RM6G1 Series Variable Speed Drive
Installation Guide
RM6G1 Series Variable Speed Drive
Any questions regarding this release, contact: support@mcscontrols.com
Micro Control Systems, Inc. 5580 Enterprise Parkway Fort Myers, Florida 33905
(239)694-0089 FAX: (239)694-0031 www.mcscontrols.com
Information contained in this document has been prepared by Micro Control Systems, Inc. and is copyright © protected 2023.
Copying or distributing this document is prohibited unless expressly approved by MCS.
VFD-R2 / VFD-R4 MODELS RM6G1 Hardwired Diagram
VFD-R2 / VFD-R4 MODELS
RM6G1 Hardwired VFD SETTINGS
Key features include: Start/Stop, 0-10V Speed Reference, Speed Reference Feedback | ||||||||||||||||||||||||
RM6G1 Parameters & Values | Parameter Description | Comments | ||||||||||||||||||||||
# | Value | Comments | Default values in parenthesis (xxxxxx) | Mfg / User | ||||||||||||||||||||
A1-05 | DF-HD | Heavy Duty Mode | HD:heavy duty mode | Set mode first HD | ||||||||||||||||||||
A1-04 | Input Voltage Setting | 100.0~300.0V(220V series) 240.0~500.0V (380V series) | Set to Motor Voltage | |||||||||||||||||||||
A3-16 | 0 | Display | 0: Disable – Alternately Display | |||||||||||||||||||||
A3-23 | 104 | Dual Display | 104 – Left side shows output amps / Right side shows Main Display | |||||||||||||||||||||
B1-00 | 2 | Primary Frequency Selection | 2: Analog Input (Vin 1) | |||||||||||||||||||||
B1-02 | 1 | Primary Start Command | 1: Digital Input (X1) | |||||||||||||||||||||
B1-04 | 1 | Primary
Direction Command |
1: Digital Input (X1) | |||||||||||||||||||||
B1-10 | 1 | Stop Method | 1: Coast to stop | |||||||||||||||||||||
b1-11 | 1 | Reverse Operation Selection | 1: Disabled | |||||||||||||||||||||
C1-01 | 10/15 | Acceleration Time (sec) | 10 sec – Acceleration Time from Min Frequency to Max Frequency | 15 sec for Centrifugal | ||||||||||||||||||||
C1-02 | 10/60 | Deceleration Time (sec) | 10 sec -Deceleration Time from Max Frequency to Min Ffrequency | 60 sec for Centrifugal | ||||||||||||||||||||
D2-02 | 0.50 | Frequency Lower Limit (%) | 0.50 = 50% | 0.70=70% for Centrifugal | ||||||||||||||||||||
E1-01 | Maximun Output Voltage Based on Motor Voltage | 0.0-300.0V (220V series)
0.0~550.0V (380V series) |
Set to Motor Votage | |||||||||||||||||||||
E1-03 | Base Voltage | 0.0-300.0V (220V series)
0.0~550.0V (380V series) |
Set to Base Voltage | |||||||||||||||||||||
E2-01 |
Model 200V | 010 | 016 | 022 | 031 | 042 | 060 | 075 | 090 | 112 | 150 | 185 | 220 | 275 | 346 | 410 | 500 | 700 | 840 | |||||
Rated Output (A) | 8 | 11 | 17 | 25 | 33 | 46 | 63 | 75 | 90 | 115 | 150 | 185 | 220 | 295 | 346 | 432 | 585 | 700 | ||||||
Model 400V | 009 | 012 | 018 | 023 | 031 | 039 | 045 | 058 | 075 | 091 | 110 | 144 | 180 | 216 | 253 | 304 | 377 | 415 | 480 | 585 | 700 | 860 | 960 | |
Rated Output (A) | 6 | 9 | 14 | 18 | 24 | 30 | 39 | 45 | 61 | 75 | 91 | 115 | 150 | 180 | 216 | 253 | 310 | 377 | 432 | 480 | 585 | 700 | 866 | |
H1-00 | +2 | Multi-Function Input Terminal (X1) | +2 FWD Command (X1) |
VFD-R2 / VFD-R4 MODELS RM6G1 MODBUS VFD SETTINGS
VFD-R2 / VFD-R4 MODELS RM6G1 MODBUS VFD SETTINGS
Key features include: Start/Stop, 0-10V Speed Reference, Speed Reference Feedback | |||||||||||||||||||||||||
RM6G1 Parameters & Values | Parameter Description | Comments | |||||||||||||||||||||||
# | Value | Comments | Default values in parenthesis (xxxxxx) | Mfg / User | |||||||||||||||||||||
A1-05 | DF-HD | Heavy Duty Mode | HD:heavy duty mode | Set mode first HD | |||||||||||||||||||||
A1-04 | Input Voltage Setting | 100.0~300.0V(220V series) 240.0~500.0V (380V series) | Set to Motor Voltage | ||||||||||||||||||||||
A3-16 | 0 | Display | 0: Disable – Alternately Display | ||||||||||||||||||||||
A3-23 | 104 | Dual Display | 104 – Left side shows output amps / Right side shows Main Display | ||||||||||||||||||||||
B1-00 | 3 | Primary Frequency Selection | 3: Modbus Communications | ||||||||||||||||||||||
B1-02 | 2 | Primary Start Command | 2: Modbus Communications | ||||||||||||||||||||||
B1-04 | 2 | Primary Direction Command | 2: Modbus Communications | ||||||||||||||||||||||
B1-10 | 1 | Stop Method | 1: Coast to stop | ||||||||||||||||||||||
b1-11 | 1 | Reverse Operation Selection | 1: Disabled | ||||||||||||||||||||||
C1-01 | 10/15 | Acceleration Time (sec) | 10 sec – Acceleration Time from Min Frequency to Max Frequency | 15 sec for Centrifugal | |||||||||||||||||||||
C1-02 | 10/60 | Deceleration Time (sec) | 10 sec -Deceleration Time from Max Frequency to Min Ffrequency | 60 sec for Centrifugal | |||||||||||||||||||||
D2-02 | 0.50 | Frequency Lower Limit (%) | 0.50= 50% | 0.70=70% for Centrifugal |
|||||||||||||||||||||
E1-01 | Maximun Output Voltage Based on Motor Voltage | 0.0-300.0V (220V series) 0.0~550.0V (380V series) |
Set to Motor Votage | ||||||||||||||||||||||
E1-03 | Base Voltage | 0.0-300.0V (220V series) 0.0~550.0V (380V series) |
Set to Base Voltage | ||||||||||||||||||||||
E2-01 |
Model 200V | 010 | 016 | 022 | 031 | 042 | 060 | 075 | 090 | 112 | 150 | 185 | 220 | 275 | 346 | 410 | 500 | 700 | 840 | ||||||
Rated Output (A) | 8 | 11 | 17 | 25 | 33 | 46 | 63 | 75 | 90 | 115 | 150 | 185 | 220 | 295 | 346 | 432 | 585 | 700 | |||||||
Model 400V | 009 | 012 | 018 | 023 | 031 | 039 | 045 | 058 | 075 | 091 | 110 | 144 | 180 | 216 | 253 | 304 | 377 | 415 | 480 | 585 | 700 | 860 | 960 | ||
Rated Output (A) | 6 | 9 | 14 | 18 | 24 | 30 | 39 | 45 | 61 | 75 | 91 | 115 | 150 | 180 | 216 | 253 | 310 | 377 | 432 | 480 | 585 | 700 | 866 | ||
H1-00 | -22 | Multi-Function Input Terminal (X1) | -22 FWD External Fault – Interlock Relay | ||||||||||||||||||||||
H5-00 | 1 | Comm. Address | 1: Modbus Address | ||||||||||||||||||||||
H5-01 | 38400 | Baud Rate | 38400 Baud Rate on Modbus Communication | ||||||||||||||||||||||
H5-04 | 2 | Comm. Overtime Disposal (COT) | 2: Keep Running on Loss of Communication (Interlock will stop VFD) | ||||||||||||||||||||||
H5-05 | 5 | Comm. Overtime(COT) | 0.0 ~ 100.0 sec – Time Out |
Documents / Resources
![]() |
MICRO CONTROL SYSTEMS RM6G1 Series Variable Speed Drive [pdf] Installation Guide RM6G1 Series Variable Speed Drive, RM6G1 Series, Variable Speed Drive, Speed Drive, Drive |