or 18 gauge stranded wire is used, then pigtails must be inserted into the ‘PB’ positions on the PBT and the leads attached to the pigtails with wire nuts.
  5. Use Lutron Decora™ cover plate to complete installation (single cover plate included).

WIRING DIAGRAM

LUTRON-CNT10176-Push-Button-Boost-Timer- (2)

* EXCEPT WHEN ERV IS OPERATING DUE TO AN ADDITIONAL CONTROL WIRED DIRECTLY TO THE UNIT.

Push Button Point-of-Use Control (PBL) OPERATION:
The Push Button point-of-use control with indicator Light (PBL) works in conjunction with one Percentage Timer Control (PTL) or with one Push Button Timer (PBT) and is compatible with the ERV unit. The PBL will operate your ERV for either 20, 40, or 60 minutes based upon how many times the logo button has been pushed. The indicator light on the front of the PBL control is on whenever the ERV is operating, unless operating due to an additional control wired directly to your ERV. The PBL control must be properly wired to a PTL or PBT control to operate the ERV.

20-40-60 Minute Ventilation Control:

  • Press the logo and your ventilator will run for 20 minutes. Press again and the unit will run 40 minutes. A third press provides for 60 minutes of operation. The PTL or PBT control does not need to be on for the PBL Control to operate the ERV unit. LUTRON-CNT10176-Push-Button-Boost-Timer- (3)
  • You can cancel a cycle at anytime. Just press the logo and hold for about five seconds.
  • You can start another cycle by pressing the logo.

NOTE: For ERV systems with more than one control: Another control other than the push button may be causing your ventilator to run. If you wish to keep your ventilator from running, check that none of your controls are calling for unit operation.

INSTALLATION:

  1. Attach two wires to the back of the PBL Control under the screws at the bottom. Tighten down the screws being careful not to over-tighten.
    Wire Size: 18–22 gauge, no more than 500 feet. Wiring is non-polar.
  2. Install control in a standard 2″ x 4″ electrical box, with a minimum depth of 1.5″, with the two screws provided.
  3. Two wires from the PBL Control should be attached to the ‘PB’ positions on the terminal block on the back of the Percent Timer Control (PTL ) or Push Button Timer (PBT).
  4. For two PBL controls, one wire from each can be twisted together and inserted into a single position on the terminal block on the PTL or PBT. The wires must be a maximum 18 gauge solid wire. If more than two PBL controls are attached or 18 gauge stranded wire is used then pigtails must be inserted into the ‘PB’ positions on the Percent Timer Control and the leads attached to the pigtails with wire nuts.
  5. Use Lutron Decora™ cover plate to complete installation (single cover plate included).

WIRING DIAGRAM:

LUTRON-CNT10176-Push-Button-Boost-Timer- (5)

* EXCEPT WHEN ERV IS OPERATING DUE TO AN ADDITIONAL CONTROL WIRED DIRECTLY TO THE UNIT.

Percentage Timer Control (PTL) OPERATION:
The Percentage Timer Control with indicator lights (PTL) is the primary control for ERV unit. This proportional runtime control will operate your ERV an adjustable amount of time each hour. When the “Runtime %” light is on, the PTL control is telling your ERV to operate. Additionally, the PTL can be set to turn your ERV off or to operate constantly. ERV operation time will vary from application to application as well as time of year, lifestyle, indoor air quality concerns and other factors. Discuss any questions with your HVAC professional or contact supplier directly.

  • Constant Operation: Press the button until the light next to “100” is lit.
  • Operation Each Hour: Run time of your ERV can be adjusted from 10%, or 6 minutes each hour, up to 100% operation in 10% increments. Simply press the button until the light next to the desired percentage amount is lit. You can increase or decrease the run time based upon daily, weekly or monthly variations in occupancy levels, indoor odors, cold weather winter humidity, or other indoor air quality concerns as needed.
    FOR NO REGULAR OPERATION: Press the logo until all lights are off. The control is off.

INSTALLATION:

  1. Install control in a standard 2″ x 4″ electrical box, with a minimum depth of 1.5″, with the two screws provided.
  2. Wire Size: 18–22 gauge, no more than 500 feet. Wiring is non-polar.
  3. The two wires from the ERV should be attached to the ‘C’ and ‘R’ positions on the terminal block on the back of the PTL Control.
  4. Use Lutron Decora™ cover plate to complete installation (single cover plate included).
    LUTRON-CNT10176-Push-Button-Boost-Timer- (6)

PERCENTAGE RUN TIME TABLES

RUNTIME % SETTING MINUTES OF OPERATION (PER HOUR) EQUIVALENT CONTINUOUS OPERATION CFM
EV90/P EV130 EV200 EV240 EV300
10 6 9 13 18 24 30
20 12 18 26 36 48 59
30 18 27 39 54 72 89
40 24 36 52 72 96 119
50 30 45 65 91 120 149
60 36 54 78 109 144 178
70 42 63 91 127 168 208
80 48 72 104 145 192 238
90 54 81 117 163 216 267
100 60 90 130 181 240 297
ASHRAE 62.2 2013/16 RESIDENTIAL VENTILATION AIR REQUIREMENTS CONTINUOUS CFM
BEDROOMS
FLOOR AREA (FT2) 1 2 3 4 5
<500 30 38 45 53 60
501 – 1000 45 53 60 68 75
1001 – 1500 60 68 75 83 90
1501 – 2000 75 83 90 98 105
2001 – 2500 90 98 105 113 120
2501 – 3000 105 113 120 128 135
3001 – 3500 120 128 135 143 150
3501 – 4000 135 143 150 158 165
4001 – 4500 150 158 165 173 180
4501 – 5000 165 173 180 188 195

WIRING DIAGRAM:

LUTRON-CNT10176-Push-Button-Boost-Timer- (7)

About Trane and American Standard Heating and Air Conditioning Trane and American Standard create comfortable, energy efficient indoor environments for residential applications. For more information, please visit www.trane.com or www.americanstandardair.com

The manufacturer has a policy of continuous data improvement and it reserves the right to change design and specifications without notice. We are committed to using environmentally conscious print practices.

18-HE143D1-1A-EN 19 Oct 2024 Supersedes (New)

Documents / Resources

LUTRON CNT10176 Push Button Boost Timer [pdf] Installation Guide
CNT10176, CNT10176 Push Button Boost Timer, Push Button Boost Timer, Button Boost Timer, Boost Timer, Timer

References

Leave a comment

Your email address will not be published. Required fields are marked *