PENTAIR Intellimaster Variable Speed Controller User Manual

Should the installer or owner be unfamiliar with the correct installation and/or operation of this type of equipment, please contact the distributor
or manufacturer for the correct advice before proceeding with the installation or operation of this product.
IMPORTANT Please read the SAFETY INSTRUCTIONS below.
FEATURES / FUNCTIONS
GENERAL SPECIFICATIONS | |
Operation Method |
Individual Inverter Operation ( Parallel up to 3 pumps ) |
Display | 2.42” OLED with keypad |
Language | English |
Input Voltage | 230V AC Single Phase, 50Hz |
Temperature & Humidity | -10~40°C / 90% |
Run History | Run-time record and display |
Alarm History | Records and display’s up to 20 alarms |
Other Fuctions |
Auto Reset, High and Low Pressure Alarms, Dry Run Protection, etc. |
CONTROL KEY DESCRIPTION
QUICK SETTINGS
TECHNICAL CHARACTERISTICS
Pump Model | Controller Model | Input Voltage [V] | Output Voltage [V] | Output Current [A] | Motor [kW] |
IMH750K |
PVFD0750S (810960) | 230V AC 1PH
+/- 10% |
3 X 220/240 |
2.4A |
0.75 |
IMH1100K |
PVFD1500S (810961) | 230V AC 1PH
+/- 10% |
3 X 220/240 |
4.7A |
1.5 |
IMH2200K |
PVFD2200S (810962) | 230V AC 1PH
+/- 10% |
3 X 220/240 |
7.1A |
2.2 |
Protection Class IP55
Output Frequency 50 Hz (+/-5%) Ambient Temperature -10°C ~ 40°C
Pump Model | IMH750K | IMH1100K | IMH2200K |
Protection Class |
IP55 |
IP55 |
IP55 |
Motor [kW] |
0.75 |
1.5 |
2.2 |
Rated Input AC Voltage | 1Phase 220V/240V (+/-15%) | 1Phase 220V/240V (+/-15%) | 1Phase 220V/240V (+/-15%) |
Rated Output Voltage [V] |
3Phase 220V/240V |
3Phase 220V/240V |
3Phase 220V/240V |
Rated Output Current [A] |
2.4 |
4.7 |
7.1 |
Output Frequency Range [Hz] |
0-50 Hz |
0-50 Hz |
0-50 Hz |
Voltage/Frequency Characteristic |
V/F control |
V/F control |
V/F control |
Overload Rated Current | 150% of rated current | 150% of rated current | 150% of rated current |
Protections |
Auto Reset, Dry Run Protection, etc |
PARALLEL OPERATION
To set parallel operation, change the operation method to the auto operation mode.
NOTE: Up to 3 pumps can be linked and operated in parallel.
Setting the MASTER PUMP : Press the for a duration 2-3 seconds. The Master pump should state “ 1 ”
Setting the SLAVE PUMP : Press the for a duration 2-3 seconds. The Slave pump should state “ 2 ”
CONTROL PARAMETER SETTING
Parameters | Input Range | Unit | Default |
Set Pressure |
0.1 ~ 20.0 | bar | 3.5 |
10 ~ 300 | psi | 30 | |
Run Deviation |
-3.0 ~ -0.2 | bar | -0.3 |
-50 ~ -3 | psi | -5 | |
Stop Delay | 3.0 ~ 999.9 | sec | 5.0 |
Restart Delay | 0 ~ 9999 | sec | 0 |
Shift Time | 0 ~ 9999 | Min | 60 |
Maximum Runtime | 0 ~ 999 | Min | 0 |
P | 1 ~ 200 | – | 25 |
I | 1 ~ 200 | – | 40 |
D | 1 ~ 200 | – | 40 |
Low Pressure Alarm | [Used] [Not Used] | [Used] | |
Low Pressure Value |
0.1 ~ 10.0 | bar | 0.3 |
1 ~ 140 | psi | 5 | |
Low Pressure Stop | 0 ~ 999 | sec | 10 |
Low Pressure Restart | 0 ~ 999 | sec | 10 |
Low Pressure Restart Time |
0 ~ 20 |
Cyle |
3 |
Pressure Unit | [bar] [psi] | [bar] |
CONTROL PARAMETER SETTING
Set Pressure | Refers to the operating set pressure. |
Run Deviation |
Refers to the run deviation in which the operating of the system starts. |
Stop Delay | Refers to the stop delay time of the system. |
Restart Delay | Refers to the start delay time of the system. |
Shift Time | Refers to the time when the lead pump alternates. |
Maximum Runtime |
Maximum time in minutes the pump is allow to operate continuously, this feature is disabled if value is set to 0. |
P |
It is relevant to ‘P’ (Propotional Constant) out of the PID controls. |
I | It is relevant to ‘I’ (Integral Constant) out of the PID controls. |
D |
It is relevant to ‘D’ (Differential Constant) out of the PID controls. |
Low Pressure Alarm |
If the operation pressure is lower than the set pressure, alarm will occur. |
Low Pressure Value | Setting the low pressure limit. |
Low Pressure Stop |
Once the low pressure alarm occurs, the system will operate duration of the set delay time and afterwards the system will stop. |
Low Pressure Restart |
Setting the low pressure restart time. The system will restart after the set value. |
Low Pressure Restart Time | Setting the low pressure restart cycle. The system will stop ater the set cycle. |
Pressure Unit | Setting the Pressure unit. |
FUNCTION PARAMETER SETTING
Content | Input Range | Unit | Default |
Sensor Range |
0.2 ~ 20.0 |
bar |
16.0 |
10 ~ 300 |
psi |
230 |
|
Sensor Offset |
-9.9 ~ 9.9 |
bar |
0.0 |
-99 ~ -99 |
psi |
0 |
|
Auto Reset |
0 ~ 20 |
cycle |
5 |
Min. Out Rate |
30.00 ~ 70.00 |
% |
50.00 |
Stop Rate |
30.00 ~ 95.00 |
% |
65.00 |
Motor Direction | [Foward] [Backward] |
– |
Forward |
Low Current Alarm | [Used] [Not Used] |
– |
Not Used |
Low Current Value |
0.0 ~ 99.9 |
A |
Depended on VSD Model |
Low Current Stop |
1 ~ 999 |
sec |
10 |
Sensor Range |
To set-up the rated capacity of the pressure sensor utilized. |
Sensor Offset |
To correct the variation between the value of the pressure sensor and acutual pressure value. |
Auto Reset |
Refers to the number of times the system will reset once an alarm occurs. |
Min. Op. Rate |
Refers to the minimum output. |
Stop Rate |
Refers to the stop output. |
Motor Direction |
Direction of the motor. |
Low Curr. Alarm |
Refers to the Stop output. |
Low Curr. Value |
Refers to the set point [Amp.] where the low current alarm occurs. |
Low Curr. Stop |
Refers to the set time the system will stop once the low current occurs. |
VFD CONTROL PARAMETER SETTING
Parameters | Input Range | Unit | Default |
Max.Output Frequency | 5.0 ~ 70 | Hz | 50.0 |
Max. Voltage Frequency | 5.0 ~ 70 | Hz | 50.0 |
Max. Voltage | 50 ~ 250 | VAC | 240 |
Mid-Point Frequency | 5.0 ~ 70 | Hz | 25 |
Mid-Point Voltage | 0 ~ 250 | VAC | 120 |
Min. Output Frequency | 0.10 ~ 20.00 | Hz | 1.50 |
Min. Output Voltage | 3.0 ~ 200 | VAC | 15 |
Acceleration Time | 1.0 ~ 120 | Sec. | 3.0 |
Deceleration Time | 1.0 ~ 120 | Sec. | 3.0 |
Stop Mode | 0: Ramp to Stop/ 1: Coast to Stop |
– |
1 |
Motor HP |
IDM-1007M | [0.5HP] [0.75HP] [1.0HP] | |
IDM-1015M |
[0.5HP] [0.75HP] [1.0HP] [1.5HP] [2.0HP] | ||
IDM-1022M |
[0.5HP] [0.75HP] [1.0HP] [1.5HP] [2.0HP] [2.5HP] [3.0HP] | ||
Overload Rate | 50 ~ 200 | % | 150 |
Overload Time | 2.0 ~ 999 | Sec | 10.0 |
Over-Voltage Rate | 100 ~ 200 | % | 120 |
Low-Voltage Rate | 70 ~ 90 | % | 80 |
Carrier Frequency | 3.0 ~ 15.0 | KHz | 8.0 |
INVERTER CONTROL PARAMETER
Max. Output Frequency | This parameter determines the inverters max. output frequency. |
Max. Voltage Frequency | This value should be set according to the rated frequency of the motor. |
Mid-Point Frequency |
Refers to the mid-point frequency of the V/F curve. The V/F ratio between the min. frequency and mid-point frequency can be determined. |
Mid-Point Voltage |
Refers to the mid-point voltage of any V/F curve. The V/F ratio between the min. frequency and mid-point frequency can be determined. |
Min.Output Frequency | Refers to the min. output frequency of the inverter. |
Min. Output Voltage | Refers to the min. output voltage of the inverter. |
Acceleration Time |
Refers to the time required for the inverter to accelerate from 0 Hz to its max. output frequency. |
Deceleration Time |
Refers to the time required for the inveter to decelerate from the max. output frequency down to 0 Hz. |
Stop Mode |
1. Ramp: the inverter decelerates the motor to min. output frequency then stops according to the set deceleration time. |
2. Coast: the inverter stops output instantly upon command, and the motor free runs until it comes to a complete stop. | |
Motor HP | Displays the inverter HP that is currently being utilized. |
Overload Rate | Refers to the trip current level against the rated current of the motor. |
Overload Time | Refers to the maintaining time of the overload trip level to generate the overload trip. |
Over-Voltage Rate | Refers to over-voltage protection. |
Low-Voltage Rate | Refers to the low-voltage protection. |
Carrier Frequency |
Refers to the trip current level against the rated current of the motor. |
SYSTEM PARAMETER SETTING
Parameters | Input Range | Default |
Power Outage Restart |
[System Stop] [System Run] [Backup State] |
Backup State |
Language | [Korean] [English] | English |
Password (0000: Not Used) |
0000 ~ 9999 |
0000 |
Test Code | 0000 ~ 9999 | 0000 |
Display | Alarm Type | Corrective Action |
Comm Fail |
Communication Fail |
Check the connection status between the master and slave pumps. |
Sensor Open |
Sensor Open |
Check if the sensor connection has been properly performed. Replace the sensor if the error still occurs after checking the connection. |
Sen.Short |
Sensor Short |
Check if the sensor connection has been properly performed. Replace the sensor if the error still occurs after checking the connection. |
High Pres. |
High Pressure |
Check the set pressure and high pressure setting values within the parameters. |
Low Pres. |
Low Pressure |
Check if the suction pipeline is filled with water and also release air from the air vent on the pump if neccessary. |
L-Pre. Stop |
Low Pressure Stop |
Check if the suction pipeline is filled with water and also release air from the air vent on the pump if neccessary. |
Low Current |
Low Current |
Check if the suction pipeline is filled with water and also release air from the air vent on the pump if neccessary. |
L-Cur. Stop |
Low Current Stop |
Check if the suction pipeline is filled with water and also release air from the air vent on the pump if neccessary. |
Overload |
Overload |
Check the rated current of the motor and the rated current setting on the inverter |
Over Cur. |
Over Current |
Check the Acc./Dec time. Also, check if the inverter capacity is suitable for the motor that is being installed. |
Low Volt. |
Low Voltage |
Check the input voltage and power capacity. |
Over Heat | Over Heat | Contact your local supplier. |
Over Volt. |
Over Voltage |
Check the supply voltage and increase the deceleration time. |
1-21 Monash Drive, Dandenong South, VIC 3175 Australia | 1300 137 344 | pentair.com.au
Information contained here-in remains the property of Pentair under Australian copyright law. Any reproduction, display, publication, modification or distribution is strictly prohibited without the prior written permission from Pentair.
Disclaimer: Pentair reserves the right to change product specifications and products details.
All product images are for reference purposes only and may not represent actual and/or current product.
©2022 Pentair. All rights reserved.