Danfoss AS-CX06 Programmable Controller

Danfoss-AS-CX06-Programmable-Controller-PRODUCT

Spesifikasi

  • Model: Pengontrol Programmable Tipe AS-CX06
  • ukuran: 105mm x 44.5mm x 128mm (Tanpa tampilan LCD)
  • Maks. Node RS485: Nganti 100
  • Maks. Baudrate RS485: 125 kbit/s
  • Maks. Node BISA FD: Nganti 100
  • Maks. Baudrate CAN FD: 1 Mbit/s
  • Panjang kabel RS485: Nganti 1000m
  • Wire Length BISA FD: Nganti 1000m

Pandhuan Panggunaan Produk

Sambungan Sistem
Kontroler AS-CX06 bisa disambungake menyang macem-macem sistem lan piranti, kalebu:

  • RS485 nganti BMS (BACnet, Modbus)
  • USB-C kanggo sambungan Stepper Driver dibangun ing
  • Sambungan PC liwat Pen drive
  • Sambungan Cloud langsung
  • Bus internal kanggo ekspansi I / O
  • port Ethernet kanggo macem-macem protokol kalebu Web, BACnet, Modbus, MQTT, SNMP, lsp.
  • Sambungan menyang pengontrol AS-CX tambahan utawa HMI remot Alsmart

RS485 lan CAN FD Komunikasi
Port RS485 lan CAN FD digunakake kanggo komunikasi karo sistem fieldbus, BMS, lan piranti liyane. Rincian utama kalebu:

  • RS485 topologi bus kudu line mandap karo external 120 Ohm resistor ing loro ends ing lingkungan Kagodha.
  • Maks. jumlah simpul kanggo RS485: Nganti 100
  • Komunikasi CAN FD digunakake kanggo komunikasi piranti-kanggo-piranti kanthi syarat topologi sing padha karo RS485.
  • Maks. jumlah simpul kanggo CAN FD: Nganti 100

Papan Input lan Output
AS-CX06 nampilake papan ndhuwur lan ngisor kanggo macem-macem input lan output kalebu sinyal analog lan digital, sambungan Ethernet, input modul serep baterei, lan liya-liyane.

Identifikasi

Danfoss AS-CX06 Lite Programmable Controller

AS-CX06 Lite 080G6008
AS-CX06 Mid 080G6006
AS-CX06 Mid+ 080G6004
AS-CX06 Pro 080G6002
AS-CX06 Pro+ 080G6000

ukuran

Tanpa tampilan LCD

Danfoss-AS-CX06-Programmable-Controller-FIG- (2)

Kanthi tampilan LCD Snap-on: 080G6016

Danfoss-AS-CX06-Programmable-Controller-FIG- (3)

Sambungan

Sambungan sistemDanfoss-AS-CX06-Programmable-Controller-FIG- (4)Papan Ndhuwur
Danfoss-AS-CX06-Programmable-Controller-FIG- (5)Papan Ngisor
input kanggo modul serep baterei kanggo ngamanake penutupan katup stepper elektronik (eg EKE 2U)
Danfoss-AS-CX06-Programmable-Controller-FIG- (6)

  1. Kasedhiya mung ing: Mid+, Pro+
  2.  Kasedhiya mung ing: Mid, Mid +, Pro, Pro +
  3. SSR Danfoss AS-CX06 Lite Programmable Controller - lambang digunakake ing panggonan relay SPST ing Mid+

Komunikasi data

Ethernet (mung kanggo versi Pro lan Pro+)Danfoss-AS-CX06-Programmable-Controller-FIG- (8)Titik kanggo titik topologi star karo hub jaringan / switch. Saben piranti AS-CX nggabungake saklar kanthi teknologi gagal-aman.

  • Tipe Ethernet: 10/100TX otomatis MDI-X
  • Tipe kabel: Kabel CAT5, maks. 100 m
  • Tipe Konektor Kabelr: rj45

Informasi akses pisanan
Piranti kasebut kanthi otomatis entuk alamat IP saka jaringan liwat DHCP.

Kanggo mriksa alamat IP saiki, penet ENTER Danfoss AS-CX06 Lite Programmable Controller - lambang 1 kanggo ngakses menu setelan gawan banjur pilih Setelan Ethernet.

Ketik alamat IP ing pilihan sampeyan web browser kanggo ngakses web ngarep-mburi. Sampeyan bakal diarahake menyang layar login kanthi kredensial standar ing ngisor iki:

  • Panganggo Default: Admin
  • Sandi Default: Administrator
  • Sandi Numerik Default: 12345 (kanggo digunakake ing layar LCD) Sampeyan bakal dijaluk ngganti tembung sandhi sawise login pisanan sukses.

Cathetan: ora ana cara kanggo njupuk sandi lali.

RS485: Modbus, BACnet
Port RS485 diisolasi lan bisa dikonfigurasi minangka klien utawa server. Iki digunakake kanggo komunikasi sistem fieldbus lan BMS.

Topologi busDanfoss AS-CX06 Lite Programmable Controller - topologi BusRekomendasi jinis kabel:

  • Pasangan bengkong karo lemah: mimpin cendhak (ie <10 m), ora ana kabel listrik ing jarak (min. 10 cm).
  • Pasangan bengkong + lemah lan tameng: timbal dawa (ie> 10 m), EMC- kaganggu lingkungan.

Max.. jumlah node: nganti 100

Panjang kabel (m) Maks. baud rate Min. ukuran kawat
1000 125 kbit/s 0.33 mm2 – 22 AWG

BISA FD
Komunikasi CAN FD digunakake kanggo komunikasi piranti-kanggo-piranti. Uga digunakake kanggo nyambungake Alsmart remot HMI liwat port tampilan.

Topologi busDanfoss AS-CX06 Lite Programmable Controller - Topologi bus 1Jinis kabel:

  • Pasangan bengkong karo lemah: mimpin cendhak (ie <10 m), ora ana kabel listrik ing jarak (min. 10 cm).
  • Pasangan bengkong + lemah lan tameng: ndadékaké dawa (IE> 10 m), EMC kaganggu lingkungan

Max.. jumlah node: nganti 100

Dawane kabel (m) 1000 Maks. baudrate BISA  Min. ukuran kawat
1000 50 kbit/s 0.83 mm2 – 18 AWG
500 125 kbit/s 0.33 mm2 – 22 AWG
250 250 kbit/s 0.21 mm2 – 24 AWG
80 500 kbit/s 0.13 mm2 – 26 AWG
30 1 Mbit/s 0.13 mm2 – 26 AWG

Instalasi RS485 lan CAN FD

  • Loro-lorone fieldbuses saka rong jinis diferensial kabel, lan iku dhasar kanggo komunikasi dipercaya kanggo nyambung kabeh Unit ing jaringan uga karo kabel lemah.
    Gunakake sepasang kabel bengkong kanggo nyambungake sinyal diferensial lan gunakake kabel liyane (kanggo example pasangan bengkong kapindho) kanggo nyambungake lemah. Kanggo example:Danfoss AS-CX06 Lite Programmable Controller - BISA FD
  • Mandap garis kudu ana ing loro bus ends kanggo mesthekake komunikasi sing tepat.
    Penghentian baris bisa diinstal kanthi rong cara:
    1. Nggawe sirkuit cendhak ing terminal CAN-FD H lan R (mung kanggo CANbus);
    2. Sambungake resistor 120 Ω antarane terminal CAN-FD H lan L kanggo CANbus utawa A + lan B- kanggo RS485.
  • Panginstalan kabel komunikasi data kudu ditindakake kanthi bener kanthi jarak sing cukup kanggo vol dhuwurtage kabel.Danfoss AS-CX06 Lite Programmable Controller - dhuwur voltage kab
  • Piranti kasebut kudu disambungake miturut topologi "BUS". Tegese kabel komunikasi disambungake saka piranti siji menyang piranti sabanjure tanpa rintisan.
    Yen stubs ana ing jaringan, mesthine kudu disingkat (<0.3 m ing 1 Mbit; <3 m ing 50 kbit). Elinga yen HMI remot disambungake menyang port tampilan nggawe rintisan.Danfoss AS-CX06 Lite Programmable Controller - tampilan port ndadekake
  • Mesthi ana sambungan lemah sing resik (ora kaganggu) ing antarane kabeh piranti sing disambungake ing jaringan. Unit kasebut kudu duwe lemah ngambang (ora nyambung menyang bumi), sing disambungake ing antarane kabeh unit kanthi kabel lemah.
  •  Ing kasus telung kabel telung konduktor plus tameng, tameng kudu grounded mung ing siji lokasi.Danfoss AS-CX06 Lite Programmable Controller - kabel konduktor

Info pemancar tekanan
Example: DST P110 karo output rasio-metrikDanfoss AS-CX06 Lite Programmable Controller - Pemancar tekananETS Stepper Valve infoDanfoss AS-CX06 Lite Programmable Controller - info Stepper ValveSambungan kabel katup
dawa kabel maksimum: 30 m

CCM / CCMT / CTR / ETS Colibri® / KVS Colibri® / ETS / KVS

Kabel Danfoss M12 Kab Putih  ireng  abang  Ijo
Pin CCM/ETS/KVS 3 4 1 2
CCMT/CTR/ETS Colibri/KVS Colibri Pins A1 A2 B1 B2
Terminal AS-CX A1 A2 B1 B2

ETS 6

Warna kawat  Oranye  kuning abang ireng abu-abu
Terminal AS-CX A1 A2 B1 B2 Ora nyambung

Info AKV (mung kanggo versi Mid+)Danfoss AS-CX06 Lite Programmable Controller - AKV infodata teknis

Spesifikasi listrik

Data listrik Nilai
Pasokan voltage AC/DC [V] 24V AC/DC, 50/60 Hz (1)(2)
Sumber daya [W] 22 W @ 24 V AC, min. 60 V A yen trafo digunakake utawa sumber daya DC 30 W (3)
Ukuran kabel listrik [mm2] 0.2 – 2.5 mm2 kanggo konektor pitch 5 mm 0.14 – 1.5 mm2 kanggo konektor pitch 3.5 mm
  1. 477 5×20 Series saka LittelFuse (0477 3.15 MXP).
  2. Vol DC sing luwih dhuwurtage bisa Applied yen kontrol diinstal ing aplikasi ngendi Produsèn nyatakake standar referensi lan voltage tingkat kanggo sirkuit SELV / PELV diakses kanggo dianggep ora mbebayani dening standar aplikasi. sing voltaglevel e bisa digunakake minangka input sumber daya sanajan 60 V DC ora kudu ngluwihi.
  3. AS: Kelas 2 < 100 VA (3)
  4. Ing kahanan sirkuit cendhak, sumber daya DC kudu bisa nyedhiyakake 6 A kanggo 5 detik utawa daya output rata-rata < 15 W

Spesifikasi Input/Output

  • Panjang kabel maksimal: 30m
  • Input analog: AI1, AI2, AI3, AI4, AI5, AI6, AI7, AI8, AI9, AI10
Jinis Fitur data
0/4-20 mA Akurasi ± 0.5% FS
Resolusi 1 uA
0/5 V Radiometric Relatif kanggo sumber internal 5 V DC (10 – 90 %)
Akurasi ± 0.4% FS
Resolusi 1 mV
0 – 1 V
0 – 5 V
0 – 10 V
Akurasi ± 0.5% FS (FS dimaksudaké khusus kanggo saben jinis)
Resolusi 1 mV
Resistance input > 100 kOhm
PT1000 Meas. jangkoan -60 nganti 180 °C
Akurasi ±0.7 K [-20…+60 °C ], ±1 K liyane
Resolusi 0.1 K
PTC1000 Meas. jangkoan -60…+80 °C
Akurasi ±0.7 K [-20…+60 °C ], ±1 K liyane
Resolusi 0.1 K
NTC10k Meas. jangkoan -50 nganti 200 °C
Akurasi ± 1 K [-30…+200 °C]
Resolusi 0.1 K
NTC5k Meas. jangkoan -50 nganti 150 °C
Akurasi ± 1 K [-35…+150 °C]
Resolusi 0.1 K
Input Digital Stimulasi Voltagkontak e-free
Reresik kontak 20 mA
Fitur liyane Pulse counting fungsi 150 ms denounce time

Input digital: DI1, DI2

Jinis Fitur data
Voltage gratis Stimulasi Voltagkontak e-free
Reresik kontak 20 mA
Fitur liyane Fungsi ngitung pulsa maks. 2 kHz

Output analog: AO1, AO2, AO3

Jinis Fitur data
Maks. momotan 15 mA
0 – 10 V Akurasi Sumber: 0.5% FS
Sink 0.5% FS kanggo Vout > 0.5 V 2% FS kabeh rentang (I<=1mA)
Resolusi 0.1% FS
Async PWM Voltage output Vout_Lo Max = 0.5 V Vout_Hi Min = 9 V
Rentang frekuensi 15 Hz – 2 kHz
Akurasi 1% FS
Resolusi 0.1% FS
Sinkronisasi PWM/PPM Voltage output Vout_Lo Max = 0.4 V Vout_Hi Min = 9 V
Frekuensi Frekuensi listrik x 2
Resolusi 0.1% FS

Output digital

Jinis data
DO1, DO2, DO3, DO4, DO5
Relay SPST 3 A Nominal, 250 V AC 10k siklus kanggo beban resistif UL: FLA 2 A, LRA 12 A
DO5 kanggo Mid+
Relay Negara Solid SPST 230 V AC / 110 V AC / 24 V AC maks 0.5 A
C6
Relay SPDT 3 A Nominal, 250 V AC 10k siklus kanggo beban resistif
Isolasi antarane relay ing grup DO1-DO5 fungsional. Isolasi antarane grup DO1-DO5 lan DO6 dikuatake.
Output motor stepper (A1, A2, B1, B2)
Bipolar / Unipolar Katup Danfoss:
• ETS / KVS / ETS C / KVS C / CCMT 2–CCMT 42 / CTR
•   ETS6 / CCMT 0 / CCMT 1 Katup liyane:
•   Kacepetan 10 – 300 pps
•   Mode drive full step – 1/32 microstep
•   Maks. arus fase puncak: 1 A
•   Daya output: Puncak 10 W, rata-rata 5 W
Baterei serep Baterei V: 18 – 24 V DC(1), maks. daya 11 W, min. kapasitas 0.1 Wh

Output daya Aux

Jinis Fitur data
+5 V +5 V DC Sumber sensor: 5 V DC / 80 mA
+15 V +15 V DC Sumber sensor: 15 V DC / 120 mA

Data fungsi

Data fungsi Nilai
Tampilan LCD 128 x 64 piksel (080G6016)
LED Green, Orange, Red LED dikontrol dening aplikasi piranti lunak.
Sambungan tampilan njaba RJ12
Komunikasi data built-in MODBUS, BACnet kanggo fieldbus lan komunikasi menyang sistem BMS.
SMNP kanggo komunikasi menyang sistem BMS. HTTP(S), MQTT(S) kanggo komunikasi kanggo web browser lan awan.
Akurasi jam +/- 15 ppm @ 25 °C, 60 ppm @ (-20 nganti +85 °C)
Cadangan daya serep baterei jam 3 dina @ 25 °C
USB-C USB Version 1.1 / 2.0 kacepetan dhuwur, DRP lan DRD support. Maks. saiki 150 mA Kanggo sambungan menyang pen drive lan laptop (waca Pandhuan pangguna).
Pemasangan DIN rel, posisi vertikal
omah plastik V0 pemadam dhewe lan tes kabel mencorong/panas ing 960 °C. Tes bal: 125 °C Arus bocor: ≥ 250 V miturut IEC 60112
Jinis kontrol Digabungake ing peralatan Kelas I lan / utawa II
Jinis tumindak 1C; 1Y kanggo versi karo SSR
Periode tegangan listrik ngliwati insulasi dawa
polusi Cocog kanggo digunakake ing lingkungan kanthi tingkat polusi 2
Kekebalan marang voltage mundhak Kategori II
Kelas lan struktur piranti lunak kelas A

kahanan lingkungan

kahanan lingkungan Nilai
Kisaran suhu sekitar, operasi [°C] -40 nganti +70 °C kanggo versi Lite, Mid, Pro.
-40 kanggo +70 °C kanggo Mid +, Pro + versi tanpa ekspansi I / O ditempelake.
-40 kanggo +65 ° C yen ora.
Kisaran suhu sekitar, transportasi [°C] -40 nganti +80 °C
Rating kandang IP IP20
IP40 ing ngarep nalika piring utawa tampilan dipasang
Rentang asor relatif [%] 5 - 90%, non-kondensasi
Maks. dhuwur instalasi 2000 m

swara listrik
Kabel kanggo sensor, vol rendahtagInput e DI lan komunikasi data kudu dipisahake saka kabel listrik liyane:

  • Gunakake tray kabel sing kapisah
  • Jaga jarak antarane kabel paling sethithik 10 cm
  • Tansah kabel I / O minangka cendhak sabisa

pertimbangan instalasi

  • Kontroler mung kudu dipasang, dilayani lan dipriksa dening personel sing mumpuni lan tundhuk karo peraturan nasional lan lokal.
  • Sadurunge nglayani peralatan kasebut, pengontrol kudu dicopot saka sumber daya kanthi mindhah saklar utama sistem menyang OFF.
  • Nggunakake sumber voltage liyane saka kasebut bisa akeh ngrusak sistem.
  • Kabeh safety ekstra kurang voltagsambungan e (input analog lan digital, output analog, sambungan bus serial, sumber daya) kudu duwe jampel sing tepat saka sumber daya.
  • Aja ndemek utawa meh ndemek komponen elektronik sing dipasang ing papan kanggo ngindhari pelepasan elektrostatik saka operator menyang komponen, sing bisa nyebabake karusakan gedhe.
  • Aja pencet screwdriver ing konektor karo pasukan gedhe banget, supaya ora ngrusak controller.
  • Kanggo mesthekake cooling konveksi sing cukup disaranake ora ngalangi bukaan ventilasi.
  • Kerusakan sing ora disengaja, instalasi sing ora apik, utawa kahanan situs bisa nyebabake kerusakan sistem kontrol, lan pungkasane nyebabake kerusakan tanduran.
  • Saben pangayoman bisa digabung menyang produk kita kanggo nyegah iki. Nanging, instalasi sing salah isih bisa nyebabake masalah. Kontrol elektronik ora bisa ngganti praktik teknik sing normal lan apik.
  • Sajrone instalasi, priksa manawa cara sing tepat digawe kanggo nyegah kabel bisa ngeculake lan nggawe risiko potensial babagan kejut utawa geni.
  • Danfoss ora bakal tanggung jawab kanggo samubarang barang, utawa komponen tanduran, rusak minangka asil saka cacat ndhuwur. Iku tanggung jawab installer kanggo mriksa instalasi sak tenane lan pas karo piranti safety perlu.
  • Agen Danfoss lokal sampeyan bakal seneng menehi saran luwih lanjut.

Sertifikat, deklarasi, lan persetujuan (in progress)

Tandhani(4) negara
CE EU
cULus (mung kanggo AS-PS20) NAM (AS lan Kanada)
kurus NAM (AS lan Kanada)
ekstensi RCM Australia/Selandia Anyar
EAC Armenia, Kyrgyzstan, Kazakhstan
UA Ukraina

Dhaptar kasebut ngemot persetujuan utama kanggo jinis produk iki. Nomer kode individu bisa uga duwe sawetara utawa kabeh persetujuan kasebut, lan persetujuan lokal tartamtu bisa uga ora katon ing dhaptar.

Sawetara persetujuan bisa uga isih ditindakake lan liyane bisa uga owah saka wektu. Sampeyan bisa mriksa status paling anyar ing pranala sing dituduhake ing ngisor iki.

Pranyatan kesesuaian EU bisa ditemokake ing kode QR.

Danfoss-AS-CX06-Programmable-Controller-FIG- (19)

Informasi babagan panggunaan karo refrigeran sing gampang kobong lan liya-liyane bisa ditemokake ing Pranyatan Produsen ing kode QR.

Danfoss-AS-CX06-Programmable-Controller-FIG- (20)

Informasi babagan panggunaan refrigeran sing gampang kobong lan liya-liyane bisa ditemokake ing Pranyatan Produsen ing kode QR.

DanfossA/S
Solusi Iklim • danfoss.com • +45 7488 2222

Informasi apa wae, kalebu, nanging ora winates ing informasi babagan pilihan produk, aplikasi utawa panggunaan, desain produk, bobot, dimensi, kapasitas utawa data teknis liyane ing manual produk, katrangan katalog, pariwara, lsp. lan kasedhiya kanthi nulis. , lisan, elektronik, ing baris utawa liwat download, bakal dianggep informatif, lan mung naleni yen lan kanggo ombone, referensi eksplisit digawe ing kutipan utawa konfirmasi pesenan. Danfoss ora bisa nampa tanggung jawab kanggo kesalahan ing katalog, brosur, video lan materi liyane. Danfoss duwe hak kanggo ngganti produke tanpa kabar. Iki uga ditrapake kanggo produk sing dipesen nanging ora
dikirim kasedhiya yen owah-owahan kuwi bisa digawe tanpa owah-owahan ing wangun, utawa fungsi produk.

Kabeh merek dagang ing materi iki minangka properti saka Danfoss A/5 utawa perusahaan grup Danfoss. Danfoss lan logo Danfoss minangka merek dagang saka Danfoss A/5. Kabeh hak dilindhungi undhang-undhang.

FAQ

P: Carane aku bisa ngakses web ngarep-mburi saka AS-CX06?
A: Ketik alamat IP ing pilihan sampeyan web browser. Kredensial standar yaiku: Panganggo Default: Admin, Sandi Default: Administrator, Sandi Numerik Default: 12345 (kanggo layar LCD).

P: Apa dawa kabel maksimum sing didhukung dening sambungan RS485 lan CAN FD?
A: Koneksi RS485 lan CAN FD ndhukung dawa kawat nganti 1000m.

P: Apa pengontrol AS-CX06 bisa disambungake menyang sawetara pengontrol AS-CX utawa piranti eksternal?
A: Ya, pengontrol AS-CX06 ndhukung sambungan menyang sawetara pengontrol AS-CX, sensor eksternal, sistem fieldbus, lan liya-liyane.

Dokumen / Sumber Daya

Danfoss AS-CX06 Programmable Controller [pdf] Pandhuan Instalasi
AS-CX06 Lite, AS-CX06 Mid, AS-CX06 Mid, AS-CX06 Pro, AS-CX06 Pro, AS-CX06 Programmable Controller, AS-CX06, Programmable Controller, Controller