MICRO CONTROL SYSTEMS - logoRM6G1 Series Variable Speed Drive
Installation GuideMICRO CONTROL SYSTEMS RM6G1 Series Variable Speed Drive

RM6G1 Series Variable Speed Drive

Any questions regarding this release, contact: support@mcscontrols.com
Micro Control Systems, Inc. 5580 Enterprise Parkway Fort Myers, Florida 33905
(239)694-0089 FAX: (239)694-0031 www.mcscontrols.com
Information contained in this document has been prepared by Micro Control Systems, Inc. and is copyright © protected 2023.
Copying or distributing this document is prohibited unless expressly approved by MCS.

VFD-R2 / VFD-R4 MODELS RM6G1 Hardwired Diagram

MICRO CONTROL SYSTEMS RM6G1 Series Variable Speed Drive - Diagram

VFD-R2 / VFD-R4 MODELS
RM6G1 Hardwired VFD SETTINGS

Key features include: Start/Stop, 0-10V Speed Reference, Speed Reference Feedback
RM6G1 Parameters & Values Parameter Description Comments
# Value Comments Default values in parenthesis (xxxxxx) Mfg / User
A1-05 DF-HD Heavy Duty Mode HD:heavy duty mode Set mode first HD
A1-04   Input Voltage Setting 100.0~300.0V(220V series) 240.0~500.0V (380V series) Set to Motor Voltage
A3-16 0 Display 0: Disable – Alternately Display  
A3-23 104 Dual Display 104 – Left side shows output amps / Right side shows Main Display  
B1-00 2 Primary Frequency Selection 2: Analog Input (Vin 1)  
B1-02 1 Primary Start Command 1: Digital Input (X1)  
B1-04 1 Primary

Direction Command

1: Digital Input (X1)  
B1-10 1 Stop Method 1: Coast to stop  
b1-11 1 Reverse Operation Selection 1: Disabled  
C1-01 10/15 Acceleration Time (sec) 10 sec – Acceleration Time from Min Frequency to Max Frequency 15 sec for Centrifugal
C1-02 10/60 Deceleration Time (sec) 10 sec -Deceleration Time from Max Frequency to Min Ffrequency 60 sec for Centrifugal
D2-02 0.50 Frequency Lower Limit (%) 0.50 = 50% 0.70=70% for Centrifugal
E1-01 Maximun Output Voltage Based on Motor Voltage 0.0-300.0V (220V series)

0.0~550.0V (380V series)

Set to Motor Votage
E1-03 Base Voltage 0.0-300.0V (220V series)

0.0~550.0V (380V series)

Set to Base Voltage
 

 

E2-01

Model 200V 010 016 022 031 042 060 075 090 112 150 185 220 275 346 410 500 700 840  
Rated Output (A) 8 11 17 25 33 46 63 75 90 115 150 185 220 295 346 432 585 700
Model 400V 009 012 018 023 031 039 045 058 075 091 110 144 180 216 253 304 377 415 480 585 700 860 960
Rated Output (A) 6 9 14 18 24 30 39 45 61 75 91 115 150 180 216 253 310 377 432 480 585 700 866
H1-00 +2 Multi-Function Input Terminal (X1) +2 FWD Command (X1)

VFD-R2 / VFD-R4 MODELS RM6G1 MODBUS VFD SETTINGS

MICRO CONTROL SYSTEMS RM6G1 Series Variable Speed Drive - Diagram 1

VFD-R2 / VFD-R4 MODELS RM6G1 MODBUS VFD SETTINGS

Key features include: Start/Stop, 0-10V Speed Reference, Speed Reference Feedback
RM6G1 Parameters & Values Parameter Description Comments
# Value Comments Default values in parenthesis (xxxxxx) Mfg / User
A1-05 DF-HD Heavy Duty Mode HD:heavy duty mode Set mode first HD
A1-04   Input Voltage Setting 100.0~300.0V(220V series) 240.0~500.0V (380V series) Set to Motor Voltage
A3-16 0 Display 0: Disable – Alternately Display  
A3-23 104 Dual Display 104 – Left side shows output amps / Right side shows Main Display  
B1-00 3 Primary Frequency Selection 3: Modbus Communications  
B1-02 2 Primary Start Command 2: Modbus Communications  
B1-04 2 Primary Direction Command 2: Modbus Communications  
B1-10 1 Stop Method 1: Coast to stop  
b1-11 1 Reverse Operation Selection 1: Disabled  
C1-01 10/15 Acceleration Time (sec) 10 sec – Acceleration Time from Min Frequency to Max Frequency 15 sec for Centrifugal
C1-02 10/60 Deceleration Time (sec) 10 sec -Deceleration Time from Max Frequency to Min Ffrequency 60 sec for Centrifugal
D2-02 0.50 Frequency Lower Limit (%) 0.50= 50% 0.70=70%
for Centrifugal
E1-01 Maximun Output Voltage Based on Motor Voltage 0.0-300.0V (220V series)
0.0~550.0V (380V series)
Set to Motor Votage
E1-03 Base Voltage 0.0-300.0V (220V series)
0.0~550.0V (380V series)
Set to Base Voltage
 

 

 

E2-01

Model 200V 010 016 022 031 042 060 075 090 112 150 185 220 275 346 410 500 700 840  
Rated Output (A) 8 11 17 25 33 46 63 75 90 115 150 185 220 295 346 432 585 700
Model 400V 009 012 018 023 031 039 045 058 075 091 110 144 180 216 253 304 377 415 480 585 700 860 960
Rated Output (A) 6 9 14 18 24 30 39 45 61 75 91 115 150 180 216 253 310 377 432 480 585 700 866
H1-00 -22 Multi-Function Input Terminal (X1) -22 FWD External Fault – Interlock Relay  
H5-00 1 Comm. Address 1: Modbus Address  
H5-01 38400 Baud Rate 38400 Baud Rate on Modbus Communication  
H5-04 2 Comm. Overtime Disposal (COT) 2: Keep Running on Loss of Communication (Interlock will stop VFD)  
H5-05 5 Comm. Overtime(COT) 0.0 ~ 100.0 sec – Time Out  