AKS 38

AKS 38 Level Controller

Danfoss AKS 38 Level ControllerDanfoss AKS 38 Level Controller - Gambar 4Danfoss AKS 38 Level Controller - Gambar 6

Kulkas
AKS 38 bisa digunakake kanggo kabeh refrigerants non-flammable umum, kalebu R717 lan non-korosif gas / Cairan gumantung kompatibilitas materi sealing.
Hidrokarbon sing gampang kobong ora dianjurake.
Kisaran suhu
-50°C/+65°C (-58°F/149°F)
Range tekanan
AKS 38 dirancang kanggo tekanan kerja maksimal 28 bar g (406 psig)
Danfoss AKS 38 Level Controller - Simbol PENTING
IG Yen tes tekanan luwih saka 28 bar g (406 psig) perlu, perakitan float internal kudu dicopot, saéngga tekanan tes maksimal 42 bar g (609 psig)
Data listrik

  • Switch-over Micro (SPDT) ngalih
  • 250 Vac/10 A
  • 30 V dc/5A
  • DIN Plug
  • DIN 43650 sambungan
  • PG 11, 8-10 mm (0.31″-0.39″)
  • Terminal sekrup 1.5 mm² (16 AWG)
  • 3+PE

Diferensial tingkat cairan
Variabel antarane 12.5 mm nganti 50 mm (1½ "nganti 2") kanthi tambahan 12.5 mm (1/2".
Setelan diferensial sing dibutuhake kudu digawe sadurunge instalasi.
Pabrik disetel ing 50 mm (2″).
Enclosure
IP 65

Instalasi

Danfoss AKS 38 Level Controller - Simbol PENTING
AKS 38 kudu tansah diinstal ing posisi vertikal (fig. 1 lan 2).
AKS 38 diwenehake lengkap karo flanges (anjir 2, pos. 14). Permukaan njaba flanges kudu dicegah saka korosi kanthi jas pelindung sing cocog sawise dipasang.
Kanggo ngindhari segel lenga sing bakal mengaruhi gerakan ngambang internal, pipa sambungan ngisor kudu miring menyang pemisah cair.
Klep mateni kudu dipasang kanthi cedhak karo float kanggo layanan (gambar 1).
Ngalih titik
Titik ngalih relatif marang tandha tingkat Cairan nyata ing omah AKS 38. Waca anjir 7.
Titik ngalih ndhuwur bener (D: 2) luwih dhuwur tinimbang tandha level cairan sing nyata.
Titik ngalih ngisor bener (D: 2) luwih murah tinimbang tandha level cairan sing nyata. Where D diferensial.
Nyetel titik switch diferensial level cairan (pirsani anjir 9)
Float dilengkapi setelan pabrik kanthi setelan diferensial 50 mm (2″) kanthi ring ngunci ngisor C ing posisi b. Kanggo entuk setelan diferensial sing luwih cilik, reposisi cincin pengunci ngisor C ing b, 37.5 mm (1½"), (b225 mm (1″); b = 12.5 mm (½").
Danfoss AKS 38 Level Controller - Simbol PENTING
Pangaturan kudu ditindakake sadurunge AKS 38 dipasang ing sistem kulkas. Gunakake rong jempol kanggo repositioning dering ngunci. Aja nggunakake piranti apa wae.
Copot kothak ngalih AKS 38 (fig. 3, pos. 2).

  • Unfasten M4 x 8 (anjir. 3, pos. 3) pinol tailstock meneng karo tombol Allen.
  • Copot kothak switch kanthi alon-alon munggah.

Copot tutup ndhuwur omah AKS 38 (fig. 3, pos. 4).

  • Unfasten 4 x M12 x 35 baut stainless steel (fig. 3, pos. 5).
  • Copot tutup ndhuwur lengkap kalebu tabung meksa diinstal (anjir. 3, pos. 7).

Copot perakitan float lengkap (anjir.3, pos. 1 lan anjir. 4, pos. 1) saka omah AKS 38 (anjir. 3, pos. 6).

  • Reposition ring ngunci ngisor ing setelan diferensial dibutuhake.
  • Waca anjir. 8 lan anjir. 9.

Reassembly

  • Refit perakitan float bali menyang omah AKS 38 (fig. 3, pos. 6).
  • Pasang maneh tutup ndhuwur lengkap (anjir. 3, pos. 4) lan nyepetake 4 x M12 x 35 bolts (anjir. 3, pos. 5).
  • Maks. torsi ngencengi: 74 Nm (100 ft-lb).
  • Instal maneh kothak ngalih (anjir. 3, pos. 2) dening alon meksa mudhun liwat tabung meksa (anjir. 3, pos. 7).
  • Posisi kothak ngalih (anjir. 3, pos. 2) minangka dibutuhake lan kenceng M4 x 8 pinol tailstock meneng (anjir. 3, pos. 3) karo tombol Allen.

Instalasi listrik
Nggawe sambungan listrik kanggo DIN plug nggunakake kabel karo maksimum 4 intine lan kabel ing sesuai karo diagram wiring (fig. 8).

  1. umum
  2. Biasane Ditutup
  3. Biasane terminal Open Earth

Pangopènan

Danfoss AKS 38 Level Controller - Simbol PENTING
AKS 38 kudu dievakuasi sadurunge mbukak menyang udara.
Ngganti rakitan float internal (anjir. 3, pos.1)

  • Bukak baut stainless steel 4xM12x35 (gambar 3, pos. 5).
  • Copot tutup ndhuwur (anjir. 3, pos. 4) kalebu tabung meksa diinstal (anjir. 3, pos. 7) lan kothak ngalih (anjir. 3, pos. 2).
  • Copot perakitan float internal (anjir 3, pos. 1).
  • Instal perakitan float anyar.

Ngganti gasket flange (anjir. 2, pos. 15)

  • Unscrew 4 x M12x35 stainless steel bolts ing flange sisih (fig. 2, pos. 13).
  • Unscrew 4x M12x35 bolts stainless steel ing flange ngisor (fig. 2, pos. 13).
  • Copot loro gaskets (anjir. 2, pos. 14).
  • Pasang gasket anyar.
  • Pasang 4 x M12 × 35 baut stainless steel ing saben flange. Maks. torsi ngencengi: 74 Nm (100 ft-lb).

Ngganti gasket tutup ndhuwur (anjir. 3, pos. 8)

  • Copot baut stainless steel 4x M12xx35 (gambar 3, pos. 5).
  • Copot tutup ndhuwur (anjir. 3, pos. 4) kalebu tabung meksa diinstal (anjir. 3, pos. 7) lan kothak ngalih (anjir. 3, pos. 2).
  • Copot gasket (anjir. 3, pos. 8).
  • Pasang gasket anyar.
  • Cepet 4 x M12 × 35 baut stainless steel (fig. 3, pos. 5). Maks. torsi ngencengi: 74 Nm (100 ft-lb).

Ngganti gasket aluminium (anjir. 3, pos. 11)

  • Unscrew M4 x 8 pinol tailstock meneng (fig. 3, pos. 3) karo tombol Allen.
  • Copot kothak ngalih (anjir. 3, pos. 2) dening alon easing munggah.
  • Copot tabung tekanan (gambar 3, pos. 7) kanthi kunci pas 32 mm.
  • Copot gasket aluminium (anjir. 3, pos. 11).
  • Pasang gasket anyar.
  • Pasang maneh tabung tekanan.
  • Instal maneh kothak ngalih.

Ngganti switchbox (fig. 3, pos 2)

  • Copot DIN-plug (anjir. 6).
  • Unscrew M4 x 8 pinol tailstock meneng (fig. 3, pos. 3) karo tombol Allen.
  • Copot kothak ngalih (anjir. 3, pos. 2) dening alon easing munggah.
  • Pasang kothak ngalih anyar.

Ngganti O-ring ing tabung tekanan (fig. 3, pos. 9)

  • Unscrew M4 x 8 pinol tailstock meneng (fig. 3, pos. 3) karo tombol Allen.
  • Copot kothak ngalih (anjir. 3, pos. 2) dening alon easing munggah.
  • Copot O-ring.
  • Pasang O-ring anyar.
  • Instal maneh kothak ngalih.

Pranyatan saka conformity
Petunjuk Peralatan Tekanan 97/23/EC
Jeneng lan Alamat Produsen ing Komunitas Eropa
Danfoss Industrial Refrigeration A/S
Stormosevej 10
Kothak POS 60 DK-8361 Hasselager
Denmark
Deskripsi Pressure Equipment
Saklar Float Refrigerant
Tipe AKS 38

Nominal bolongan DN32 (11/4 in.)
Klasifikasi kanggo Cairan Grup I (kabeh refrigeran (beracun, ora beracun, gampang kobong lan ora kobong)) Kanggo rincian / watesan luwih lengkap - deleng Instruksi Instalasi
Kisaran suhu AKS 38 —50°C/+65°C (-58°F/+149°F)
Tekanan kerja maksimum sing diidini AKS 38 28 bar (406 psi) -50°C/+65°C
(-58°F/+149°F)

Conformity lan Assessment Prosedur Dituruti

kategori I
Modul A
Nominal bosen Aplikasi standar DN32 mm. (11/4 ing.)

Jeneng lan Alamat Badan Notifikasi sing nindakake Inspeksi
TÜV-Nord eV
Grosse Bahnstrasse 31 22525 Hamburg, Jerman
SIMBOL CE
(0045)
Jeneng lan Alamat Badan Notifikasi ngawasi Sistem Jaminan Kualitas Produsen
TÜV-Nord eV
Grosse Bahnstrasse 31
22525 Hamburg, Jerman
Referensi Standar Harmonisasi digunakake
EN 10028-3
EN 10213-3
EN 10222-4
LVD 73/23/EEC
Referensi Standar Teknis lan Spesifikasi liyane sing digunakake
DIN 3840
EN/IEC 60730-2-16
AD-Merkblätter
Wong sing Sah kanggo Produsen ing Komunitas Eropa
Jeneng: Morten Steen Hansen
Judul : Manajer Produksi
Tandha tangan: Danfoss AKS 38 Level Controller - Tandha
Tanggal: 10/01/2003

Logo DanfossRI5MA352 ©
Danfoss A/S (RC-CMS/MWA), 03 – 2004