ERC-LOGO

ERC 213 Digital Controller for Refrigeration

ERC-213-Digital-Controller-for-Refrigeration-PRODUCT-IMAGE

Specifications

  • Model: ERC 213
  • Function: Digital controller for refrigeration and defrost with 3 relays
  • Dimensions: 61.2mm x 83mm x 66mm
  • Mounting: Rear mounting with lock and clips
  • Electrical Connections: DI1, DI2, Sair, S5, DO1, DO2, DO3, GND

Product Usage Instructions

Installation

  1. Use the provided drilling template to mark the mounting points.
  2. Securely mount the ERC 213 digital controller using the rear mounting system with clips.

Dimensions (mm) and Mounting

ERC-213-Digital-Controller-for-Refrigeration- (1)

ERC-213-Digital-Controller-for-Refrigeration- (2)

Electrical Connections

ERC-213-Digital-Controller-for-Refrigeration- (3)

The ERC 213 is a smart, multipurpose refrigeration controller with temperature and defrost management, available with 3 relays.
The controller has been designed to fulfil today’s requirements for commercial refrigeration applications.

Technical Highlights

  • Ease of use: Four buttons, easy menu structure, pre-installed application solutions ensure superior usability.
  • Simple installation:
    High Effect 16 A relay enable direct connection of heavy loads without use of intermediate relay: up to 2 hp compressors depending on its power factor and motor efficiency (greater than 0.65 for 230 V and greater than 0.85 for 115 V).
    A wide range of compatible types of sensors and screw connection terminals ensure highly flexible installation.
  • Unit protection: Special software features like compressor protection from fluctuation in the power supply or from high condensing temperature ensure the safe operation of the unit.
  • Energy efficiency: Defrost on demand, day/night mode and smart evaporator fan management ensure energy efficiency.

User Interface

Key Function
ERC-213-Digital-Controller-for-Refrigeration- (4)  Press and hold at power up: FACTORY RESET
(“FAC” is displayed)
ERC-213-Digital-Controller-for-Refrigeration- (5) Press for one second: BACK
Press and hold: PULL-DOWN
ERC-213-Digital-Controller-for-Refrigeration- (6) Press for one second: TEMPERATURE SETPOINT/OK
Press and hold: MENU
ERC-213-Digital-Controller-for-Refrigeration- (7) Press for one second: UP
Press and hold: ON/OFF
ERC-213-Digital-Controller-for-Refrigeration- (8)  Press for one second: DOWN
Press and hold: DEFROST

ERC-213-Digital-Controller-for-Refrigeration- (9)

Quick Configuration at Power Up

  • STEP 1: Power on
  • STEP 2: Select the quick configuration menu
    Within 30 seconds of power on, press “<” BACK for 3 seconds.
    The main switch “r12” is automatically set to OFF.
  • STEP 3: Select pre-installed application “o61”
    The display automatically shows the application selection parameter “o61”. Press SET to select the pre-installed application. The display shows the default value (eg. “AP0” flashing). Choose the application type by pressing UP/DOWN and press SET to confirm. The controller presets parameter values according to the selected application and does not hide relevant parameters. Tip: you can easily move from AP0 to AP6, and thus select the simplified list of parameters, by pressing the UP key (circular list).

ERC-213-Digital-Controller-for-Refrigeration- (10)

  • STEP 4: Select sensor type “o06”
    The display automatically shows sensor selection parameter “o06”. Press SET to select the sensor type. The display shows the default value (eg. “n10” flashing). Choose sensor type by pressing UP/DOWN (n5=NTC 5 K, n10=NTC 10 K, Ptc=PTC, Pt1=Pt1000) and press SET to confirm.
    NOTE: All sensors must be the same type.

Menu structure

ERC-213-Digital-Controller-for-Refrigeration- (11)

Quick Configuration via “cFg” Menu

  • Press SET for three seconds to access the parameters groups.
  • Select “CFg” menu and press SET to enter. The first menu “r12” (main switch) is displayed.
  • Switch OFF main switch (r12=0) for changing the pre-installed application.
  • Press UP/DOWN to scroll through the parameter list.
  • Configure the “o61” parameter to select a pre-installed application
    • Press SET to access the “o61” parameter.
    • Press UP/DOWN to select an application (AP0= no application selected).
    • Press SET to confirm, “o61” is displayed.
  • Continue to set the next parameters (“o06” sensor type) in the “cFg” menu.

Basic operation

Adjust the setpoint temperature

ERC-213-Digital-Controller-for-Refrigeration- (12)

Initiate a manual defrost

ERC-213-Digital-Controller-for-Refrigeration- (13)

Initiate a pull down

ERC-213-Digital-Controller-for-Refrigeration- (14)

View an active alarm

ERC-213-Digital-Controller-for-Refrigeration- (15)

Unlock keyboard

ERC-213-Digital-Controller-for-Refrigeration- (16)

  • After 5 minutes of no activity, the keypad is locked (if P76=yes).
  • When the keypad is locked any button press shows “LoC” in the display.
  • Press UP and DOWN buttons simultaneously for 3 seconds to unlock the keyboard. “unl” is displayed for 3 seconds.

Technical Data

ERC-213-Digital-Controller-for-Refrigeration- (17)

ERC-213-Digital-Controller-for-Refrigeration- (18)ERC-213-Digital-Controller-for-Refrigeration- (19)

Predefined Application Setup

ERC-213-Digital-Controller-for-Refrigeration- (20)

ERC-213-Digital-Controller-for-Refrigeration- (21)

Parameter List

Parameter Name – ERC 213 Code Min Max Unit App. 0 (Def.) App. 1 App. 2 App. 3 App. 4 App. 5 App. 6
Configuration cFg
Main switch
-1=service, 0=OFF, 1=ON
r12 -1 1 1 1 1 1 1 1 1
Predefined applications
AP0, AP1, AP2, AP3, AP4, AP5, AP6
o61 AP0 AP6 AP0 AP1 AP2 AP3 AP4 AP5 AP6
Sensor type selection n5=NTC 5 K, n10=NTC 10 K, Ptc=PTC, Pt1=Pt1000  

o06

 

n5

 

Pt1

 

n10

 

n10

 

n10

 

n10

 

n10

 

n10

 

n10

Reference/thermostat r–
Temperature setpoint r00 -100.0 200.0 C/F 2.0 4.0 2.0 -24.0 2.0 -24.0 2.0
Differential r01 0.1 20.0 K 2.0 2.0 2.0 2.0 2.0 2.0 2.0
Min set point limitation r02 -100.0 200.0 C/F -35.0 2.0 0.0 -26.0 0.0 -26.0 -35.0
Max set point limitation r03 -100.0 200.0 C/F 50.0 6.0 4.0 -20.0 4.0 -20.0 50.0
Display offset
(correction value in display temperature)
r04 -10.0 10.0 K 0.0 0.0 0.0 0.0 0.0 0.0 0.0
Display Unit (°C/°F) r05 -C -F -C -C -C -C -C -C -C
Calibration of Sair
(offset for air temperature calibration)
r09 -20.0 20.0 K 0.0 0.0 0.0 0.0 0.0 0.0
Main switch
-1=service, 0=OFF, 1=ON
r12 -1 1 1 1 1 1 1 1
Night set back (offset temperature during night mode) r13 -50.0 50.0 K 0.0 0.0 0.0 0.0 0.0 0.0 0.0
Thermostat reference displacement (offset temperature) r40 -50.0 50.0 K 0.0 0.0 0.0 0.0 0.0 0.0
Pull-down duration r96 0 960 min 0 0 0 0 0 0
Pull-down limit temperature r97 -100.0 200.0 C/F 0.0 0.0 0.0 0.0 0.0 0.0
Note: hidden parameters are greyed out
Parameter Name – ERC 213 Code Min Max Unit App. 0 (Def.) App. 1 App. 2 App. 3 App. 4 App. 5 App. 6
Alarm A–
Delay for temperature alarm during normal conditions A03 0 240 min 30 45 30 30 30 30 30
Delay for temperature alarm during pull-down/start-up/defrost A12 0 240 min 60 90 60 60 60 60 60
High temperature alarm limit(Cabinet/Room) A13 -100.0 200.0 C/F 8.0 10.0 8.0 -15.0 8.0 -15.0 8.0
Low temperature alarm limit A14 -100.0 200.0 C/F -30.0 0.0 -2.0 -30.0 -2.0 -30.0 -30.0
DI1 delay(time delay for selected DI1 function) A27 0 240 min 30 30 30 30 30 30 30
DI2 delay(time delay for selected DI2 function) A28 0 240 min 30 30 30 30 30 30 30
Condenser high alarm limit A37 0 200 C/F 80 80 80 80 80 80
Condenser high block limit A54 0 200 C/F 85 85 85 85 85 85
Voltage protection enable A72 no yES no no no no no no no
Minimum cut-in voltage A73 0 270 V 0 0 0 0 0 0 0
Minimum cut-out voltage A74 0 270 V 0 0 0 0 0 0 0
Maximum voltage A75 0 270 V 270 270 270 270 270 270 270
Defrost d–
Defrost method no=no defrost, nAt=natural, EL=electrical, gAS=hot gas  d01  no  gAS  EL  nAt  EL  EL  EL  EL  EL
Defrost stop temperature d02 0.0 50.0 C/F 6.0 6.0 6.0 6.0
Defrost interval d03 0 240 hours 8 6 8 12 8 12 8
Max defrost time d04 0 480 min 30 45 15 15 30 30 30
Defrost delay at power up(or DI signal) d05 0 240.0 min 0 0 0 0 0 0
Drip delay d06 0 60 min 0 0 0 0 0 0 5
Fan delay after defrost d07 0 60 min 0 0 0 0 0 0 5
Fan start temperature after defrost d08 -50.0 0.0 C/F -5.0 -5.0 -5.0
Fan during defrost d09 oFF on on on on on on on on
Note: hidden parameters are greyed out
Parameter Name – ERC 213 Code Min Max Unit App. 0 (Def.) App. 1 App. 2 App. 3 App. 4 App. 5 App. 6
Defrost stop sensor configuration non=time, Air=Sair (air temperature), dEF=S5 (defrost sensor)   d10   non   dEF   non   non   non   non   dEF   dEF   non
Compressor accumulated runtime to start defrost, 0=OFF  d18  0  96  hours  0  0  0  0  0  0  
Defrost on demand20.0=OFF d19 0.0 20.0 K 20.0 20.0 20.0
Defrost delay after pull-down0=OFF d30 0 960 min 0 0 0 0 0 0
Fan control F–
Fan at compressor cutout FFc=fan follow compressor, FAo=fan always ON,FPL= fan pulsating  F01  FFc  FPL  FAo  FAo  FAo  FAo  FAo  FAo  FAo
Fan stop evaporator temperature50.0=OFF F04 -50.0 50.0 C/F 50.0 50.0 50.0
Fan ON cycle F07 0 15 min 2 2 2 2 2 2 2
Fan OFF cycle F08 0 15.0 min 2 2 2 2 2 2 2
Compressor c–
Compressor minimum ON time C01 0 30 min 0 0 0 0 0 0 0
Compressor minimum OFF time C02 0 30 min 2 2 2 2 2 2 2
Compressor OFF delay at door open C04 0 15 min 0 0 0 0 0 0 1
Zero crossing selection C70 no yES yES yES yES yES yES yES yES
Note: hidden parameters are greyed out
Parameter Name – ERC 213 Code Min Max Unit App. 0 (Def.) App. 1 App. 2 App. 3 App. 4 App. 5 App. 6
Others o–
Delay of output sat startup o01 0 600 min 5 5 5 5 5 5 5
DI1 configuration oFF=not used, Sdc=status display output, doo=door alarm with resumption, doA=door alarm without resumption, SCH=main switch, nig=day/ night mode, rFd=reference displacement, EAL=external alarm, dEF=defrost, Pud=pull-down, Sc=condenser sensor    o02    oFF    Sc    oFF    oFF    oFF    oFF    oFF    oFF    oFF
Serial address o03 0 247 0 0 0 0 0 0
Password o05 no 999 no no no no no no no
Sensor type selection n5=NTC 5 K, n10=NTC 10 K, Ptc=PTC, Pt1=Pt1000  o06  n5  Pt1  n10  n10  n10  n10  n10  n10  
Display resolution 0.1=steps of 0.1 °C 0.5=steps of 0.5 °C, 1.0=steps of 1.0 °C  o15  0.1  1.0  0.1  0.1  0.1  0.1  0.1  0.1  0.1
Relay 1 counter(1 count=100 cycles of operation) o23 0 999 0 0 0 0 0 0
Relay 2 counter(1 count=100 cycles of operation) o24 0 999 0 0 0 0 0 0
Relay 3 counter(1 count=100 cycles of operation) o25 0 999 0 0 0 0 0 0
DI2 configuration oFF=not used, Sdc=status display output, doo=door alarm with resumption, doA=door alarm without resumption, SCH=main switch, nig=day/night mode, rFd=reference displacement, EAL=external alarm, dEF=defrost, Pud=pull-down    o37    oFF    Pud    oFF    oFF    oFF    oFF    oFF    oFF    oFF
Predefined applications o61 AP0 AP6 AP0 AP1 AP2 AP3 AP4 AP5
Note: hidden parameters are greyed out
Parameter Name – ERC 213 Code Min Max Unit App. 0 (Def.) App. 1 App. 2 App. 3 App. 4 App. 5 App. 6
Save settings as factory
WARNING: the earlier factory settings are over written
 o67  no  yES  no  no  no  no  no  no  
DO2 config dEF=defrost, ALA=alarm o71 dEF ALA dEF ALA dEF dEF dEF dEF dEF
Display at defrost Air=actual air temperature, FrE=freezed temperature, -d-=”-d-” is displayed  o91  Air  -d-  -d-  -d-  -d-  -d-  -d-  -d-  -d-
Polarity P–
DI1 input polarity nc=normally closed, no=normally open  P73  nc  no  no  no  no  no  no  no  no
DI2 input polarity nc=normally closed, no=normally open  P74  nc  no  no  no  no  no  no  no  no
Invert alarm relay0=normal, 1=invert relay action P75 0 1 0 0
Keyboard lock enable P76 no yES no no no no no no
Readouts u–
Controller StatusS0=cooling ON/Heating ON,S2=wait for compressor ON time to elapse, S3=wait for compressor OFF time to elapse- restart time, S4=drip OFF delay after defrost, S10=cooling stop S11=cooling stopped by thermostat/heating OFF, S14=defrosting state, S15=fan delay state after defrost, S17=door open (DI input), S20=emergency cooling, S25=manual control of outputs, S30=continous cycle/Pull-down,S32=delay of outputs at power up      u00      S0      S32      
Air temperature (Sair) u01 -100.0 200.0 C/F
Read the present regulation reference u02 -100.0 200.0 C/F
Defrost temperature (S5) u09 -100.0 200.0 C/F
Note: hidden parameters are greyed out
Parameter Name – ERC 213 Code Min Max Unit App. 0 (Def.) App. 1 App. 2 App. 3 App. 4 App. 5 App. 6
DI1 input u10 oFF on
Status of night operation u13 oFF on
DI2 input u37 oFF on
Condenser temperature (Sc) U09 -100.0 200.0 C/F
Compressor relay status u58 oFF on
Fan relay status u59 oFF on
Defrost relay status u60 oFF on
Light relay status u63 oFF on
Firmware version readout u80 000 999
Alarm status
Sair air temperature sensor error E29
S5 defrost sensor error E27
Sc condenser sensor error E30
High temperature alarm A01
Low temperature alarm A02
High voltage alarm A99
Low voltage alarm AA1
Condenser alarm A61
Door alarm A04
Standby alarm A45
DI external alarm A15
Note: hidden parameters are greyed out

Safety Standards
Check if the supply voltage is correct before connecting the instrument.
Do not expose to water or moisture: use the controller only within the operating limits avoiding sudden temperature changes with high atmospheric humidity to prevent the formation of condensation.

Disposal of the Product
The appliance (or the product) must be disposed of in accordance with the local waste disposal legislation.

EU Design Registration
002566703-0001
Danfoss can accept no responsibility for possible errors in catalogues, brochures and other printed material. Danfoss reserves the right to alter its products without notice. This also applies to products already on order provided that such alterations can be made without subsequent changes being necessary in specifications already agreed. All trademarks in this material are property of the property of the respective companies. Danfoss and Danfoss logotype are trademarks of Danfoss A/S. All rights reserved.

KoolCode App
Download the KoolCode App on your app store. More and more from your ERC controller!

ERC-213-Digital-Controller-for-Refrigeration- 22

Scan this code to find out more about the ERC 213 parameter

ERC-213-Digital-Controller-for-Refrigeration- 23

Download ERC 21X series www.danfoss.com/erc
© Danfoss | DCS (az) | 2016.04

Frequently Asked Questions

  • Q: How do I reset the controller to factory settings?
    A: Press and hold the specified button during power-up to perform a factory reset. Follow on-screen prompts for confirmation.
  • Q: What should I do if I encounter an active alarm icon on the display?
    A: Check the user manual for information on troubleshooting alarms. You may need to take specific actions based on the alarm displayed.