Fitur utama kalebu: Start / Stop, 0-10V Speed ​​Reference, Speed ​​Reference Feedback
Parameter & Nilai RM6G1 Katrangan Parameter Komentar
# Nilai Komentar Nilai standar ing kurung (xxxxxx) Mfg / Panganggo
A1-05 DF-HD Mode tugas abot HD: mode tugas abot Setel mode HD dhisik
A1-04   Vol inputtage Setelan 100.0~300.0V (seri 220V) 240.0~500.0V (seri 380V) Setel menyang Motor Voltage
A3-16 0 Tampilan 0: Pateni - Ganti Tampilan  
A3-23 104 Dual Tampilan 104 – Sisih kiwa nuduhake output amps / Sisih tengen nuduhake Tampilan Utama  
B1-00 2 Pilihan Frekuensi Utama 2: Input Analog (Vin 1)  
B1-02 1 Command Mulai Utama 1: Input Digital (X1)  
B1-04 1 utami

Komando Arah

1: Input Digital (X1)  
B1-10 1 Metode Stop 1: Pesisir mandheg  
b1-11 1 Pilihan Operasi Balik 1: dipatèni  
C1-01 10/15 Wektu Akselerasi (detik) 10 detik - Wektu Percepatan saka Frekuensi Min nganti Frekuensi Maks 15 detik kanggo Centrifugal
C1-02 10/60 Wektu Perlambatan (detik) 10 sec -Deceleration Wektu saka Max Frequency kanggo Min Ffrequency 60 detik kanggo Centrifugal
D2-02 0.50 Frekuensi Watesan Ngisor (%) 0.50 = 50% 0.70 = 70% kanggo Centrifugal
E1-01 Maksimum Output Voltage Adhedhasar Motor Voltage 0.0-300.0V (seri 220V)

0.0~550.0V (seri 380V)

Setel menyang Motor Votage
E1-03 Pangkalan Voltage 0.0-300.0V (seri 220V)

0.0~550.0V (seri 380V)

Setel menyang Base Voltage
 

 

E2-01

Model 200 V 010 016 022 031 042 060 075 090 112 150 185 220 275 346 410 500 700 840  
Dirating Output (A) 8 11 17 25 33 46 63 75 90 115 150 185 220 295 346 432 585 700
Model 400 V 009 012 018 023 031 039 045 058 075 091 110 144 180 216 253 304 377 415 480 585 700 860 960
Dirating Output (A) 6 9 14 18 24 30 39 45 61 75 91 115 150 180 216 253 310 377 432 480 585 700 866
H1-00 +2 Terminal Input Multi-Fungsi (X1) +2 FWD Command (X1)

VFD-R2 / VFD-R4 MODEL RM6G1 MODBUS PKS

SISTEM KONTROL MIKRO RM6G1 Series Variabel Speed ​​Drive - Diagram 1

VFD-R2 / VFD-R4 MODEL RM6G1 MODBUS PKS

Fitur utama kalebu: Start / Stop, 0-10V Speed ​​Reference, Speed ​​Reference Feedback
Parameter & Nilai RM6G1 Katrangan Parameter Komentar
# Nilai Komentar Nilai standar ing kurung (xxxxxx) Mfg / Panganggo
A1-05 DF-HD Mode tugas abot HD: mode tugas abot Setel mode HD dhisik
A1-04   Vol inputtage Setelan 100.0~300.0V (seri 220V) 240.0~500.0V (seri 380V) Setel menyang Motor Voltage
A3-16 0 Tampilan 0: Pateni - Ganti Tampilan  
A3-23 104 Dual Tampilan 104 – Sisih kiwa nuduhake output amps / Sisih tengen nuduhake Tampilan Utama  
B1-00 3 Pilihan Frekuensi Utama 3: Komunikasi Modbus  
B1-02 2 Command Mulai Utama 2: Komunikasi Modbus  
B1-04 2 Komando Arah Utama 2: Komunikasi Modbus  
B1-10 1 Metode Stop 1: Pesisir mandheg  
b1-11 1 Pilihan Operasi Balik 1: dipatèni  
C1-01 10/15 Wektu Akselerasi (detik) 10 detik - Wektu Percepatan saka Frekuensi Min nganti Frekuensi Maks 15 detik kanggo Centrifugal
C1-02 10/60 Wektu Perlambatan (detik) 10 sec -Deceleration Wektu saka Max Frequency kanggo Min Ffrequency 60 detik kanggo Centrifugal
D2-02 0.50 Frekuensi Watesan Ngisor (%) 0.50 = 50% 0.70=70%
kanggo Centrifugal
E1-01 Maksimum Output Voltage Adhedhasar Motor Voltage 0.0-300.0V (seri 220V)
0.0~550.0V (seri 380V)
Setel menyang Motor Votage
E1-03 Pangkalan Voltage 0.0-300.0V (seri 220V)
0.0~550.0V (seri 380V)
Setel menyang Base Voltage
 

 

 

E2-01

Model 200 V 010 016 022 031 042 060 075 090 112 150 185 220 275 346 410 500 700 840  
Dirating Output (A) 8 11 17 25 33 46 63 75 90 115 150 185 220 295 346 432 585 700
Model 400 V 009 012 018 023 031 039 045 058 075 091 110 144 180 216 253 304 377 415 480 585 700 860 960
Dirating Output (A) 6 9 14 18 24 30 39 45 61 75 91 115 150 180 216 253 310 377 432 480 585 700 866
H1-00 -22 Terminal Input Multi-Fungsi (X1) -22 FWD External Fault - Interlock Relay  
H5-00 1 Comm. alamat 1: Alamat Modbus  
H5-01 38400 Baud Rate 38400 Baud Rate ing Komunikasi Modbus  
H5-04 2 Comm. Pembuangan Lembur (COT) 2: Terus Mlaku ing Kehilangan Komunikasi (Interlock bakal mungkasi VFD)  
H5-05 5 Comm. Lembur (COT) 0.0 ~ 100.0 sec – Wektu Metu  

SISTEM KONTROL MICRO - logo

Dokumen / Sumber Daya

SISTEM KONTROL MICRO RM6G1 Series Variabel Speed ​​Drive [pdf] Pandhuan Instalasi
RM6G1 Series Variable Speed ​​Drive, RM6G1 Series, Variable Speed ​​Drive, Speed ​​Drive, Drive

Referensi

Ninggalake komentar

Alamat email sampeyan ora bakal diterbitake. Kolom sing dibutuhake ditandhani *