PENTAIR Intellimaster Variable Speed Controller User Manual

Yen installer utawa pemilik ora ngerti instalasi sing bener lan / utawa operasi saka jinis peralatan iki, hubungi distributor
utawa pabrikan kanggo saran sing bener sadurunge nerusake instalasi utawa operasi produk iki.
PENTING Mangga waca PETUNJUK KESELAMATAN ing ngisor iki.
FITUR / FUNGSI
SPESIFIKASI UMUM | |
Metode Operasi |
Operasi Inverter Individu (Paralel nganti 3 pompa) |
Tampilan | 2.42" OLED karo keypad |
Basa | Inggris |
Vol inputtage | 230V AC Fase Tunggal, 50Hz |
Suhu & Kelembapan | -10~40°C / 90% |
Run Sajarah | Run-time rekaman lan tampilan |
Riwayat Weker | Rekaman lan tampilan nganti 20 weker |
Fungsi liyane |
Reset Otomatis, Alarm Tekanan Dhuwur lan Sedheng, Proteksi Dry Run, lsp. |
CONTROL KEY DESCRIPTION
SETTING CEPAT
KARAKTERISTIK TEKNIS
Model Pompa Kab | Pengontrol Model | Vol inputtage [V] | Output Voltage [V] | Output Saiki [A] | Motor [kW] |
IMH750K |
PVFD0750S (810960) | 230 V AC 1 PH
+/- 10% |
3 X 220/240 |
2.4A |
0.75 |
IMH1100K |
PVFD1500S (810961) | 230 V AC 1 PH
+/- 10% |
3 X 220/240 |
4.7A |
1.5 |
IMH2200K |
PVFD2200S (810962) | 230 V AC 1 PH
+/- 10% |
3 X 220/240 |
7.1A |
2.2 |
Kelas Proteksi IP55
Frekuensi Output 50 Hz (+/-5%) Suhu Sekitar -10°C ~ 40°C
Model Pompa Kab | IMH750K | IMH1100K | IMH2200K |
Kelas Proteksi |
IP55 |
IP55 |
IP55 |
Motor [kW] |
0.75 |
1.5 |
2.2 |
Input AC Voltage | 1 Phase 220V/240V (+/-15%) | 1 Phase 220V/240V (+/-15%) | 1 Phase 220V/240V (+/-15%) |
Dinilai Output Voltage [V] |
3 Phase 220V/240V |
3 Phase 220V/240V |
3 Phase 220V/240V |
Arus Output Rated [A] |
2.4 |
4.7 |
7.1 |
Rentang Frekuensi Output [Hz] |
0-50 Hz |
0-50 Hz |
0-50 Hz |
Voltage/Karakteristik Frekuensi |
Kontrol V/F |
Kontrol V/F |
Kontrol V/F |
Kakehan Rated Saiki | 150% saka dirating saiki | 150% saka dirating saiki | 150% saka dirating saiki |
Pangreksan |
Auto Reset, Dry Run Protection, lsp |
OPERASI PARALEL
Kanggo nyetel operasi paralel, ganti cara operasi menyang mode operasi otomatis.
CATETAN: Nganti 3 pompa bisa disambungake lan dioperasikake kanthi paralel.
Nyetel MASTER PUMP : Tekan suwene 2-3 detik. Pompa Master kudu nyatakake " 1 ”
Nyetel POMPA SLAVE : Tekan suwene 2-3 detik. Pompa Slave kudu nyatakake " 2 ”
SETTING PARAMETER KONTROL
Paramèter | Range Input | Unit | Default |
Setel Tekanan |
0.1 ~ 20.0 | bar | 3.5 |
10 ~ 300 | psi | 30 | |
Run Deviasi |
-3.0 ~ -0.2 | bar | -0.3 |
-50 ~ -3 | psi | -5 | |
Stop Tundha | 3.0 ~ 999.9 | sek | 5.0 |
Wiwiti maneh Tundha | 0 ~ 9999 | sek | 0 |
Wektu Ngalih | 0 ~ 9999 | Min | 60 |
Runtime maksimum | 0 ~ 999 | Min | 0 |
P | 1 ~ 200 | – | 25 |
I | 1 ~ 200 | – | 40 |
D | 1 ~ 200 | – | 40 |
Low Pressure Weker | [Digunakake] [Ora Digunakake] | [Digunakake] | |
kurang Tekanan Nilai |
0.1 ~ 10.0 | bar | 0.3 |
1 ~ 140 | psi | 5 | |
Low Pressure Stop | 0 ~ 999 | sek | 10 |
Low Pressure Wiwiti maneh | 0 ~ 999 | sek | 10 |
kurang Tekanan Wiwiti maneh Wektu |
0 ~ 20 |
Cyle |
3 |
Unit Tekanan | [bar] [psi] | [bar] |
SETTING PARAMETER KONTROL
Setel Tekanan | Nuduhake tekanan set operasi. |
Run Deviasi |
Nuduhake panyimpangan roto nalika operasi sistem diwiwiti. |
Stop Tundha | Nuduhake wektu tundha mandeg sistem. |
Wiwiti maneh Tundha | Nuduhake wektu tundha wiwitan sistem. |
Wektu Ngalih | Nuduhake wektu nalika pompa timbal gantian. |
Runtime maksimum |
Wektu maksimal ing sawetara menit pompa bisa terus-terusan, fitur iki dipateni yen nilai disetel dadi 0. |
P |
Iku cocog kanggo 'P' (Propotional Constant) metu saka kontrol PID. |
I | Iku cocog kanggo 'I' (Integral Constant) metu saka kontrol PID. |
D |
Iku cocog kanggo 'D' (Differential Constant) metu saka kontrol PID. |
Low Pressure Weker |
Yen tekanan operasi luwih murah tinimbang tekanan sing disetel, weker bakal kedadeyan. |
kurang Tekanan Nilai | Nyetel watesan tekanan rendah. |
Low Pressure Stop |
Sawise weker tekanan rendah kedadeyan, sistem bakal ngoperasikake durasi wektu tundha sing disetel lan banjur sistem bakal mandheg. |
Low Pressure Wiwiti maneh |
Nyetel wektu miwiti maneh tekanan rendah. Sistem bakal diwiwiti maneh sawise nilai sing disetel. |
Tekanan Low Wiwiti maneh Wektu | Nyetel siklus urip maneh tekanan rendah. Sistem bakal mandheg sawise siklus sing disetel. |
Unit Tekanan | Setelan unit Tekanan. |
SETTING PARAMETER FUNGSI
Isi | Range Input | Unit | Default |
Range Sensor |
0.2 ~ 20.0 |
bar |
16.0 |
10 ~ 300 |
psi |
230 |
|
Sensor Offset |
-9.9 ~ 9.9 |
bar |
0.0 |
-99 ~ -99 |
psi |
0 |
|
Reset otomatis |
0 ~ 20 |
siklus |
5 |
Min. Out Rate |
30.00 ~ 70.00 |
% |
50.00 |
mandeg Rate |
30.00 ~ 95.00 |
% |
65.00 |
Arah Motor | [Mundur] [Mundur] |
– |
Maju |
kurang saiki Weker | [Digunakake] [Ora Digunakake] |
– |
Ora Digunakake |
Nilai Saiki Low |
0.0 ~ 99.9 |
A |
Gumantung ing Model VSD |
kurang saiki mandeg |
1 ~ 999 |
sek |
10 |
Range Sensor |
Kanggo nyetel kapasitas dirating saka sensor tekanan digunakake. |
Sensor Offset |
Kanggo mbenerake variasi antarane nilai sensor tekanan lan nilai tekanan akut. |
Reset otomatis |
Nuduhake jumlah kaping sistem bakal ngreset yen weker kedadeyan. |
Min. Op. Rate |
Nuduhake output minimal. |
mandeg Rate |
Nuduhake output mandeg. |
Arah Motor |
Arah motor. |
Low Curr. Weker |
Nuduhake output Stop. |
Low Curr. Nilai |
Nuduhake set point [Amp.] ngendi weker saiki kurang. |
kurang Curr. mandeg |
Nuduhake wektu sing disetel sistem bakal mandheg yen ana arus sing sithik. |
SETTING PARAMETER KONTROL VFD
Paramèter | Range Input | Unit | Default |
Max.Frekuensi Output | 5.0 ~ 70 | Hz | 50.0 |
Maks. Voltage Frekuensi | 5.0 ~ 70 | Hz | 50.0 |
Maks. Voltage | 50 ~ 250 | VAC | 240 |
Frekuensi Mid-Point | 5.0 ~ 70 | Hz | 25 |
Mid-Point Voltage | 0 ~ 250 | VAC | 120 |
Min. Frekuensi Output | 0.10 ~ 20.00 | Hz | 1.50 |
Min. Output Voltage | 3.0 ~ 200 | VAC | 15 |
Wektu Akselerasi | 1.0 ~ 120 | Sek. | 3.0 |
Penundaan Wektu | 1.0 ~ 120 | Sek. | 3.0 |
Mode Stop | 0: Ramp kanggo Stop / 1: Coast kanggo Stop |
– |
1 |
HP motor |
IDM-1007M | [0.5HP] [0.75HP] [1.0HP] | |
IDM-1015M |
[0.5HP] [0.75HP] [1.0HP] [1.5HP] [2.0HP] | ||
IDM-1022M |
[0.5HP] [0.75HP] [1.0HP] [1.5HP] [2.0HP] [2.5HP] [3.0HP] | ||
Tingkat kakehan | 50 ~ 200 | % | 150 |
Wektu kakehan | 2.0 ~ 999 | Sek | 10.0 |
Over-Voltage Rate | 100 ~ 200 | % | 120 |
Low-Voltage Rate | 70 ~ 90 | % | 80 |
Pembawa Frekuensi | 3.0 ~ 15.0 | KHz | 8.0 |
PARAMETER KONTROL INVERTER
Maks. Frekuensi Output | Parameter iki nemtokake max inverter. frekuensi output. |
Maks. Voltage Frekuensi | Nilai iki kudu disetel miturut frekuensi dirating motor. |
Frekuensi Mid-Point |
Nuduhake frekuensi titik tengah kurva V / F. Rasio V / F antarane min. frekuensi lan mid-titik frekuensi bisa ditemtokake. |
Mid-Point Voltage |
Nuduhake vol tengah-titiktage saka sembarang kurva V/F. Rasio V / F antarane min. frekuensi lan mid-titik frekuensi bisa ditemtokake. |
Min.Frekuensi Output | Nuduhake min. frekuensi output saka inverter. |
Min. Output Voltage | Nuduhake min. output voltage saka inverter. |
Wektu Akselerasi |
Nuduhake wektu sing dibutuhake kanggo inverter kanggo akselerasi saka 0 Hz nganti maksimal. frekuensi output. |
Penundaan Wektu |
Nuduhake wektu sing dibutuhake kanggo inveter kanggo decelerate saka max. frekuensi output mudhun kanggo 0 Hz. |
Mode Stop |
1. Ramp: inverter decelerates motor kanggo min. frekuensi output banjur mandheg miturut wektu deceleration disetel. |
2. Coast: inverter mandheg output enggal marang printah, lan motor free mlaku nganti teka mandeg lengkap. | |
HP motor | Nampilake HP inverter sing saiki digunakake. |
Tingkat kakehan | Nuduhake tingkat saiki trip marang saiki dirating motor. |
Wektu kakehan | Nuduhake wektu ngramut tingkat trip kakehan kanggo generate trip kakehan. |
Over-Voltage Rate | Nuduhake over-voltage pangayoman. |
Low-Voltage Rate | Nuduhake low-voltage pangayoman. |
Pembawa Frekuensi |
Nuduhake tingkat saiki trip marang saiki dirating motor. |
SETTING PARAMETER SISTEM
Paramèter | Range Input | Default |
Daya Outage Wiwiti maneh |
[System Stop] [System Run] [Status Serep] |
Negara serep |
Basa | [Korea] [Inggris] | Inggris |
Sandi (0000: Ora Digunakake) |
0000 ~ 9999 |
0000 |
Kode Tes | 0000 ~ 9999 | 0000 |
Tampilan | Weker Jinis | Tindakan korektif |
Comm Gagal |
Komunikasi Gagal |
Priksa status sambungan antarane pompa master lan slave. |
Sensor mbukak |
Sensor mbukak |
Priksa manawa sambungan sensor wis ditindakake kanthi bener. Ganti sensor yen kesalahan isih ana sawise mriksa sambungan. |
Sen.Short |
Sensor Singkat |
Priksa manawa sambungan sensor wis ditindakake kanthi bener. Ganti sensor yen kesalahan isih ana sawise mriksa sambungan. |
High Pres. |
Tekanan Dhuwur |
Priksa tekanan set lan nilai setelan tekanan dhuwur ing paramèter. |
Low Pres. |
Tekanan Low |
Priksa manawa saluran pipa nyedhot diisi banyu lan uga ngeculake hawa saka ventilasi udara ing pompa yen perlu. |
L-Pra. mandeg |
Low Pressure Stop |
Priksa manawa saluran pipa nyedhot diisi banyu lan uga ngeculake hawa saka ventilasi udara ing pompa yen perlu. |
kurang saiki |
Saiki Low |
Priksa manawa saluran pipa nyedhot diisi banyu lan uga ngeculake hawa saka ventilasi udara ing pompa yen perlu. |
L-Kur. mandeg |
Low Saiki Stop |
Priksa manawa saluran pipa nyedhot diisi banyu lan uga ngeculake hawa saka ventilasi udara ing pompa yen perlu. |
Kakehan beban |
Kakehan beban |
Priksa arus sing dirating motor lan setelan saiki sing dirating ing inverter |
Swara Cur. |
Sajrone Saiki |
Priksa wektu Acc./Dec. Uga, priksa manawa kapasitas inverter cocok kanggo motor sing dipasang. |
kurang Volt. |
Low Voltage |
Priksa input voltage lan kapasitas daya. |
Over Panas | Over Panas | Hubungi supplier lokal sampeyan. |
Swara Volt. |
Swara Voltage |
Priksa pasokan voltage lan nambah wektu deceleration. |
1-21 Monash Drive, Dandenong South, VIC 3175 Australia | 1300 137 344 | pentair.com.au
Informasi sing ana ing kene tetep dadi properti Pentair miturut hukum hak cipta Australia. Sembarang reproduksi, tampilan, publikasi, modifikasi utawa distribusi wis strictly dilarang tanpa ijin ditulis sadurunge saka Pentair.
Penafian: Pentair duwe hak kanggo ngganti spesifikasi produk lan rincian produk.
Kabeh gambar produk mung kanggo tujuan referensi lan bisa uga ora makili produk nyata lan / utawa saiki.
© 2022 Pentair. Kabeh hak dilindhungi undhang-undhang.
Waca Liyane Babagan Manual Iki & Unduh PDF: