Solid - logoCIR-44
Premium Solid State
ANTARA FACE PELANGGAN
LEMBAR PITUDUH

Relay Antarmuka Pelanggan CIR-44

Solid State Instruments CIR 44 Customer Interface Relay - liwatview 1

LAMPIRAN – CIR-44 nduweni kandang tahan cuaca lan bledug NEMA4X. CIR-44 bisa dipasang ing posisi apa wae, nanging umume paling trep lan dirancang kanggo dipasang kanthi engsel ing sisih kiwa ing orientasi sing dituduhake ing ndhuwur. Four bolongan soyo tambah kasedhiya.
POWER INPUT - Kanggo daya 120 nganti 277 VAC, sambungake timbal "panas" menyang terminal LINE. Sambungake terminal NEU menyang netral. Sambungake terminal GND menyang lemah sistem listrik. CIR-44 kudu kabel Phase menyang Netral, dudu Phase menyang Phase. Yen netral bener ora kasedhiya, sambungake terminal NEU lan GND menyang lemah sistem listrik. Terminal GND WAJIB disambungake. AJA ninggalake terminal GND ora nyambung.
KONEKSI METER - Empat input pulsa 2-Wire (Formulir A) diwenehake ing CIR-44. Sambungake kabel K lan Y saka saben meter. Sambungake K & Y ndadékaké saka output pulsa kontak garing Meter #1 menyang terminal K & Y ing INPUT #1 saka strip terminal ing kompartemen sarana. Sambungake Meter #2 menyang terminal K & Y saka Input #2, lsp. Terminal input Y nyedhiyakake wetting (rasa) vol "ditarik munggah".tage saka +12VDC menyang terminal "Y" meter. Terminal input "K" CIR44 nyedhiyakake bali umum. Input KY CIR-44 kompatibel karo inisiator pulsa elektromekanis utawa solid state. Nalika nggunakake output transistor NPN Bi-Polar kolektor mbukak utawa transistor N-Channel FET saluran mbukak kanggo antarmuka meter karo CIR-44, pin emitor (-) transistor utawa pin sumber FET (-) kudu disambungake menyang terminal input K. Penagih transistor (+) utawa pin saluran FET (+) kudu disambungake menyang terminal input Y. Saben input Y duwe LED KUNING ing kompartemen pelanggan kanggo nuduhake nalika input Y aktif.
OUTPUT - Sekawan output terisolasi rong kabel diwenehake ing CIR-44, kanthi terminal output K1 & Y1, K2 & Y2, K3 & Y3, lan K4 & Y4 lan dumunung ing ngisor kandang ing kompartemen pelanggan. Output minangka jinis kontak garing solid-state lan kudu diwenehake karo vol wettingtage saka sumber eksternal, biasane diwenehake dening piranti panampa pulsa. Kontak dirating ing 120VAC/VDC MAX lan saiki winates kanggo 180mA. Penindasan sementara kanggo kontak relay solid state diwenehake sacara internal. Saben relay kudu diutus utawa "dipetake" menyang salah siji saka papat saluran input, nggunakake SSI Universal Programmer V1.1.0 utawa mengko. LED ing saben output nuduhake status output kang. LED Ijo nuduhake penutupan KY saben output.

CIR-44 Wiring Diagram

Solid State Instruments CIR 44 Customer Interface Relay - Wiring Diagram 1

CIR-44WiringDiagram.vsd

CIR-44 Diagram Wiring Relay Pulse Repeating REVISI
NO. TANGGAL DESKRIPSI
DATE ASLI
05/10/24
SKALA
N/A
REVISI TERBARU PEKERJAAN NO. DIPriksa WHB

Brayden Automation Corp./Solid State Instruments div.
6230 Aviation Circle Loveland, CO 80538 (970)461-9600
support@brayden.com
www.solidstateinstruments.com

DISIPASI DAYA MAKSIMUM OUTPUT – Piranti output dirating ing maksimum 1500 mW. Care kudu dijupuk kanggo njamin sing wetting voltage digunakake liwat piranti output kaping saiki (utawa beban) saka input saka piranti hilir, ora ngluwihi boros output daya maksimum 1500mW. Biasane iki ora dadi masalah amarga piranti instrumentasi hilir duwe impedansi dhuwur lan beban sing sithik, biasane kurang saka 10mA. Kanggo example, yen 120VAC digunakake, saiki maksimum allowable tengen output 12.5 mA. Yen 12VDC digunakake, arus maksimum sing diidini ing output kira-kira 125mA, uga miturut rating piranti saiki 180mA. Mulane, boros maksimal nalika nggunakake 12V yaiku 1500mW amarga saiki diwatesi nganti .125 Amp. Hitung arus maksimum nggunakake rumus ing ngisor iki: 1500milliWatts / Voltage = Maks. Saiki (beban) ing milliamps. Nyetel voltage utawa saiki digunakake tengen output kanggo njamin sing boros daya maksimum, voltage lan maksimum saiki ora ngluwihi.
SEKRING – Saben output wis otomatis ngreset Fuse dirating ing 150mA. F1, F2, F3 lan F4 cocog karo output 1, 2, 3, lan 4. Rating sekring maksimal ditetepake ing layar sutra ing ngisor utawa ing jejere saben posisi sekring.
FORM A PULSE WIDTHS - Yen pangguna mbutuhake jembar pulsa tetep ing output, jembar pulsa saka .00001 detik nganti 10000 detik bisa diprogram. Dawane output tetep dipateni kanthi ngetik 0.0000 minangka jembar pulsa. Iki nempatake output ing mode pilihan utawa mode "Mirror" ing ngendi wektu output padha karo wektu input.
MODE OPERASI – CIR-44 nduweni telung mode operasi kaya ing ngisor iki:
1.) Formulir A In / Formulir A Out - Pass liwat; Wektu nutup output padha karo wektu nutup Input.
2.) Formulir A In / Formulir A Out - Pass liwat karo wektu Output Width Tetep.
3.) Formulir A In / Formulir A Out - Mode Konversi kanthi nilai Input lan Output sing ditemtokake.
Mode iki bisa ditugasake dening entri menyang tabel pemrograman.
TOTALIZING – CIR-44 bisa kanggo totalize samubarang papat input, karo salah siji positif (dikirim) bijih negatif (ditampa) Nilai. Kanthi cara iki, CIR-44 ngidini sampeyan "Net Out" energi antarane jumlah energi sing Dikirim lan Ditampa. Watesan Negatif uga bisa disetel kanggo njamin yen nilai akrual negatif ora luwih negatif tinimbang watesan sing ditemtokake. Nilai pulsa uga bisa disetel kanggo nilai input lan output supaya nilai pulsa nyata saka meter sing beda bisa dijumlah kanthi akurat. Waca SoCo Programmer Manual kanggo
informasi rinci babagan totalizing.

KARYA WILAYAH CIR-44

MODE OPERASI: CIR-44 Programmable Customer Interface Relay nduweni 3 mode operasi. Salah sijine yaiku "Pass-Thru", sing nomer loro yaiku mode output "Fixed-Width" lan nomer telu yaiku mode "Konversi Nilai". Sembarang mode iki bisa digunakake nganggo utawa tanpa fungsi totalizer.
Mode 1 – Formulir A In/Form A Out: Ing mode Pass-Thru iki, input lan output disetel menyang mode Formulir A (2-kabel) lan Width Pulse Output tetep dipateni. Output Formulir A ngetutake input Formulir A. Lebar pulsa output padha karo lebar pulsa input.

Gambar 1: Form A Input/FormA Output Operasi Mode Normal

Instrumen Solid State CIR 44 Relay Antarmuka Pelanggan - KERJA 1

Mode 2 – Formulir A In/Form A Out kanthi Width Pulse Output tetep: Ing mode Width Tetap iki, output Formulir A tindakake input Formulir A, nanging cedhak kanggo durasi lebar pulsa sing dipilih.

Gambar 3: Formulir A Input / FormA Operasi Output Width Output Pulse

Instrumen Solid State CIR 44 Relay Antarmuka Pelanggan - KERJA 2

Ing mode iki, jembaré pulsa output disetel kanggo 50mS, nganti 10,000mS, supaya pulses output sing jembaré tetep ( Instrumen Solid State CIR 44 Relay Antarmuka Pelanggan - lambang 1 ) kaya sing ditegesake dening kothak mlebu Pulse Width. Pulsa input bakal nyepetake lan mudhun alon-alon supaya wektu antarane pulsa variabel, nanging wektu (T1) pulsa tetep. Yen pulsa input luwih cepet tinimbang pulsa output, kebanjiran bisa kedadeyan ing mode iki. Tegese pulsa output ora bisa ngetutake pulsa input amarga watesan wektu lebar pulsa tetep. Pilih lebar pulsa sing luwih cendhek tinimbang pulsa input paling cepet utawa mateni jembar pulsa tetep, banjur klik .

Mode 3 - Formulir A In/Form A Out, Mode Konversi Nilai Pulsa: Ing mode iki, nilai pulsa Input lan Output dilebokake ing program. Sawise saben penutupan input Formulir A, nilai pulsa ditambahake menyang register Nilai Energi Akru (AER). Nalika nilai ing AER padha karo utawa luwih saka nilai pulsa output programmed, pulsa punika
outputted. Fungsi konversi iki ngidini nilai pulsa input lan output dadi beda.

Gambar 4: Formulir A Input / FormA Operasi Output Mode Konversi Nilai Pulsa

Instrumen Solid State CIR 44 Relay Antarmuka Pelanggan - KERJA 3

Kanggo Example, ayo kang nganggep yen pulsa input worth 2.88 watt-jam saben pulsa. Salajengipun ayo nganggep yen nilai pulsa ouput disetel dadi 4.00 watt-jam saben pulsa. Pulsa pisanan mlebu 2.88 ing registrasi Energi accrued (AER). Ora ana pulsa output sing digawe. Pulsa kapindho nampa tambahan AER kanthi 2.88 wh liyane menehi 5.76 wh. 5.76 luwih saka 4 supaya pulsa digawe. Sisa 1.76 wh tetep ing AER. Pulsa input katelu 2.88 nambah AER menehi imbangan 4.64 wh. Pulsa output liyane digawe, ninggalake .64 wh ing register. Pulsa input kaping papat nambahake 2.88 menyang AER menehi imbangan anyar 3.52 wh. Iki ora cukup kanggo ngasilake pulsa, mula 3.52 ditahan ing AER nganti pulsa kaping 5 ditampa, nalika pulsa liyane digawe. Proses iki terus, nggawe manawa pulsa output worth 4.00 Wh saben. Dadi kaya sing sampeyan deleng, iki nggawe pola pulsa asimetris nanging ngganti nilai saka 2.88wh / pulsa dadi 4.00 wh / pulsa.
Mapping saben Output menyang Input: Papat output saka CIR-44 kudu ditugasake, utawa "dipetake", menyang salah siji input. Sembarang output bisa dipetakan menyang salah siji saka papat input.
Konfigurasi standar 1 kanggo 1, 2 kanggo 2, 3 kanggo 3 lan 4 kanggo 4. Iki diarani konfigurasi 4 × 4 lan konfigurasi standar. Ing konfigurasi iki, saben output disambungake menyang input saka nomer sing padha.
Sembarang konfigurasi utawa kombinasi output kanggo input bisa gumantung ing aplikasi. Kabeh papat output bisa ditugasake menyang siji input menehi papat kontak terisolasi. Input sing ora digunakake bisa dipateni.
Konfigurasi populer liyane yaiku "24" ing ngendi loro output saben siji ngetutake siji input. Kanggo example output #1 lan #2 tindakake input #1 lan output #3 lan #4 tindakake Input #2. Mulane,
Input #3 lan #4 ora digunakake. Konfigurasi iki asring digunakake kanggo pulsa kWh sing dikirim lan ditampa, utawa kanggo pulsa kwh lan kVARh.

Hubungi pabrik kanggo dhukungan teknis ing (888)272-9336.

Programer SOCO

SoCo Programer minangka utilitas pemrograman berbasis windows kanggo Seri CIR-44. Download SoCo Programmer saka kaca CIR-44 ing SSI websitus ing www.solidstateinstruments.com/sitepages/downloads.php. Kaca Programmer kapacak ing ngisor iki. Mangga deleng manual Pemrograman SOCO kanggo instruksi babagan carane program CIR-44.

Solid State Instruments CIR 44 Customer Interface Relay - SOCO Programer 1

Reset Default Pabrik- Sampeyan bisa ngreset CIR-44 menyang standar pabrik kanthi ngeklik tombol Default.

Solid - logoINSTRUMEN SOLID STATE
Salah siji bagéan saka Brayden Automation Corp.
6230 Aviation Circle, Loveland, Colorado 80538
Telpon: (970) 461-9600 Fax: (970) 461-9605
E-mail:support@solidstateinstruments.com

Dokumen / Sumber Daya

Solid State Instruments CIR-44 Customer Interface Relay [pdf] Pandhuan
CIR-44 Relay Antarmuka Pelanggan, CIR-44, Relay Antarmuka Pelanggan, Relay Antarmuka