BAC-9000A Series
BACnet VAV Controller-Actuators (B-AAC)

KMC CONTROLS BAC-9001AC Clock Dual Port Ethernet

(BAC-9001ACE with
Ethernet/IP shown)

KMC CONTROLS BAC-9001AC Clock Dual Port Ethernet - Symbol 1

DESCRIPTION

KMC Conquest™ BAC-9000A series controller-actuators are designed to operate VAV (Variable Air Volume) terminal units.
The integrated alarming, scheduling, and trending enable these BACnet Advanced Application Controllers to be powerful edge devices for the modern smart building ecosystem.
With integrated actuators, internal air pressure sensors, and other powerful features, they are ideal for new installations and upgrades of less-efficient equipment. They easily mount to terminal boxes by securing a “V” clamp on the shaft and securing a single-screw anti-rotation bracket.
The factory-supplied programming covers common VAV applications. The controllers feature simple, menu-driven setup choices using an STE-9000 series digital sensor, which can be installed permanently as the room sensor or used temporarily as a technician’s service tool.
Alternately, quick configuration of controller properties can be done using NFC (Near Field Communication) from a smart phone, tablet, or computer (using KMC Connect Lite™ app) while the controller is unpowered. For demanding building automation custom requirements, these controllers are also fully programmable. Custom configuration and programming, with wizards for application programming selection/ configuration, are enabled by KMC Connect™ software and the KMC Converge™ module for Niagara Workbench.
KMC Converge and TotalControl™ software additionally provide the capability of creating custom graphical web pages (hosted on a remote web server) to use as a custom user-interface for the controllers.

APPLICATIONS

Application options include:

  • Pressure independent or dependent VAV
  • Cooling only and with changeover
  • Staged, modulated, floating, or time-proportional reheat
  • Series or parallel fan control
  • Dual duct (with TSP-8003 actuators)
  • CAV (Constant Air Volume)

For installations with a BACnet building automation system, these easily integrated controllers signal demands for higher static duct pressure, cooler or warmer supply air, and other diagnostics for AHU optimization.
(See also Sample Installation on page 6.)

MODEL

APPLICA- TIONS INPUTS OUTPUTS FEATURES MODEL
Air Pressure Sensor Real Time Clock MS/TP Ethernet
Pressure- independent VAV, cooling/heating with fan and reheat; CAV 8 total:
•1 Internal actuator position feedback
•1 Integrated air pressure sensor
•2 analog (temperature sensor port)
•4 software-configurable universa) Inputs (terminals)
9 total:
•2 internal Macs (actuator motor control)
•4 external triacs (terminals)
•3 universal outputs (0-12 VDC on terminals)
KMC CONTROLS BAC-9001AC Clock Dual Port Ethernet - Symbol 2 KMC CONTROLS BAC-9001AC Clock Dual Port Ethernet - Symbol 2 BAC-9001AC
KMC CONTROLS BAC-9001AC Clock Dual Port Ethernet - Symbol 2 KMC CONTROLS BAC-9001AC Clock Dual Port Ethernet - Symbol 2 BAC-9001 ACE

SPECIFICATIONS

KMC CONTROLS BAC-9001AC Clock Dual Port Ethernet - SPECIFICATIONS

Inputs and Outputs
Inputs, Universal (4 on Terminal Blocks)

Universal inputs Configurable as analog, binary, or accumulator objects
Termination 1K and 10K ohm sensors, 0–12 VDC, or 0–20 mA (without need for an external resistor)
Resolution 16-bit analog-to-digital conversion
Protection Overvoltage protection (24 VAC, continuous)
Wire size 12–24 AWG, copper, in removable screw terminal blocks

Input, Dedicated Room Sensor Port

Connector Modular connector for STE-9xx1 series digital wall sensors or STE6010/6014/6017 analog temperature
sensors
Cable Uses standard Ethernet patch cable up to 150 feet (45 meters)

Input, Integrated Air Pressure Sensor (optional)

Δ pressure range 0 to 2″ wc (0 to 500 Pa)
Sensor accuracy ±4.5% of the reading or (when near zero) 0.0008″ wc (0.2 Pa), whichever is greater (@ 25° C); internally linearized and temperature compensated
Connections Barbed for 1/4 inch FR (Flame Retard- ant) tubing

Outputs, Universal (3 on Terminal Blocks)

Universal outputs Configurable as an analog (0 to 12 VDC) or binary object (0 or 12 VDC, on/off)
Power/protection Each short-circuit protected universal output capable of driving up to 100 mA (at 0–12 VDC) or 100 mA total for all outputs
Resolution 12-bit digital-to-analog conversion
Wire size 12–24 AWG, copper, in removable screw terminal blocks

Outputs, Triac (4 Binary)

Triac outputs Optically isolated zero-crossing triac output configured as a binary object
Power Maximum switching 24 VAC at 1.0 A for each output; maximum total for controller is 3.0 A
Wire size 12–24 AWG, copper, in removable screw terminal blocks

Output, Integrated Actuator

Torque 40 in-lb. (4.5 N•m)
Angular rotation 0 to 95°; adjustable end stops at 45 and 60° rotation
Motor timing 90 sec. for 90° at 60 Hz; 108 sec. for 90° at 50 Hz
Shaft type/size Mounts on round or square damper shafts—see Enclosure and Mounting on page 4
Noise level <35 db(A) @ 1 meter (3.3 feet)

Communication Ports

MS/TP (optional) One EIA-485 port (removable terminal block) for BACnet MS/TP, operating at 9.6, 19.2, 38.4, 57.6, 76.8, or 115.2 kilobaud; max. length of up to 4,000 feet (1,200 meters) of 18 AWG shielded twisted-pair, no more than 51 pf/ft (167 pf/m); use repeaters for longer distances
Ethernet (optional) On “E” model only, two 10/100BaseT Ethernet connectors for BACnet IP, Foreign Device, and Ethernet 802.3 (ISO 8802-3); segmentation supported; up to 328 ft (100 m) between controllers (using T568B Category 5 or better cable)
NFC NFC (Near Field Communication) up to 1 inch (2.54 cm) from the top of the enclosure
Room sensor Modular STE connection jack for STE-9000A series digital sensors and STE-6010/6014/6017 analog sensors
Auxiliary One serial port with mini Type B connector (reserved for future use)

Configurability

OBJECTS* MAXIMUM #
Inputs and Outputs
Analog, binary, or accumulator input 8
Analog or binary output 9
Values
Analog value 120
Binary value 80
Multi-state value 40
Program and Control
Program (Control Basic) 10
PID loop 10
Schedules
Schedule 2
Calendar 1
Logs
Trend log 20
Trend log multiple (must be created) 4 (default 0)
Alarms and Events
Notification class 5
Event enrollment 40

*Configuration allows creation and deletion of objects (maximum number of objects shown).
The number and configuration of default objects depends on the selected application. For lists of default objects, see the KMC Conquest Controller Application Guide. See also the PIC statement for all supported BACnet objects.

Configuring, Programming, and Designing

SETUP PROCESS KMC CONTROLS TOOL
Configuration Programming (Control Basic) Web Page Graphics*
KMC CONTROLS BAC-9001AC Clock Dual Port Ethernet - Symbol 2 Conquest NetSensor
KMC CONTROLS BAC-9001AC Clock Dual Port Ethernet - Symbol 2 Internal configuration web pages in Conquest Ethernet “E” models**
KMC CONTROLS BAC-9001AC Clock Dual Port Ethernet - Symbol 2 KMC Connect Lite” (NFC) app*”*
KMC CONTROLS BAC-9001AC Clock Dual Port Ethernet - Symbol 2 KMC CONTROLS BAC-9001AC Clock Dual Port Ethernet - Symbol 2 KMC Connect” software
KMC CONTROLS BAC-9001AC Clock Dual Port Ethernet - Symbol 3 KMC CONTROLS BAC-9001AC Clock Dual Port Ethernet - Symbol 3 KMC CONTROLS BAC-9001AC Clock Dual Port Ethernet - Symbol 2 TotalControl” software
KMC CONTROLS BAC-9001AC Clock Dual Port Ethernet - Symbol 2 KMC CONTROLS BAC-9001AC Clock Dual Port Ethernet - Symbol 2 KMC Converge” module for Niagara WorkBench
KMC CONTROLS BAC-9001AC Clock Dual Port Ethernet - Symbol 2 KMC Converge GFX module for Niagara WorkBench

*Custom graphical user-interface web pages can be hosted on a remote web server, but not in the controller.
**Conquest Ethernet-enabled “E” models with the latest firmware can be configured with an HTML5-compatible web browser from pages served from within the controller. For information, see the Conquest Ethernet Controller Configuration Web Pages Application Guide.
***Near Field Communication via enabled smart phone or tablet running the KMC Connect Lite app.
****Full configuration and programming of KMC Conquest controllers is supported starting with TotalControl ver. 4.0.

Hardware Features

Processor, Memory, and Clock

Processor 32-bit ARM®  Cortex-M4
Memory Programs and configuration parameters
are stored in nonvolatile memory; auto restart on power failure
RTC Real time clock with (capacitor) power backup for 72 hours (“C” model only) for network time synchronization or full stand-alone operation

Indicators and Isolation

LED indicators Power/status, MS/TP communication, and Ethernet status
MS/TP protection One network bulb assembly indicates reversed polarity and isolates circuit
Switch EOL (end of line) for MS/TP

Installation

Power

Supply voltage 24 VAC (–15%, +20%), 50/60 Hz, Class 2 only; non-supervised (all circuits, including supply voltage, are power limited circuits)
Required power 8 VA, plus external loads
Wire size 12–24 AWG, copper, in a removable screw terminal block

Enclosure and Mounting

Weight 1.17 lb. (0.53 kg)
Case material Green and black flame retardant plastic
Mounting Directly mounts on 3/8 to 5/8 inch (9.5 to 16 mm) round or 3/8 to 7/16 inch (9.5 to 11 mm) square damper shafts with 2 inch (51 mm) minimum shaft length

Environmental Limits

Operating 32 to 120° F (0 to 49° C)
Shipping –40 to 160° F (–40 to 71° C)
Humidity 0 to 95% relative humidity (non-condensing)

Warranty, Protocol, and Approvals
Warranty
KMC Limited Warranty 5 years (from mfg. date code)

BACnet Protocol

Standard Meets or exceeds the specifications in ANSI/ASHRAE BACnet Standard 135-2010 for Advanced Application Controllers
Type BTL-certified as a B-AAC controller type

Regulatory

UL UL 916 Energy Management Equipment listed
BTL BACnet Testing Laboratory listed as Advanced Application Controller (B-AAC)
RoHS 2 RoHS 2 compliant
FCC FCC Class A, Part 15, Subpart B and complies with Canadian ICES-003 Class A*

*This device complies with part 15 of the FCC Rules. Operation is subject to the following two conditions: (1) This device may not cause harmful interference, and (2) this device must accept any interference received, including interference that may cause undesired operation. (NFC operation meets FCC compliance while the controller is in an unpowered state.)

ACCESSORIES

NOTE: For accessory details, see the respective product data sheets and installation guides.

DAT Sensor and Dual Duct Actuator

STE-1405  Discharge air temperature sensor with 10-foot plenum-rated cable
TSP-8003  Tri-state actuator with pressure sensor for dual-duct applications

Differential Air Pressure Sensors

SSS-1012  Sensor, 3-5/32 inches (80 mm) length
SSS-1013  Sensor, 5-13/32 in. (137 mm) length
SSS-1014  Sensor, 7-21/32 in. (194 mm) length
SSS-1015  Sensor, 9-29/32 in. (252 mm) length

Miscellaneous Hardware

HPO-9901  Controller replacement parts kit with terminal blocks (1 gray, 1 black, 2 green 3-terminal, 4 green 4-terminal, 2 green 5-terminal, 2 green 6-terminal) and DIN clips (2 small for router and 1 large for controllers)
SP-001  Screwdriver (KMC branded) with a hex end (for NetSensor cover screws) and a flat blade end (for controller terminals)

Network Communications

BAC-5051AE  BACnet router with single MS/TP and IP/Ethernet ports
HPO-0055  Replacement network bulb assembly (pack of 5)
HPO-5551  Router technician cable kit
HPO-9003  NFC Bluetooth/USB module (fob)
HSO-9001  Ethernet patch cable, 50 feet
HSO-9011  Ethernet patch cable, 50 feet, plenum rated
HSO-9012  Ethernet patch cable, 75 feet, plenum rated
KMD-5567  Network surge suppressor

Room Sensors, Analog

STE-6010W10  Temperature sensor, white
STE-6014W10  Sensor with rotary setpoint dial, white
STE-6017W10  Sensor with rotary setpoint dial and override button, white
HPO-9005  Room sensor adapter allows the use of other sensors and optional setpoint potentiometers (with wire leads or terminal blocks) to be used instead of STE-601x sensor models with modular jacks

NOTE: Other STE-6000 series sensors are not fully compatible with the dedicated sensor port. However, various other models can be used with an HPO-9005 adapter or with the controller screw terminals. See the STE-6000 series data sheet for more information. For digital sensor information, see the STE-9000 series.
NOTE: To order the STE-601x sensor with light almond color instead of white, drop the W on the end of the model number (e.g., STE-6010W is white and STE-6010 is light almond).

Room Sensors, Digital (LCD Display)

STE-9000 Series  KMC Conquest NetSensor digital room temperature sensors for viewing, configuring, and optional humidity, occupancy, and CO2 sensing
HPO-9001  NetSensor distribution module

Transformers, 120 to 24 VAC

XEE-6111-050 50 VA, single-hub
XEE-6112-050 50 VA, dual-hub

SAMPLE INSTALLATION

KMC CONTROLS BAC-9001AC Clock Dual Port Ethernet - SAMPLE INSTALLATION

For more information about installation and operation, see:

SUPPORT
Additional resources for installation, configuration, application, operation, programming, upgrading, and much more are available on the web at www.kmccontrols.com. Log-in to see all available files.

KMC CONTROLS logo

© 2024 KMC Controls, Inc.
Specifications and design are subject to change without notice