ERC 213 Digital Controller for Refrigeration
Specifications
- Model: ERC 213
- Function: Digital controller for refrigeration and defrost with 3 relays
- Dimensions: 61.2mm x 83mm x 66mm
- Mounting: Rear mounting with lock and clips
- Electrical Connections: DI1, DI2, Sair, S5, DO1, DO2, DO3, GND
Product Usage Instructions
Installation
- Use the provided drilling template to mark the mounting points.
- Securely mount the ERC 213 digital controller using the rear mounting system with clips.
Dimensions (mm) and Mounting
Electrical Connections
The ERC 213 is a smart, multipurpose refrigeration controller with temperature and defrost management, available with 3 relays.
The controller has been designed to fulfil today’s requirements for commercial refrigeration applications.
Technical Highlights
- Ease of use: Four buttons, easy menu structure, pre-installed application solutions ensure superior usability.
- Simple installation:
High Effect 16 A relay enable direct connection of heavy loads without use of intermediate relay: up to 2 hp compressors depending on its power factor and motor efficiency (greater than 0.65 for 230 V and greater than 0.85 for 115 V).
A wide range of compatible types of sensors and screw connection terminals ensure highly flexible installation. - Unit protection: Special software features like compressor protection from fluctuation in the power supply or from high condensing temperature ensure the safe operation of the unit.
- Energy efficiency: Defrost on demand, day/night mode and smart evaporator fan management ensure energy efficiency.
User Interface
Key Function | |
![]() |
Press and hold at power up: FACTORY RESET (“FAC” is displayed) |
![]() |
Press for one second: BACK Press and hold: PULL-DOWN |
![]() |
Press for one second: TEMPERATURE SETPOINT/OK Press and hold: MENU |
![]() |
Press for one second: UP Press and hold: ON/OFF |
![]() |
Press for one second: DOWN Press and hold: DEFROST |
Quick Configuration at Power Up
- STEP 1: Power on
- STEP 2: Select the quick configuration menu
Within 30 seconds of power on, press “<” BACK for 3 seconds.
The main switch “r12” is automatically set to OFF. - STEP 3: Select pre-installed application “o61”
The display automatically shows the application selection parameter “o61”. Press SET to select the pre-installed application. The display shows the default value (eg. “AP0” flashing). Choose the application type by pressing UP/DOWN and press SET to confirm. The controller presets parameter values according to the selected application and does not hide relevant parameters. Tip: you can easily move from AP0 to AP6, and thus select the simplified list of parameters, by pressing the UP key (circular list).
- STEP 4: Select sensor type “o06”
The display automatically shows sensor selection parameter “o06”. Press SET to select the sensor type. The display shows the default value (eg. “n10” flashing). Choose sensor type by pressing UP/DOWN (n5=NTC 5 K, n10=NTC 10 K, Ptc=PTC, Pt1=Pt1000) and press SET to confirm.
NOTE: All sensors must be the same type.
Quick Configuration via “cFg” Menu
- Press SET for three seconds to access the parameters groups.
- Select “CFg” menu and press SET to enter. The first menu “r12” (main switch) is displayed.
- Switch OFF main switch (r12=0) for changing the pre-installed application.
- Press UP/DOWN to scroll through the parameter list.
- Configure the “o61” parameter to select a pre-installed application
- Press SET to access the “o61” parameter.
- Press UP/DOWN to select an application (AP0= no application selected).
- Press SET to confirm, “o61” is displayed.
- Continue to set the next parameters (“o06” sensor type) in the “cFg” menu.
Basic operation
Adjust the setpoint temperature
Initiate a manual defrost
Initiate a pull down
View an active alarm
Unlock keyboard
- After 5 minutes of no activity, the keypad is locked (if P76=yes).
- When the keypad is locked any button press shows “LoC” in the display.
- Press UP and DOWN buttons simultaneously for 3 seconds to unlock the keyboard. “unl” is displayed for 3 seconds.
Technical Data
Predefined Application Setup
Parameter List
Parameter Name – ERC 213 | Code | Min | Max | Unit | App. 0 (Def.) | App. 1 | App. 2 | App. 3 | App. 4 | App. 5 | App. 6 |
Configuration | cFg | ||||||||||
Main switch -1=service, 0=OFF, 1=ON |
r12 | -1 | 1 | 1 | 1 | 1 | 1 | 1 | 1 | 1 | |
Predefined applications AP0, AP1, AP2, AP3, AP4, AP5, AP6 |
o61 | AP0 | AP6 | AP0 | AP1 | AP2 | AP3 | AP4 | AP5 | AP6 | |
Sensor type selection n5=NTC 5 K, n10=NTC 10 K, Ptc=PTC, Pt1=Pt1000 |
o06 |
n5 |
Pt1 |
n10 |
n10 |
n10 |
n10 |
n10 |
n10 |
n10 |
|
Reference/thermostat | r– | ||||||||||
Temperature setpoint | r00 | -100.0 | 200.0 | C/F | 2.0 | 4.0 | 2.0 | -24.0 | 2.0 | -24.0 | 2.0 |
Differential | r01 | 0.1 | 20.0 | K | 2.0 | 2.0 | 2.0 | 2.0 | 2.0 | 2.0 | 2.0 |
Min set point limitation | r02 | -100.0 | 200.0 | C/F | -35.0 | 2.0 | 0.0 | -26.0 | 0.0 | -26.0 | -35.0 |
Max set point limitation | r03 | -100.0 | 200.0 | C/F | 50.0 | 6.0 | 4.0 | -20.0 | 4.0 | -20.0 | 50.0 |
Display offset (correction value in display temperature) |
r04 | -10.0 | 10.0 | K | 0.0 | 0.0 | 0.0 | 0.0 | 0.0 | 0.0 | 0.0 |
Display Unit (°C/°F) | r05 | -C | -F | -C | -C | -C | -C | -C | -C | -C | |
Calibration of Sair (offset for air temperature calibration) |
r09 | -20.0 | 20.0 | K | 0.0 | 0.0 | 0.0 | 0.0 | 0.0 | 0.0 | – |
Main switch -1=service, 0=OFF, 1=ON |
r12 | -1 | 1 | 1 | 1 | 1 | 1 | 1 | 1 | – | |
Night set back (offset temperature during night mode) | r13 | -50.0 | 50.0 | K | 0.0 | 0.0 | 0.0 | 0.0 | 0.0 | 0.0 | 0.0 |
Thermostat reference displacement (offset temperature) | r40 | -50.0 | 50.0 | K | 0.0 | 0.0 | 0.0 | 0.0 | 0.0 | 0.0 | – |
Pull-down duration | r96 | 0 | 960 | min | 0 | 0 | 0 | 0 | 0 | 0 | – |
Pull-down limit temperature | r97 | -100.0 | 200.0 | C/F | 0.0 | 0.0 | 0.0 | 0.0 | 0.0 | 0.0 | – |
Note: hidden parameters are greyed out |
Parameter Name – ERC 213 | Code | Min | Max | Unit | App. 0 (Def.) | App. 1 | App. 2 | App. 3 | App. 4 | App. 5 | App. 6 |
Alarm | A– | ||||||||||
Delay for temperature alarm during normal conditions | A03 | 0 | 240 | min | 30 | 45 | 30 | 30 | 30 | 30 | 30 |
Delay for temperature alarm during pull-down/start-up/defrost | A12 | 0 | 240 | min | 60 | 90 | 60 | 60 | 60 | 60 | 60 |
High temperature alarm limit(Cabinet/Room) | A13 | -100.0 | 200.0 | C/F | 8.0 | 10.0 | 8.0 | -15.0 | 8.0 | -15.0 | 8.0 |
Low temperature alarm limit | A14 | -100.0 | 200.0 | C/F | -30.0 | 0.0 | -2.0 | -30.0 | -2.0 | -30.0 | -30.0 |
DI1 delay(time delay for selected DI1 function) | A27 | 0 | 240 | min | 30 | 30 | 30 | 30 | 30 | 30 | 30 |
DI2 delay(time delay for selected DI2 function) | A28 | 0 | 240 | min | 30 | 30 | 30 | 30 | 30 | 30 | 30 |
Condenser high alarm limit | A37 | 0 | 200 | C/F | 80 | 80 | 80 | 80 | 80 | 80 | – |
Condenser high block limit | A54 | 0 | 200 | C/F | 85 | 85 | 85 | 85 | 85 | 85 | – |
Voltage protection enable | A72 | no | yES | no | no | no | no | no | no | no | |
Minimum cut-in voltage | A73 | 0 | 270 | V | 0 | 0 | 0 | 0 | 0 | 0 | 0 |
Minimum cut-out voltage | A74 | 0 | 270 | V | 0 | 0 | 0 | 0 | 0 | 0 | 0 |
Maximum voltage | A75 | 0 | 270 | V | 270 | 270 | 270 | 270 | 270 | 270 | 270 |
Defrost | d– | ||||||||||
Defrost method no=no defrost, nAt=natural, EL=electrical, gAS=hot gas | d01 | no | gAS | EL | nAt | EL | EL | EL | EL | EL | |
Defrost stop temperature | d02 | 0.0 | 50.0 | C/F | 6.0 | – | – | – | 6.0 | 6.0 | 6.0 |
Defrost interval | d03 | 0 | 240 | hours | 8 | 6 | 8 | 12 | 8 | 12 | 8 |
Max defrost time | d04 | 0 | 480 | min | 30 | 45 | 15 | 15 | 30 | 30 | 30 |
Defrost delay at power up(or DI signal) | d05 | 0 | 240.0 | min | 0 | 0 | 0 | 0 | 0 | 0 | – |
Drip delay | d06 | 0 | 60 | min | 0 | 0 | 0 | 0 | 0 | 0 | 5 |
Fan delay after defrost | d07 | 0 | 60 | min | 0 | 0 | 0 | 0 | 0 | 0 | 5 |
Fan start temperature after defrost | d08 | -50.0 | 0.0 | C/F | -5.0 | – | – | – | -5.0 | -5.0 | – |
Fan during defrost | d09 | oFF | on | on | on | on | on | on | on | on | |
Note: hidden parameters are greyed out |
Parameter Name – ERC 213 | Code | Min | Max | Unit | App. 0 (Def.) | App. 1 | App. 2 | App. 3 | App. 4 | App. 5 | App. 6 |
Defrost stop sensor configuration non=time, Air=Sair (air temperature), dEF=S5 (defrost sensor) | d10 | non | dEF | non | non | non | non | dEF | dEF | non | |
Compressor accumulated runtime to start defrost, 0=OFF | d18 | 0 | 96 | hours | 0 | 0 | 0 | 0 | 0 | 0 | – |
Defrost on demand20.0=OFF | d19 | 0.0 | 20.0 | K | 20.0 | – | – | – | 20.0 | 20.0 | – |
Defrost delay after pull-down0=OFF | d30 | 0 | 960 | min | 0 | 0 | 0 | 0 | 0 | 0 | – |
Fan control | F– | ||||||||||
Fan at compressor cutout FFc=fan follow compressor, FAo=fan always ON,FPL= fan pulsating | F01 | FFc | FPL | FAo | FAo | FAo | FAo | FAo | FAo | FAo | |
Fan stop evaporator temperature50.0=OFF | F04 | -50.0 | 50.0 | C/F | 50.0 | – | – | – | 50.0 | 50.0 | – |
Fan ON cycle | F07 | 0 | 15 | min | 2 | 2 | 2 | 2 | 2 | 2 | 2 |
Fan OFF cycle | F08 | 0 | 15.0 | min | 2 | 2 | 2 | 2 | 2 | 2 | 2 |
Compressor | c– | ||||||||||
Compressor minimum ON time | C01 | 0 | 30 | min | 0 | 0 | 0 | 0 | 0 | 0 | 0 |
Compressor minimum OFF time | C02 | 0 | 30 | min | 2 | 2 | 2 | 2 | 2 | 2 | 2 |
Compressor OFF delay at door open | C04 | 0 | 15 | min | 0 | 0 | 0 | 0 | 0 | 0 | 1 |
Zero crossing selection | C70 | no | yES | yES | yES | yES | yES | yES | yES | yES | |
Note: hidden parameters are greyed out |
Parameter Name – ERC 213 | Code | Min | Max | Unit | App. 0 (Def.) | App. 1 | App. 2 | App. 3 | App. 4 | App. 5 | App. 6 |
Others | o– | ||||||||||
Delay of output sat startup | o01 | 0 | 600 | min | 5 | 5 | 5 | 5 | 5 | 5 | 5 |
DI1 configuration oFF=not used, Sdc=status display output, doo=door alarm with resumption, doA=door alarm without resumption, SCH=main switch, nig=day/ night mode, rFd=reference displacement, EAL=external alarm, dEF=defrost, Pud=pull-down, Sc=condenser sensor | o02 | oFF | Sc | oFF | oFF | oFF | oFF | oFF | oFF | oFF | |
Serial address | o03 | 0 | 247 | 0 | 0 | 0 | 0 | 0 | 0 | – | |
Password | o05 | no | 999 | no | no | no | no | no | no | no | |
Sensor type selection n5=NTC 5 K, n10=NTC 10 K, Ptc=PTC, Pt1=Pt1000 | o06 | n5 | Pt1 | n10 | n10 | n10 | n10 | n10 | n10 | – | |
Display resolution 0.1=steps of 0.1 °C 0.5=steps of 0.5 °C, 1.0=steps of 1.0 °C | o15 | 0.1 | 1.0 | 0.1 | 0.1 | 0.1 | 0.1 | 0.1 | 0.1 | 0.1 | |
Relay 1 counter(1 count=100 cycles of operation) | o23 | 0 | 999 | 0 | 0 | 0 | 0 | 0 | 0 | – | |
Relay 2 counter(1 count=100 cycles of operation) | o24 | 0 | 999 | 0 | 0 | 0 | 0 | 0 | 0 | – | |
Relay 3 counter(1 count=100 cycles of operation) | o25 | 0 | 999 | 0 | 0 | 0 | 0 | 0 | 0 | – | |
DI2 configuration oFF=not used, Sdc=status display output, doo=door alarm with resumption, doA=door alarm without resumption, SCH=main switch, nig=day/night mode, rFd=reference displacement, EAL=external alarm, dEF=defrost, Pud=pull-down | o37 | oFF | Pud | oFF | oFF | oFF | oFF | oFF | oFF | oFF | |
Predefined applications | o61 | AP0 | AP6 | AP0 | AP1 | AP2 | AP3 | AP4 | AP5 | – | |
Note: hidden parameters are greyed out |
Parameter Name – ERC 213 | Code | Min | Max | Unit | App. 0 (Def.) | App. 1 | App. 2 | App. 3 | App. 4 | App. 5 | App. 6 |
Save settings as factory WARNING: the earlier factory settings are over written |
o67 | no | yES | no | no | no | no | no | no | – | |
DO2 config dEF=defrost, ALA=alarm | o71 | dEF | ALA | dEF | ALA | dEF | dEF | dEF | dEF | dEF | |
Display at defrost Air=actual air temperature, FrE=freezed temperature, -d-=”-d-” is displayed | o91 | Air | -d- | -d- | -d- | -d- | -d- | -d- | -d- | -d- | |
Polarity | P– | ||||||||||
DI1 input polarity nc=normally closed, no=normally open | P73 | nc | no | no | no | no | no | no | no | no | |
DI2 input polarity nc=normally closed, no=normally open | P74 | nc | no | no | no | no | no | no | no | no | |
Invert alarm relay0=normal, 1=invert relay action | P75 | 0 | 1 | 0 | 0 | – | – | – | – | – | |
Keyboard lock enable | P76 | no | yES | no | no | no | no | no | no | – | |
Readouts | u– | ||||||||||
Controller StatusS0=cooling ON/Heating ON,S2=wait for compressor ON time to elapse, S3=wait for compressor OFF time to elapse- restart time, S4=drip OFF delay after defrost, S10=cooling stop S11=cooling stopped by thermostat/heating OFF, S14=defrosting state, S15=fan delay state after defrost, S17=door open (DI input), S20=emergency cooling, S25=manual control of outputs, S30=continous cycle/Pull-down,S32=delay of outputs at power up | u00 | S0 | S32 | — | |||||||
Air temperature (Sair) | u01 | -100.0 | 200.0 | C/F | — | ||||||
Read the present regulation reference | u02 | -100.0 | 200.0 | C/F | — | ||||||
Defrost temperature (S5) | u09 | -100.0 | 200.0 | C/F | — | – | – | – | |||
Note: hidden parameters are greyed out |
Parameter Name – ERC 213 | Code | Min | Max | Unit | App. 0 (Def.) | App. 1 | App. 2 | App. 3 | App. 4 | App. 5 | App. 6 |
DI1 input | u10 | oFF | on | — | |||||||
Status of night operation | u13 | oFF | on | — | |||||||
DI2 input | u37 | oFF | on | — | |||||||
Condenser temperature (Sc) | U09 | -100.0 | 200.0 | C/F | — | ||||||
Compressor relay status | u58 | oFF | on | — | |||||||
Fan relay status | u59 | oFF | on | — | |||||||
Defrost relay status | u60 | oFF | on | — | |||||||
Light relay status | u63 | oFF | on | — | |||||||
Firmware version readout | u80 | 000 | 999 | — | |||||||
Alarm status | |||||||||||
Sair air temperature sensor error | E29 | ||||||||||
S5 defrost sensor error | E27 | ||||||||||
Sc condenser sensor error | E30 | ||||||||||
High temperature alarm | A01 | ||||||||||
Low temperature alarm | A02 | ||||||||||
High voltage alarm | A99 | ||||||||||
Low voltage alarm | AA1 | ||||||||||
Condenser alarm | A61 | ||||||||||
Door alarm | A04 | ||||||||||
Standby alarm | A45 | ||||||||||
DI external alarm | A15 | ||||||||||
Note: hidden parameters are greyed out |
Safety Standards
Check if the supply voltage is correct before connecting the instrument.
Do not expose to water or moisture: use the controller only within the operating limits avoiding sudden temperature changes with high atmospheric humidity to prevent the formation of condensation.
Disposal of the Product
The appliance (or the product) must be disposed of in accordance with the local waste disposal legislation.
EU Design Registration
002566703-0001
Danfoss can accept no responsibility for possible errors in catalogues, brochures and other printed material. Danfoss reserves the right to alter its products without notice. This also applies to products already on order provided that such alterations can be made without subsequent changes being necessary in specifications already agreed. All trademarks in this material are property of the property of the respective companies. Danfoss and Danfoss logotype are trademarks of Danfoss A/S. All rights reserved.
KoolCode App
Download the KoolCode App on your app store. More and more from your ERC controller!
Scan this code to find out more about the ERC 213 parameter
Download ERC 21X series www.danfoss.com/erc
© Danfoss | DCS (az) | 2016.04
Frequently Asked Questions
- Q: How do I reset the controller to factory settings?
A: Press and hold the specified button during power-up to perform a factory reset. Follow on-screen prompts for confirmation. - Q: What should I do if I encounter an active alarm icon on the display?
A: Check the user manual for information on troubleshooting alarms. You may need to take specific actions based on the alarm displayed.