Installation Guide for ERC models including: ERC 213, ERC 213 Digital Controller for Refrigeration, Digital Controller for Refrigeration, Controller for Refrigeration, Refrigeration
File Info : application/pdf, 152 Pages, 2.28MB
DocumentDocumentInstallation Guide ERC 213 Digital controller for refrigeration and defrost, 3 relays. Dimensions (mm) and Mounting 61.2 83 66 Rear mounting (lock with clips) 36 28 71 29 Drilling template Mounting Dismounting | 2 Instruction sheet | ERC 213 DKRCE.PI.RL0.G5.ML/520H11075 Electrical Connections DI1 DI2 Sair S5 DO1 DO1 DO2 DO3 Sc DO2 DO3 12 3L 4N 5 6 7 Programming key EKA 183B GND TX RX +5V 15 16 17 18 GND GND 8 9 10 11 12 13 14 ~ ~ ~~ Sair Power supply (according to the product code number) DKRCE.PI.RL0.G5.ML/520H11075 Instruction sheet | ERC 213 S5 Sc/DI1 DI2 | 3 ENGLISH The ERC 213 is a smart, multipurpose refrigeration controller with temperature and defrost management, available with 3 relays. The controller has been designed to fulfil today's requirements for commercial refrigeration applications. 1 - Technical Highlights y Ease of use: Four buttons, easy menu structure, pre-installed application solutions ensure superior usability. y Simple installation: High Effect 16 A relay enable direct connection of heavy loads without use of intermediate relay: up to 2 hp compressors depending on its power factor and motor efficiency (greater than 0.65 for 230 V and greater than 0.85 for 115 V). A wide range of compatible types of sensors and screw connection terminals ensure highly flexible installation. y Unit protection: Special software features like compressor protection from fluctuation in the power supply or from high condensing temperature ensure the safe operation of the unit. y Energy efficiency: Defrost on demand, day/night mode and smart evaporator fan management ensure energy efficiency. | 4 Instruction sheet | ERC 213 DKRCE.PI.RL0.G5.ML/520H11075 ENGLISH 2 - User Interface Key Function Press and hold at power up: FACTORY RESET ("FAC" is displayed) Press for one second: BACK Press and hold: PULL-DOWN Press for one second: TEMPERATURE SETPOINT/OK Press and hold: MENU Press for one second: UP Press and hold: ON/OFF Press for one second: DOWN Press and hold: DEFROST Display Icons Night mode (Energy saving) Compressor running Flashes in pull-down mode Fan running Active alarm Defrost Unit (°C or °F) DKRCE.PI.RL0.G5.ML/520H11075 Instruction sheet | ERC 213 | 5 ENGLISH 3 - Quick Configuration at Power Up y STEP 1: Power on y STEP 2: Select the quick configuration menu Within 30 seconds of power on, press "<" BACK for 3 seconds. The main switch "r12" is automatically set to OFF. y STEP 3: Select pre-installed application "o61" The display automatically shows the application selection parameter "o61". Press SET to select the pre-installed application. The display shows the default value (eg. "AP0" flashing). Choose the application type by pressing UP/DOWN and press SET to confirm. The controller presets parameter values according to the selected application and does not hide relevant parameters. Tip: you can easily move from AP0 to AP6, and thus select the simplified list of parameters, by pressing the UP key (circular list). App App 0 App 1 App 2 App 3 App 4 App 5 App 6 Description None (no preset application) Medium temperature ventilated refrigeration units (2 6 °C), with timed natural defrost Medium temperature ventilated refrigeration units (0 4 °C), with timed electrical defrost Low temperature ventilated refrigeration units (-26 -20 °C), with timed electrical defrost Medium temperature ventilated refrigeration units (0 4 °C), with electrical defrost (by temperature) Low temperature ventilated refrigeration units (-26 -20 °C), with electrical defrost (by temperature) None (no preset application) with simplified parameter list | 6 Instruction sheet | ERC 213 DKRCE.PI.RL0.G5.ML/520H11075 ENGLISH Quick Configuration at Power Up y STEP 4: Select sensor type "o06" The display automatically shows sensor selection parameter "o06". Press SET to select the sensor type. The display shows the default value (eg. "n10" flashing). Choose sensor type by pressing UP/DOWN (n5=NTC 5 K, n10=NTC 10 K, Ptc=PTC, Pt1=Pt1000) and press SET to confirm. NOTE: All sensors must be the same type. DKRCE.PI.RL0.G5.ML/520H11075 Instruction sheet | ERC 213 | 7 | 8 ENGLISH 4 - Menu structure 1) Parameter groups SET: press for 3 seconds to access status, setup and service Password (if enabled) Status input 2) Parameter name SET Configuration Main switch SET Application 3) Value Application 1-2-3-4-5-6 Application 0 Sensor type Scroll through the parameter names Application 6-5-4-3-2-1 Instruction sheet | ERC 213 DKRCE.PI.RL0.G5.ML/520H11075 Scroll through the parameter groups ENGLISH 5 - Quick Configuration via "cFg" Menu y Press SET for three seconds to access the parameters groups. y Select "CFg" menu and press SET to enter. The first menu "r12" (main switch) is displayed. y Switch OFF main switch (r12=0) for changing the pre-installed application. y Press UP/DOWN to scroll through the parameter list. y Configure the "o61" parameter to select a pre-installed application - Press SET to access the "o61" parameter. - Press UP/DOWN to select an application (AP0= no application selected). - Press SET to confirm, "o61" is displayed. y Continue to set the next parameters ("o06" sensor type) in the "cFg" menu. DKRCE.PI.RL0.G5.ML/520H11075 Instruction sheet | ERC 213 | 9 ENGLISH 6 - Basic operation Adjust the setpoint temperature (short press) SET: adjust setpoint temperature. UP/DOWN: change the temperature setpoint (in setting mode the setpoint flashes). SET: save the temperature setpoint. Initiate a manual defrost DEFROST: press for 3 seconds to initiate a defsost. DEFROST: press for 3 seconds to stop manual defrost. The DEFROST icon is shown during defrost. | 10 Instruction sheet | ERC 213 DKRCE.PI.RL0.G5.ML/520H11075 ENGLISH Basic operation - 02 Initiate a pull down PULL DOWN: press for 3 seconds to initiate pull down. "Pud": is shown for 3 seconds to indicate pull down. The PULL DOWN icon flashes during pull down. PULL DOWN: press for 3 seconds to stop pull down. View an active alarm Temperature and alarm codes alternate flashes until the alarm resolved. The alarm bell is shown. Unlock keyboard - After 5 minutes of no activity, the keypad is locked (if P76=yes). - When the keypad is locked any button press shows "LoC" in the display. - Press UP and DOWN buttons simultaneously for 3 seconds to unlock the keyboard. "unl" is displayed for 3 seconds. DKRCE.PI.RL0.G5.ML/520H11075 Instruction sheet | ERC 213 | 11 ENGLISH 7 - Technical Data FEATURES Power supply Rated power Inputs Allowed sensors types Sensors included in Kit Solution Accuracy DESCRIPTION 115 V AC / 230 V AC 50/60 Hz, galvanic isolated low voltage regulated power supply Less than 0.7 W 4 inputs: 2 analogue, 1 analogue/digital and 1 digital NTC 5000 Ohm at 25 °C, (Beta value=3980 at 25/100 °C - e.g. EKS 211) NTC 10000 Ohm at 25 °C, (Beta value=3435 at 25/85 °C - e.g. EKS 221) PTC 990 Ohm at 25 °C, (e.g. EKS 111) Pt1000, (e.g. AKS 11, AKS 12, AKS 21) NTC 10000 Ohm at 25 °C, cable length = 1.5 m Measuring range: -40 105 °C (-40 221 °F) Controller accuracy: +/-1 K below -35 °C, +/-0.5 K between -35 25 °C, +/-1 K above 25 °C | 12 Instruction sheet | ERC 213 DKRCE.PI.RL0.G5.ML/520H11075 FEATURES Output Display Operating conditions Storage conditions Protection Environmental Resistance to heat and fire EMC category Approvals DKRCE.PI.RL0.G5.ML/520H11075 DESCRIPTION DO1 Compressor relay: 16 A, 16 (16) A, EN 60730 10 FLA / 60 LRA at 230 V, UL60730 16FLA / 72 LRA at 115 V, UL60730 DO2 Defrost relay: 8 A, 2 FLA / 12 LRA, UL60730 8 A, 2 (2 A), EN60730 DO3 Fan relay: 3 A, 2 FLA/12 LRA, UL60730 3 A, 2 (2 A), EN60730 LED display, 3 digits, decimal point and multi-function icons, °C + °F scale -10 55 °C (14 131 °F), 90% Rh -40 70 °C (-40 158 °F), 90% Rh Front: IP65 (Gasket integrated) Rear: IP00 Pollution degree II, non-condensing Category D (UL94-V0) Category I UL recognition (US & Canada) (UL 60730) ENEC (EN 60730) CQC CE (LVD & EMC Directive) EAC (GHOST) NSF ROHS2.0 HACCP temperature monitoring in compliance with EN134785 Class I, when used with AKS 12 sensor Instruction sheet | ERC 213 | 13 ENGLISH ENGLISH 8 - Predefined Application Setup App Mode Description App 0 Cooling None (no preset application) App 1 Cooling Medium temperature ventilated refrigeration units with timed natural defrost App 2 Cooling Medium temperature ventilated refrigeration units with timed electrical defrost App 3 Cooling Low temperature ventilated refrigeration units with timed electrical defrost App 4 Cooling Medium temperature ventilated refrigeration units with electrical defrost (by temperature) App 5 Cooling Low temperature ventilated refrigeration units with electrical defrost (by temperature) App 6 Cooling None (no preset application) with simplified parameter list Temp. Def. type Def. end (2 6 °C) Natural Time (0 4 °C) Electrical Time (-26 -20 °C) Electrical Time (0 4 °C) Electrical Temperature (-26 -20 °C) Electrical Temperature APP 1 DI1 DI2 Sair APP 2/3 DI1 DI2 Sair APP 4/5 DI1 DI2 S5 Sair 230 V AC DO1 DO2 DO3 | 14 230 V AC DO1 DO2 DO3 Instruction sheet | ERC 213 230 V AC DO1 DO2 DO3 DKRCE.PI.RL0.G5.ML/520H11075 ENGLISH 9 - Parameter List Parameter Name - ERC 213 Configuration Main switch -1=service, 0=OFF, 1=ON Predefined applications AP0, AP1, AP2, AP3, AP4, AP5, AP6 Sensor type selection n5=NTC 5 K, n10=NTC 10 K, Ptc=PTC, Pt1=Pt1000 Reference/thermostat Temperature setpoint Differential Min set point limitation Max set point limitation Display offset (correction value in display temperature) Display Unit (°C/°F) Calibration of Sair (offset for air temperature calibration) Main switch -1=service, 0=OFF, 1=ON Night set back (offset temperature during night mode) Thermostat reference displacement (offset temperature) Pull-down duration Pull-down limit temperature Note: hidden parameters are greyed out Code Min Max Unit App. 0 (Def.) App. 1 App. 2 App. 3 App. 4 App. 5 App. 6 cFg r12 -1 1 1 1 1 1 1 1 1 o61 AP0 AP6 AP0 AP1 AP2 AP3 AP4 AP5 AP6 o06 n5 Pt1 n10 n10 n10 n10 n10 n10 n10 r-- r00 -100.0 200.0 C/F 2.0 4.0 r01 0.1 20.0 K 2.0 2.0 r02 -100.0 200.0 C/F -35.0 2.0 r03 -100.0 200.0 C/F 50.0 6.0 r04 -10.0 10.0 K 0.0 0.0 r05 -C -F -C -C r09 -20.0 20.0 K 0.0 0.0 2.0 -24.0 2.0 -24.0 2.0 2.0 2.0 2.0 2.0 2.0 0.0 -26.0 0.0 -26.0 -35.0 4.0 -20.0 4.0 -20.0 50.0 0.0 0.0 0.0 0.0 0.0 -C -C -C -C -C 0.0 0.0 0.0 0.0 - r12 -1 1 1 1 1 1 1 1 - r13 -50.0 50.0 K 0.0 0.0 0.0 0.0 0.0 0.0 0.0 r40 -50.0 50.0 K 0.0 0.0 0.0 0.0 0.0 0.0 - r96 0 960 min 0 0 0 0 0 0 - r97 -100.0 200.0 C/F 0.0 0.0 0.0 0.0 0.0 0.0 - DKRCE.PI.RL0.G5.ML/520H11075 Instruction sheet | ERC 213 | 15 ENGLISH Parameter Name - ERC 213 Alarm Delay for temperature alarm during normal conditions Delay for temperature alarm during pull-down/start-up/defrost High temperature alarm limit (Cabinet/Room) Low temperature alarm limit DI1 delay (time delay for selected DI1 function) DI2 delay (time delay for selected DI2 function) Condenser high alarm limit Condenser high block limit Voltage protection enable Minimum cut-in voltage Minimum cut-out voltage Maximum voltage Defrost Defrost method no=no defrost, nAt=natural, EL=electrical, gAS=hot gas Defrost stop temperature Defrost interval Max defrost time Defrost delay at power up (or DI signal) Drip delay Fan delay after defrost Fan start temperature after defrost Fan during defrost Note: hidden parameters are greyed out | 16 Code Min Max Unit App. 0 (Def.) App. 1 App. 2 App. 3 App. 4 App. 5 App. 6 A-- A03 0 240 min 30 45 30 30 30 30 30 A12 0 240 min 60 90 60 60 60 60 60 A13 -100.0 200.0 C/F 8.0 10.0 8.0 -15.0 8.0 -15.0 8.0 A14 -100.0 200.0 C/F -30.0 0.0 -2.0 -30.0 -2.0 -30.0 -30.0 A27 0 240 min 30 30 30 30 30 30 30 A28 0 240 min 30 30 30 30 30 30 30 A37 0 200 C/F 80 80 80 80 80 80 - A54 0 200 C/F 85 85 85 85 85 85 - A72 no yES no no no no no no no A73 0 270 V 0 0 0 0 0 0 0 A74 0 270 V 0 0 0 0 0 0 0 A75 0 270 V 270 270 270 270 270 270 270 d-- d01 no gAS EL nAt EL EL EL EL EL d02 0.0 50.0 C/F 6.0 - - - 6.0 6.0 6.0 d03 0 240 hours 8 6 8 12 8 12 8 d04 0 480 min 30 45 15 15 30 30 30 d05 0 240.0 min 0 0 0 0 0 0 - d06 0 60 min 0 0 0 0 0 0 5 d07 0 60 min 0 0 0 0 0 0 5 d08 -50.0 0.0 C/F -5.0 - - - -5.0 -5.0 - d09 oFF on on on on on on on on Instruction sheet | ERC 213 DKRCE.PI.RL0.G5.ML/520H11075 ENGLISH Parameter Name - ERC 213 Defrost stop sensor configuration non=time, Air=Sair (air temperature), dEF=S5 (defrost sensor) Compressor accumulated runtime to start defrost, 0=OFF Defrost on demand 20.0=OFF Defrost delay after pull-down 0=OFF Fan control Fan at compressor cutout FFc=fan follow compressor, FAo=fan always ON, FPL= fan pulsating Fan stop evaporator temperature 50.0=OFF Fan ON cycle Fan OFF cycle Compressor Compressor minimum ON time Compressor minimum OFF time Compressor OFF delay at door open Zero crossing selection Note: hidden parameters are greyed out Code Min Max Unit App. 0 (Def.) App. 1 App. 2 App. 3 App. 4 App. 5 App. 6 d10 non dEF non non non non dEF dEF non d18 0 96 hours 0 0 0 0 0 0 - d19 0.0 20.0 K 20.0 - - - 20.0 20.0 - d30 0 960 min 0 0 0 0 0 0 - F-- F01 FFc FPL FAo FAo FAo FAo FAo FAo FAo F04 -50.0 50.0 C/F 50.0 - - - 50.0 50.0 - F07 0 15 min 2 2 2 2 2 2 2 F08 0 15.0 min 2 2 2 2 2 2 2 c-- C01 0 30 min 0 0 0 0 0 0 0 C02 0 30 min 2 2 2 2 2 2 2 C04 0 15 min 0 0 0 0 0 0 1 C70 no yES yES yES yES yES yES yES yES DKRCE.PI.RL0.G5.ML/520H11075 Instruction sheet | ERC 213 | 17 ENGLISH Parameter Name - ERC 213 Code Min Max Unit App. 0 (Def.) App. 1 App. 2 App. 3 App. 4 App. 5 App. 6 Others o-- Delay of outputs at startup o01 0 600 min 5 5 5 5 5 5 5 DI1 configuration oFF=not used, Sdc=status display output, doo=door alarm with resumption, doA=door alarm without resumption, SCH=main o02 oFF Sc switch, nig=day/ night mode, rFd=reference displacement, EAL=external alarm, dEF=defrost, Pud=pull-down, Sc=condenser sensor oFF oFF oFF oFF oFF oFF oFF Serial address o03 0 247 0 0 0 0 0 0 - Password o05 no 999 no no no no no no no Sensor type selection n5=NTC 5 K, n10=NTC 10 K, Ptc=PTC, Pt1=Pt1000 o06 n5 Pt1 n10 n10 n10 n10 n10 n10 - Display resolution 0.1=steps of 0.1 °C 0.5=steps of 0.5 °C, 1.0=steps of 1.0 °C o15 0.1 1.0 0.1 0.1 0.1 0.1 0.1 0.1 0.1 Relay 1 counter (1 count=100 cycles of operation) o23 0 999 0 0 0 0 0 0 - Relay 2 counter (1 count=100 cycles of operation) o24 0 999 0 0 0 0 0 0 - Relay 3 counter (1 count=100 cycles of operation) o25 0 999 0 0 0 0 0 0 - DI2 configuration oFF=not used, Sdc=status display output, doo=door alarm with resumption, doA=door alarm without resumption, SCH=main switch, o37 nig=day/night mode, rFd=reference displacement, EAL=external alarm, dEF=defrost, Pud=pull-down oFF Pud oFF oFF oFF oFF oFF oFF oFF Predefined applications o61 AP0 AP6 AP0 AP1 AP2 AP3 AP4 AP5 - Note: hidden parameters are greyed out | 18 Instruction sheet | ERC 213 DKRCE.PI.RL0.G5.ML/520H11075 ENGLISH Parameter Name - ERC 213 Save settings as factory WARNING: the earlier factory settings are overwritten DO2 config dEF=defrost, ALA=alarm Display at defrost Air=actual air temperature, FrE=freezed temperature, -d-="-d-" is displayed Polarity DI1 input polarity nc=normally closed, no=normally open DI2 input polarity nc=normally closed, no=normally open Invert alarm relay 0=normal, 1=invert relay action Keyboard lock enable Readouts Controller Status S0=cooling ON/Heating ON, S2=wait for compressor ON time to elapse, S3=wait for compressor OFF time to elapserestart time, S4=drip OFF delay after defrost, S10=cooling stop S11=cooling stopped by thermostat/heating OFF, S14=defrosting state, S15=fan delay state after defrost, S17=door open (DI input), S20=emergency cooling, S25=manual control of outputs, S30=continous cycle/Pull-down, S32=delay of outputs at power up Air temperature (Sair) Read the present regulation reference Defrost temperature (S5) Note: hidden parameters are greyed out Code Min Max Unit App. 0 (Def.) App. 1 App. 2 App. 3 App. 4 App. 5 App. 6 o67 no yES no no no no no no - o71 dEF ALA dEF ALA dEF dEF dEF dEF dEF o91 Air -d- P-- P73 nc no -d- -d- -d- -d- -d- -d- -d- no no no no no no no P74 nc no P75 0 1 P76 no yES u-- no no no no no no no 0 0 - - - - - no no no no no no - u00 S0 S32 -- u01 -100.0 200.0 C/F --- u02 -100.0 200.0 C/F --- u09 -100.0 200.0 C/F --- - - - DKRCE.PI.RL0.G5.ML/520H11075 Instruction sheet | ERC 213 | 19 ENGLISH Parameter Name - ERC 213 DI1 input Status of night operation DI2 input Condenser temperature (Sc) Compressor relay status Fan relay status Defrost relay status Light relay status Firmware version readout Alarm status Sair air temperature sensor error S5 defrost sensor error Sc condenser sensor error High temperature alarm Low temperature alarm High voltage alarm Low voltage alarm Condenser alarm Door alarm Standby alarm DI external alarm Note: hidden parameters are greyed out Code u10 u13 u37 U09 u58 u59 u60 u63 u80 Min Max Unit App. 0 (Def.) App. 1 App. 2 App. 3 App. 4 App. 5 App. 6 oFF on --- oFF on --- oFF on --- -100.0 200.0 C/F --- oFF on --- oFF on --- oFF on --- oFF on --- 000 999 --- E29 E27 E30 A01 A02 A99 AA1 A61 A04 A45 A15 | 20 Instruction sheet | ERC 213 DKRCE.PI.RL0.G5.ML/520H11075 ENGLISH Safety Standards Check if the supply voltage is correct before connecting the instrument. Do not expose to water or moisture: use the controller only within the operating limits avoiding sudden temperature changes with high atmospheric humidity to prevent the formation of condensation. Disposal of the Product The appliance (or the product) must be disposed of in accordance with the local waste disposal legislation. EU Design Registration 002566703-0001 Danfoss can accept no responsibility for possible errors in catalogues, brochures and other printed material. Danfoss reserves the right to alter its products without notice. This also applies to products already on order provided that such alterations can be made without subsequent changes being necessary in specifications already agreed. All trademarks in this material are property of the property of the respective companies. Danfoss and Danfoss logotype are trademarks of Danfoss A/S. All rights reserved. DKRCE.PI.RL0.G5.ML/520H11075 Instruction sheet | ERC 213 | 21 FRANÇAIS L'ERC 213 est un régulateur de réfrigération polyvalent et intelligent doté de fonctions de gestion de la température et du dégivrage, disponible avec 3 relais. Le régulateur a été conçu pour répondre aux besoins actuels des applications de réfrigération commerciale. 1 - Principales caractéristiques techniques y Simplicité d'utilisation : quatre touches, une structure de menus facile à utiliser et des applications pré-installées garantissent une maniabilité supérieure. y Installation simple : un relais hautes performances de 16 A permet la connexion directe de lourdes charges sans utiliser des relai intermédiaires: jusqu'à 2 compresseurs en fonction de son facteur de puissance et de l'efficacité moteur (supérieur à 0.65 pour 230 V et supérieur à 0.85 pour 115 V). Une large gamme de types de sondes et de bornes avec raccord à vis compatibles offrent une grande flexibilité pendant l'installation. y Protection de l'unité : des fonctions logicielles spéciales comme la protection du compresseur contre les fluctuations de l'alimentation électrique ou contre une température de condensation élevée garantissent le fonctionnement de l'unité en toute sécurité. y Rendement énergétique : le dégivrage à la demande, le mode jour/nuit et la gestion intelligente du ventilateur de l'évaporateur garantissent le rendement énergétique. | 22 Instruction sheet | ERC 213 DKRCE.PI.RL0.G5.ML/520H11075 FRANÇAIS 2 - Interface utilisateur Fonctionnement des touches Pression prolongée à la mise sous tension: RÉINITIALISATION D'USINE (" FAC " s'affiche) Pression brève : RETOUR Pression prolongée : DIMINUTION Pression brève : POINT DE CONSIGNE DE TEMPÉRATURE/OK Pression prolongée : MENU Pression brève : HAUT Pression prolongée : MARCHE/ARRÊT Pression brève : BAS Pression prolongée : DÉGIVRAGE Icônes de l'afficheur Mode nuit (économies d'énergie) Compresseur en fonctionnement (clignote en mode diminution) Ventilateur en fonctionnement Alarme active Dégivrage Unité (°C ou °F) DKRCE.PI.RL0.G5.ML/520H11075 Instruction sheet | ERC 213 | 23 FRANÇAIS 3 - Configuration rapide à la mise sous tension y ÉTAPE 1 : Mettre sous tension y ÉTAPE 2 : Sélectionner le menu de configuration rapide Dans un délai de 30 secondes suivant la mise sous tension, appuyer sur " < " RETOUR pendant 3 secondes. Le sectionneur principal "r12" est automatique réglé sur OFF (Arrêt). y ÉTAPE 3 : Sélectionner l'application pré-installée " o61 " L'écran affiche automatiquement le paramètre de sélection de l'application " o61 ". Appuyer sur SET pour sélectionner l'application pré-installée. L'écran affiche la valeur par défaut (par ex. " AP0 " clignote). Sélectionner le type d'application en appuyant sur HAUT/BAS et appuyer sur SET pour confirmer. Le régulateur effectue le préréglage des valeurs de paramètre en fonction de l'application sélectionnée et masque les paramètres non pertinents. Astuce: vous pouvez aisément passer de AP0 à AP6, et donc sélectionner la liste simplifiée des paramètres, en pressant la touche HAUT (liste circulaire). App App 0 App 1 App 2 App 3 App 4 App 5 App 6 Description Aucune (aucune application préréglée) Unités de réf. ventilées moyenne température (2 6 °C), avec dégivrage naturel programmé Unités de réf. ventilées moyenne température (0 4 °C), avec dégivrage électrique programmé Unités de réf. ventilées basse température (-26 -20 °C), avec dégivrage électrique programmé Unités de réf. ventilées moyenne température (0 4 °C), avec dégivrage électrique programmé (par la température) Unités de réf. ventilées basse température (-26 -20 °C), avec dégivrage électrique programmé (par la température) Aucun (pas de présélection) avec la liste des paramètres simplifiés | 24 Instruction sheet | ERC 213 DKRCE.PI.RL0.G5.ML/520H11075 FRANÇAIS Configuration rapide à la mise sous tension y ÉTAPE 4 : Sélectionner un type de sonde " o06 " L'écran affiche automatiquement le paramètre de sélection de la sonde " o06 ". Appuyer sur SET pour sélectionner le type de sonde. L'écran affiche la valeur par défaut (par ex. " n10 " clignote). Sélectionner le type de sonde en appuyant sur HAUT/BAS (n5=NTC 5 K, n10=NTC 10 K, Ptc=PTC, Pt1=Pt1000) et appuyer sur SET pour confirmer. REMARQUE : toutes les sondes doivent être du même type. DKRCE.PI.RL0.G5.ML/520H11075 Instruction sheet | ERC 213 | 25 | 26 FRANÇAIS 4 - Structure de menus 1) Groupes de paramètres SET (Régler) : appuyer pendant 3 secondes pour accéder à l'état, à l'installation et à l'entretien Mot de passe (le cas échéant) Entrée d'état 2) Nom du paramètre SET Configuration Sectionneur principal SET Application 3) Valeur Application 1-2-3-4-5-6 Application 0 Type de sonde Faire défiler le nom du paramètre Application 6-5-4-3-2-1 Instruction sheet | ERC 213 DKRCE.PI.RL0.G5.ML/520H11075 Faire défiler le groupe de paramètres FRANÇAIS 5 - Configuration rapide via le menu " cFg " y Appuyer sur la touche SET (Régler) pendant trois secondes pour accéder aux groupes de paramètres. y Sélectionner le menu " cFg " et appuyer sur SET pour entrer dans le menu. Le premier menu " r12 " y (sectionneur principal) s'affiche. y Couper le sectionneur principal (r12=0) pour modifier l'application pré-installée. y Appuyer sur HAUT/BAS pour faire défiler la liste des paramètres. y Configurer le paramètre " o61 " pour sélectionner une application pré-installée - Appuyer sur SET pour accéder au paramètre " o61 ". - Appuyer sur HAUT/BAS pour sélectionner une application (AP0=pas d'application sélectionnée). - Appuyer sur SET pour confirmer, " o61 " s'affiche. y Continuer à régler les paramètres suivants (type de sonde " o06 ") dans le menu " cfg ". DKRCE.PI.RL0.G5.ML/520H11075 Instruction sheet | ERC 213 | 27 FRANÇAIS 6 - Fonctionnement de base Régler la température de consigne (pression brève) SET (Régler) : ajuster la température de consigne. HAUT/BAS : modifier le point de consigne de température (en mode réglage, le point de consigne clignote). SET : enregistrer le point de consigne de température. Lancer un dégivrage manuel DEFROST (Dégivrage) : appuyer pendant 3 secondes pour lancer un dégivrage. DEFROST : appuyer pendant 3 secondes pour arrêter le dégivrage manuel. L'icône DEFROST s'affiche pendant le dégivrage. | 28 Instruction sheet | ERC 213 DKRCE.PI.RL0.G5.ML/520H11075 FRANÇAIS Fonctionnement de base - 02 Lancer une diminution PULL DOWN (Diminution) : appuyer pendant 3 secondes pour lancer une diminution. « Pud » : s'affiche pendant 3 secondes pour indiquer la diminution. L'icône PULL DOWN clignote pendant la diminution. PULL DOWN : appuyer pendant 3 secondes pour arrêter la diminution. Afficher une alarme active La température et les codes d'alarme clignotent en alternance jusqu'à ce q ue l'alarme soit résolue. La sonnette d' alarme s'affiche. Déverrouiller le clavier - Au bout de 5 minutes d'inactivité, le clavier se verrouille (si P76=yes). - Lorsque le clavier est verrouillé, la pression sur une touche entraîne l'affichage de « LoC ». - Appuyer simultanément sur la touche HAUT et BAS pendant 3 secondes pour déverrouiller le clavier. « unl » s'affiche pendant 3 secondes. DKRCE.PI.RL0.G5.ML/520H11075 Instruction sheet | ERC 213 | 29 FRANÇAIS 7 - Données techniques CARACTÉRISTIQUES Alimentation électrique Puissance nominale Entrées Type de sonde autorisé Sonde inclus dans Solution Kit Précision DESCRIPTION Alimentation de 115 V c. a. /230 V c. a., 50/60 Hz, régulée à basse tension et isolée galvaniquement Inférieure à 0,7 W 4 entrées : 2 analogique, 1 analogique/numérique et 1 numérique NTC 5000 Ohm à 25 °C, (valeur Beta=3980 à 25/100 °C - ex. EKS 211) NTC 10000 Ohm à 25 °C, (valeur Beta=3435 à 25/85 °C - ex. EKS 221) PTC 990 Ohm à 25 °C, (ex. EKS 111) Pt1000, (ex. AKS 11, AKS 12, AKS 21) NTC 10000 Ohm à 25 °C, longueur du câble=1.5 m Plage de mesure : -40 105 °C (-40 221 °F) Précision du régulateur : +/-1 K en dessous de -35 °C, +/-0.5 K entre -35 et 25 °C, +/-1 K au-dessus de 25 °C | 30 Instruction sheet | ERC 213 DKRCE.PI.RL0.G5.ML/520H11075 FRANÇAIS CARACTÉRISTIQUES Sortie Affichage Conditions de fonctionnement Conditions de stockage Protection Impact sur l'environnement Résistance à l'incendie et à la chaleur Catégorie D (UL94-V0) Homologations DESCRIPTION Relais du compresseur DO1 16 A, 16 (16) A, EN 60730 10 FLA/ 60 LRA à 230 V, UL60730 16 FLA/ 72 LRA à 115 V, UL60730 Relais de dégivrage DO2 : 8 A, 2 FLA/12 LRA, UL60730 8 A, 2 (2 A), EN60730 Relais de ventilateur DO3 : 3 A, 2 FLA/12 LRA, UL60730 3 A, 2 (2 A), EN60730 Écran LED 3 chiffres, point décimal et icônes multifonctions, valeurs °C/°F De -10 à 55 °C (de 14 à 131 °F), 90% HR De -40 à 70 °C (de - 40 à 158 °F), 90% HR Avant : IP65 (garniture intégrée) Arrière : IP00 Degré de pollution II, sans condensation Catégorie D (UL94-V0) Catégorie I UL reconaissance (US & Canada) (UL 60730) ENEC (EN 60730) CQC CE (LVD & EMC Directive) EAC (GHOST) NSF ROHS2.0 Surveillance de température HACCP en conformité avec EN134785 Classe I, Lorsque l'on utilise des sondes AKS 12 DKRCE.PI.RL0.G5.ML/520H11075 Instruction sheet | ERC 213 | 31 FRANÇAIS 8 - Installation de l'application prédéfinie App Mode Description Temp. Type déf. Fin déf. App 0 Refrodis. Aucune (aucune application préréglée) App 1 Refrodis. Unités de réf. ventilées moyenne température avec dégivrage naturel programmé (2 6 °C) Naturel Temps App 2 Refrodis. Unités de réf. ventilées moyenne température avec dégivrage électrique programmé (0 4 °C) Électrique Temps App 3 Refrodis. Unités de réf. ventilées basse température avec dégivrage électrique programmé (-26 -20 °C) Électrique Temps App 4 Refrodis. Unités de réf. ventilées moyenne température avec dégivrage électrique programmé (par la température) (0 4 °C) Électrique Température App 5 Refrodis. Unités de réf. ventilées basse température avec dégivrage électrique programmé (par la température) (-26 -20 °C) Électrique Température App 6 Refrodis. Aucun (pas de présélection) avec la liste des paramètres simplifiés APP 1 DI1 DI2 Sair APP 2/3 DI1 DI2 Sair APP 4/5 DI1 DI2 S5 Sair 230 V AC DO1 DO2 DO3 | 32 230 V AC DO1 DO2 DO3 Instruction sheet | ERC 213 230 V AC DO1 DO2 DO3 DKRCE.PI.RL0.G5.ML/520H11075 FRANÇAIS 9 -Liste des paramètres Nom du paramètre - ERC 213 Configuration Sectionneur principal -1=entretien, 0=arrêt, 1=marche Applications prédéfinies AP0, AP1, AP2, AP3, AP4, AP5, AP6 Sélection du type de sonde n5=NTC 5 K, n10=NTC 10 K, Ptc=PTC, Pt1=Pt1000 Référence/Thermostat Point de consigne de la température Différentiel Limite min. du point de consigne Limite max. du point de consigne Décalage d'affichage (valeur de correction de la température affichée) Afficheur (°C/°F) Calibrage de Sair (décalage de calibrage de la température d'air) Sectionneur principal -1=entretien, 0=arrêt, 1=marche Régime de nuit (Décalage température en mode nuit) Température de décalage (du déplacement de référence du thermostat) Durée de diminution Température limite de la diminution Remarque : les paramètres cachés sont grisés Code Min. Max. Unité App. 0 (Def.) App. 1 App. 2 App. 3 App. 4 App. 5 App. 6 cFg r12 -1 1 1 1 1 1 1 1 1 o61 AP0 AP6 AP0 AP1 AP2 AP3 AP4 AP5 AP6 o06 n5 Pt1 n10 n10 n10 n10 n10 n10 n10 r-- r00 -100.0 200.0 C/F 2.0 4.0 r01 0.1 20.0 K 2.0 2.0 r02 -100.0 200.0 C/F -35.0 2.0 r03 -100.0 200.0 C/F 50.0 6.0 2.0 -24.0 2.0 -24.0 2.0 2.0 2.0 2.0 2.0 2.0 0.0 -26.0 0.0 -26.0 -35.0 4.0 -20.0 4.0 -20.0 50.0 r04 -10.0 10.0 K 0.0 0.0 0.0 0.0 0.0 0.0 0.0 r05 -C -F -C -C -C -C -C -C -C r09 -20.0 20.0 K 0.0 0.0 0.0 0.0 0.0 0.0 - r12 -1 1 r13 -50.0 50.0 K 1 1 1 1 1 1 - 0.0 0.0 0.0 0.0 0.0 0.0 0.0 r40 -50.0 50.0 K 0.0 0.0 0.0 0.0 0.0 0.0 - r96 0 960 min 0 0 0 0 0 0 - r97 -100.0 200.0 C/F 0.0 0.0 0.0 0.0 0.0 0.0 - DKRCE.PI.RL0.G5.ML/520H11075 Instruction sheet | ERC 213 | 33 FRANÇAIS Nom du paramètre - ERC 213 Code Alarme A-- Temporisation de l'alarme de température pendant des conditions normales A03 Temporisation de l'alarme de température pendant diminution/démarrage/dégivrage A12 Seuil d'alarme de température élevée (armoire/pièce) A13 Seuil d'alarme de basse température A14 Temporisation de DI1 (temporisation pour la fonction DI1 sélectionnée A27 Temporisation DI2 (temporisation pour la fonction DI2 A28 sélectionnée) Seuil d'alarme maximum du condenseur A37 Limite haute de blocage du condenseur A54 Activer la protection de la tension A72 Tension d'enclenchement minimale A73 Tension de coupure minimale A74 Tension maximale A75 Dégivrage d-- Méthode de dégivrage no=aucun dégivrage, nAt=naturel, d01 EL=électrique, gAS=gaz chaud Température d'arrêt du dégivrage d02 Intervalle de dégivrage d03 Temps de dégivrage max. d04 Temporisation du dégivrage à la mise sous tension (ou signal DI) d05 Temps d'égouttage d06 Temporisation du ventilateur d07 Remarque : les paramètres cachés sont grisés Min. Max. Unité App. 0 (Def.) App. 1 App. 2 App. 3 App. 4 App. 5 App. 6 0 240 min 30 45 30 30 30 30 30 0 240 min 60 90 60 60 60 60 60 -100.0 200.0 C/F 8.0 10.0 8.0 -15.0 8.0 -15.0 8.0 -100.0 200.0 C/F -30.0 0.0 -2.0 -30.0 -2.0 -30.0 -30.0 0 240 min 30 30 30 30 30 30 30 0 240 min 30 30 30 30 30 30 30 0 200 C/F 80 80 80 80 80 80 - 0 200 C/F 85 85 85 85 85 85 - no yES no no no no no no no 0 270 V 0 0 0 0 0 0 0 0 270 V 0 0 0 0 0 0 0 0 270 V 270 270 270 270 270 270 270 no gAS EL nAt EL EL EL EL EL 0.0 50.0 C/F 6.0 - - - 6.0 6.0 6.0 0 240 heures 8 6 8 12 8 12 8 0 480 min 30 45 15 15 30 30 30 0 240.0 min 0 0 0 0 0 0 - 0 60 min 0 0 0 0 0 0 5 0 60 min 0 0 0 0 0 0 5 | 34 Instruction sheet | ERC 213 DKRCE.PI.RL0.G5.ML/520H11075 Nom du paramètre - ERC 213 Température de démarrage du ventilateur après dégivrage Ventilateur pendant le dégivrage Configuration de la sonde d'arrêt du dégivrage non=heure, Air=Sair (température de l'air), dEF=S5 (sonde de dégivrage) Temps d'exécution cumulé du compresseur pour démarrer le dégivrage 0=Arrêt Dégivrage à la demande 0.0=Arrêt Temporisation du dégivrage après diminution 0=Arrêt Régulation de ventilateur Ventilateur à la coupure du compresseur FFc=le ventilateur suit le compresseur, FAo=le ventilateur est toujours sous tension, FPL= ventilateur à impulsions Température de l'évaporateur à l'arrêt du ventilateur 50.0=Arrêt Cycle d'activation du ventilateur Cycle d'arrêt du ventilateur Compresseur Durée minimum de marche du compresseur Durée de mise hors tension minimum du compresseur Temporisation d'arrêt du compresseur à l'ouverture de la porte Sélection du passage par zéro Remarque : les paramètres cachés sont grisés DKRCE.PI.RL0.G5.ML/520H11075 Code d08 d09 Min. Max. Unité App. 0 (Def.) App. 1 App. 2 App. 3 App. 4 App. 5 App. 6 -50.0 0.0 C/F -5.0 - - - -5.0 -5.0 - oFF on on on on on on on on d10 non dEF non non non non dEF dEF non d18 0 96 heures 0 0 0 0 0 0 - d19 0.0 20.0 K 20.0 - - - 20.0 20.0 - d30 0 960 min 0 0 0 0 0 0 - F-- F01 FFc FPL FAo FAo FAo FAo FAo FAo FAo F04 -50.0 50.0 C/F 50.0 - - - 50.0 50.0 - F07 0 15 min 2 2 2 2 2 2 2 F08 0 15.0 min 2 2 2 2 2 2 2 c-- C01 0 30 min 0 0 0 0 0 0 0 C02 0 30 min 2 2 2 2 2 2 2 C04 0 15 min 0 0 0 0 0 0 1 C70 no yES yES yES yES yES yES yES yES Instruction sheet | ERC 213 | 35 FRANÇAIS FRANÇAIS Nom du paramètre - ERC 213 Code Autres o-- Temporisation des sorties à la mise en route o01 Configuration de DI1 oFF=non utilisé, Sdc=affichage d'état sortie, doo=Alarme de porte avec reprise, doA=Alarme de porte sans reprise, SCH=sectionneur principal, nig=mode jour/ o02 nuit, rFd=déplacement de référence, EAL=alarme externe, dEF=dégivrage, Pud=diminution, Sc=sonde du condenseur Adresse série o03 Mot de passe o05 Sélection du type de sonde n5=NTC 5 K, n10=NTC 10 K, o06 Ptc=PTC, Pt1=Pt1000 Résolution de l'écran 0.1=incréments de 0.1 °C, 0.5=incréments de 0.5 °C, o15 1.0=incréments de 1.0 °C Compteur du relais 1 (1 comptage=100 cycles de fonctionnement) o23 Compteur du relais 2 (1 comptage=100 cycles de fonctionnement) o24 Compteur du relais 3 (1 comptage=100 cycles de fonctionnement) o25 Configuration de DI2 oFF=non utilisé, Sdc=affichage d'état sortie, doo=Alarme de porte avec reprise, doA=Alarme de porte sans reprise, SCH=sectionneur o37 principal, nig=mode jour/nuit, rFd=déplacement de référence, EAL=alarme externe, dEF=dégivrage, Pud=diminution Remarque : les paramètres cachés sont grisés Min. Max. Unité App. 0 (Def.) App. 1 App. 2 App. 3 App. 4 App. 5 App. 6 0 600 min 5 5 5 5 5 5 5 oFF Sc 0 247 no 999 n5 Pt1 0.1 1.0 0 999 0 999 0 999 oFF Pud oFF oFF oFF oFF oFF oFF oFF 0 0 0 0 0 0 - no no no no no no no n10 n10 n10 n10 n10 n10 - 0.1 0.1 0.1 0.1 0.1 0.1 0.1 0 0 0 0 0 0 - 0 0 0 0 0 0 - 0 0 0 0 0 0 - oFF oFF oFF oFF oFF oFF oFF | 36 Instruction sheet | ERC 213 DKRCE.PI.RL0.G5.ML/520H11075 FRANÇAIS Nom du paramètre - ERC 213 Code Min. Max. Unité App. 0 (Def.) App. 1 App. 2 App. 3 App. 4 App. 5 App. 6 Applications prédéfinies o61 AP0 AP6 AP0 AP1 AP2 AP3 AP4 AP5 - Enregistrer les réglages par défaut AVERTISSEMENT: les réglages d'usine antérieurs sont écrasés o67 no yES no no no no no no - Configuration de DO2 dEF=defrost, ALA=alarm o71 dEF ALA dEF ALA dEF dEF dEF dEF dEF Affichage au dégivrage Air=température réelle de l'air, o91 Air -d- FrE=température de gelée, -d-=" -d- " s'affiche -d- -d- -d- -d- -d- -d- -d- Polarité P-- Polarité d'entrée DI1 nc=normalement fermée, no=normalement ouverte P73 nc no no no no no no no no Polarité d'entrée DI2 nc=normalement fermée, no=normalement ouverte P74 nc no no no no no no no no Inverser le relais d'alarme 0=normal, 1=action d'inverser le relais P75 0 1 0 0 - - - - - Activer le verrouillage du clavier P76 no yES no no no no no no - Relevés u-- État du régulateur S0=Refroidissement activé/Chauffage activé, S2=attendre la fin du délai d'activation du compresseur, S3=attendre la fin du délai d'activation du compresseur-temps de redémarrage, S4=temporisation d'arrêt de l'égouttage après dégivrage, S10=refroidissement arrêté par l'arrêt du sectionneur principal, S11=refroidissement arrêté u00 S0 S32 -- par le thermostat/arrêt du chauffage, S14=état du dégivrage, S15=état de la temporisation du ventilateur après dégivrage, S17=ouverture de la porte (entrée DI), S20=refroidissement d'urgence, S25=contrôle manuel des sorties, S30=cycle continu/ diminution S32=temporisation des sorties à la mise en route Remarque : les paramètres cachés sont grisés DKRCE.PI.RL0.G5.ML/520H11075 Instruction sheet | ERC 213 | 37 FRANÇAIS Nom du paramètre - ERC 213 Température de l'air (Sair) Affichage de la référence de régulation actuelle Température de dégivrage (S5) Entrée DI2 État du régime de nuit Entrée DI2 Température du condenseur (Sc) État du relais du compresseur État du relais du ventilateur État du relais de dégivrage État du relais d'éclairage Relevé de la version du micrologiciel État d'alarme Incident sur la sonde de température de l'air Sair Incident sur la sonde de dégivrage S5 Incident sur la sonde du condenseur Sc Alarme de température élevée Alarme de basse température Alarme de haute tension Alarme de basse tension Alarme du condenseur Alarme porte Alarme de veille Alarme externe DI Remarque : les paramètres cachés sont grisés Code u01 u02 u09 u10 u13 u37 U09 u58 u59 u60 u63 u80 Min. -100.0 -100.0 -100.0 oFF oFF oFF -100.0 oFF oFF oFF oFF 000 Max. 200.0 200.0 200.0 on on on 200.0 on on on on 999 Unité C/F C/F C/F C/F App. 0 (Def.) --- --- --------------------- App. 1 App. 2 App. 3 App. 4 App. 5 App. 6 - - - E29 E27 E30 A01 A02 A99 AA1 A61 A04 A45 A15 | 38 Instruction sheet | ERC 213 DKRCE.PI.RL0.G5.ML/520H11075 FRANÇAIS Normes de sécurité Vérifier si la tension d'alimentation est correcte avant de brancher l'instrument. Ne pas exposer à l'eau ou à l'humidité : Utiliser le régulateur uniquement dans les limites d'exploitation prévues en évitant les variations subites de température avec une forte humidité atmosphérique pour empêcher la formation de condensation. Mise au rebut du produit L'appareil (ou le produit) doit être mis au rebut conformément à la législation locale en vigueur sur la mise au rebut des déchets. Enregistrement des modèles de l'Union européenne 002566703-0001 Danfoss n'assume aucune responsabilité quant aux éventuelles erreurs présentes dans les catalogues, brochures ou autres documentations écrites. Danfoss se réserve le droit de modifier ses produits sans préavis. Cela vaut également pour les produits déjà commandés pour autant que ces modifications se fassent sans changements ultérieurs des spécifications convenues. Toutes les marques commerciales mentionnées dans la présente documentation sont la propriété de leurs détenteurs respectifs. Danfoss et le logotype de Danfoss sont des marques commerciales de Danfoss A/S. Tous droits réservés. DKRCE.PI.RL0.G5.ML/520H11075 Instruction sheet | ERC 213 | 39 ESPAÑOL El ERC 213 es un controlador de refrigeración multifuncional inteligente con funciones de gestión de la temperatura y el desescarche, disponible con 3 relés. El diseño del controlador cumple los requisitos actuales de las aplicaciones de refrigeración comercial. 1 - Características técnicas y Facilidad de uso: Sus cuatro botones, la sencilla estructura del menú y las aplicaciones preinstaladas garantizan la máxima usabilidad. y Instalación sencilla: Un relé de 16 A de alto rendimiento permite conectar directamente grandes cargas sin necesidad de usar relé intermedios: hasta 2 compresores hp en función de su factor de potencia y la eficiencia del motor (mayor de 0,65 para 230 V y mayor que 0,85 para 115 V). Amplia gama de sensores compatibles y terminales de conexión roscada para garantizar la máxima flexibilidad de instalación. y Protección de la unidad: Funciones de software especiales para proteger el compresor frente a las fluctuaciones de la fuente de alimentación o las altas temperaturas de condensación, garantizando así el funcionamiento seguro de la unidad. y Eficiencia energética: Desescarche bajo demanda, modo diurno/nocturno y gestión inteligente del ventilador del evaporador para asegurar la eficiencia energética. | 40 Instruction sheet | ERC 213 DKRCE.PI.RL0.G5.ML/520H11075 ESPAÑOL 2 - Interfaz de usuario Uso de los botones Pulsación prolongada al encender: RESTABLECIMIENTO DE LA CONFIGURACIÓN PREDETERMINADA (la pantalla mostrará "FAC") Pulsación breve: ATRÁS Pulsación prolongada: VACIADO Pulsación breve: VALOR DE CONSIGNA DE TEMPERATURA/ACEPTAR Pulsación prolongada: MENÚ Pulsación breve: ARRIBA Pulsación prolongada: activar/desactivar Pulsación breve: ABAJO Pulsación prolongada: DESESCARCHE Iconos de la pantalla Modo nocturno (ahorro energético) Compresor en funcionamiento (parpadea en el modo de vaciado) Ventilador en funcionamiento Alarma activa Desescarche Unidad (°C o °F) DKRCE.PI.RL0.G5.ML/520H11075 Instruction sheet | ERC 213 | 41 ESPAÑOL 3 - Configuración rápida al encender y PASO 1: Encendido y PASO 2: Selección del menú de configuración rápida Mantenga pulsado ATRÁS ("<") durante 3 segundos antes de transcurridos 30 segundos desde el encendido. El interruptor principal ("r12") se desactivará automáticamente. y PASO 3: Selección de la aplicación preinstalada ("o61") La pantalla mostrará automáticamente el parámetro de selección de aplicación ("o61"). Pulse SET para seleccionar la aplicación preinstalada. La pantalla mostrará el valor predeterminado de forma intermitente (por ejemplo, "AP0"). Elija el tipo de aplicación pulsando ARRIBA/ABAJO y pulse SET para confirmar. El controlador predefinirá los valores de los parámetros de acuerdo con la aplicación predeterminada y ocultará los parámetros irrelevantes. Sugerencia: Usted puede fácilmente cambiar entre las aplicaciones AP0 y AP6, así seleccionar la lista simplificada de parámetros a través del botón UP. Aplic. App 0 App 1 App 2 App 3 App 4 App 5 App 6 Descripción Ninguna (ninguna aplicación predefinida) Media temperaturas (2 a 6 °C), unidades de ref. ventiladas con desescarche natural por tiempo Media temperaturas (0 a 4 °C), unidades de ref. ventiladas con desescarche eléctrico por tiempo Baja temperaturas (-26 a -20 °C), unidades de ref. ventiladas con desescarche eléctrico por tiempo Media temperaturas (0 a 4 °C), unidades de ref. ventiladas con desescarche eléctrico por temperatura Baja temperaturas (-26 a -20 °C), unidades de ref. ventiladas con desescarche eléctrico por temperatura Estas aplicaciones no cambian ningún valor, sólo reducen la cantidad de parámetros que se desea modificar | 42 Instruction sheet | ERC 213 DKRCE.PI.RL0.G5.ML/520H11075 ESPAÑOL Configuración rápida al encender y PASO 4: Selección del tipo de sensor ("o06") La pantalla mostrará automáticamente el parámetro de selección de sensor ("o06"). Pulse SET para seleccionar el tipo de sensor. La pantalla mostrará el valor predeterminado de forma intermitente (por ejemplo, "n10"). Elija el tipo de sensor pulsando ARRIBA/ABAJO (n5=NTC 5 K, n10=NTC 10 K, Ptc=PTC, Pt1=Pt1000); pulse SET para confirmar. NOTA: Todos los sensores deben ser del mismo tipo DKRCE.PI.RL0.G5.ML/520H11075 Instruction sheet | ERC 213 | 43 | 44 ESPAÑOL 4 - Estructura del menú 1) Grupos de parámetros SET: mantener pulsado durante 3 segundos para acceder a los modos de estado, configuración y mantenimiento Contraseña (si está habilitada) Entrada de estado 2) Nombre del parámetro SET Configuración Interruptor principal SET Aplicaciones 3) Valor Aplicación 1-2-3-4-5-6 Aplicación 0 Tipo de sensor Recorrer los nombres de los parámetros Aplicación 6-5-4-3-2-1 Instruction sheet | ERC 213 DKRCE.PI.RL0.G5.ML/520H11075 Recorrer los grupos de parámetros ESPAÑOL 5 - Configuración rápida a través del menú "cFg" y Mantenga pulsado SET durante tres segundos para acceder a los grupos de parámetros. y Seleccione el menú "cFg" y pulse SET para acceder a él. La pantalla mostrará el primer menú: "r12" (interruptor principal). y Desactive el interruptor principal (r12 = 0) para cambiar la aplicación preinstalada. y Pulse ARRIBA/ABAJO para desplazarse por la lista de parámetros. y Configure el parámetro "o61" para seleccionar una aplicación preinstalada: - Pulse SET para acceder al parámetro "o61". - Pulse ARRIBA/ABAJO para seleccionar una aplicación (AP0 = ninguna aplicación seleccionada). - Pulse SET para confirmar; la pantalla mostrará "o61". y Continúe configurando el tipo de sens ("o06") en el menú "cFg". DKRCE.PI.RL0.G5.ML/520H11075 Instruction sheet | ERC 213 | 45 ESPAÑOL 6 - Operaciones básicas Establecimiento del punto de ajuste de temperatura SET (pulsación breve): establecimiento del punto de ajuste de temperatura. ARRIBA/ABAJO: modificación del punto de ajuste de temperatura (en el modo de ajuste, el punto de ajuste parpadea). SET: almacenamiento del punto de ajuste de temperatura. Inicio de un desescarche manual DESESCARCHE: mantener pulsado durante 3 segundos para iniciar el desescarche. DESESCARCHE: mantener pulsado durante 3 segundos para detener el desescarche manual. La pantalla mostrará el icono de DESESCARCHE durante el desescarche. | 46 Instruction sheet | ERC 213 DKRCE.PI.RL0.G5.ML/520H11075 ESPAÑOL Operaciones básicas Inicio de un vaciado VACIADO: mantener pulsado durante 3 segundos para iniciar el vaciado. La pantalla mostrará "Pud" durante 3 segundos para indicar el vaciado. El icono de VACIADO parpadeará en la pantalla durante el vaciado. VACIADO: mantener pulsado durante 3 segundos para detener el vaciado. Consulta de una alarma activa Desbloqueo del teclado La pantalla mostrará alternativamente la temperatura y el código de alarma correspondiente hasta que se resuelva la alarma. Se mostrará un icono con forma de campana. - El teclado se bloquea si no tiene lugar ninguna actividad durante 5 minutos (si P76 = yES). - Cuando el teclado está bloqueado, la pantalla muestra "LoC" al pulsar cualquier botón. - Cuando el teclado está bloqueado, la pantalla muestra "LoC" al pulsar cualquier botón. DKRCE.PI.RL0.G5.ML/520H11075 Instruction sheet | ERC 213 | 47 ESPAÑOL 7 - Datos técnicos CARACTERÍSTICAS Fuente de alimentación Potencia nominal Entradas Tipos de sensores permitidos Sensores incluidos en Solución Kit NTC Precisión DESCRIPCIÓN Fuente de alimentación regulada de baja tensión con aislamiento galvánico, 115 V c.a./230 V c.a., 50/60 Hz Menos de 0.7 W 4 entradas: 2 analógica, 1 analógica/digital y 1 digital NTC 5000 Ohm a 25 °C, (valeur Beta=3980 a 25/100 °C - ex. EKS 211) NTC 10000 Ohm a 25 °C, (valeur Beta=3435 a 25/85 °C - ex. EKS 221) PTC 990 Ohm a 25 °C, (ex. EKS 111) Pt1000, (ex. AKS 11, AKS 12, AKS 21) NTC 10000 Ohm a 25 °C, cable de 1.5 m Rango de medida: -40 a 105 °C (-40 a 221 °F) Precisión del controlador: +/-1 K a menos de -35 °C, +/-0.5 K entre -35 y 25 °C, +/-1 K a más de 25 °C | 48 Instruction sheet | ERC 213 DKRCE.PI.RL0.G5.ML/520H11075 ESPAÑOL CARACTERÍSTICAS Salida Pantalla Condiciones de funcionamiento Condiciones de almacenamiento Protección Condiciones ambientales Resistencia al calor y al fuego Categoría EMC Homologaciones DESCRIPCIÓN Relé de compresor DO1: 16 A, 16 (16) A (EN 60730) 10 FLA/60 LRA at 230 V (UL 60730) 16 FLA/72 LRA at 115 V (UL 60730) Relé de desescarche DO2: 8 A, 2 FLA/12 LRA (UL 60730) 8 A, 2 (2 A) (EN 60730) Relé de ventilador DO3: 3 A, 2 FLA/12 LRA (UL 60730) 3 A, 2 (2 A) (EN 60730) Pantalla LED de 3 dígitos con punto decimal, iconos de función y escala °C + °F -10 a 55 °C (14 a 131 °F), 90% H.R. -40 a 70 °C (-40 a 158 °F), 90% H.R. Frontal: IP65 (junta integrada) Posterior: IP00 Grado de contaminación II, sin condensación Categoría D (UL 94-V0) Categoría I UL reconocimiento (US & Canada) (UL 60730) ENEC (EN 60730) CQC CE (LVD & EMC Directive) EAC (GHOST) NSF ROHS2.0 Monitorización de temperatura HACCP en conformidad con EN134785 Clase I, Cuando se utiliza con un sensor AKS 12 DKRCE.PI.RL0.G5.ML/520H11075 Instruction sheet | ERC 213 | 49 ESPAÑOL 8 - Configuración de la aplicación predefinida Apl. Modo Modo Apl. 0 Enfriam. Ninguna (ninguna aplicación predefinida) Apl. 1 Enfriam. Media temperaturas unidades de ref. ventiladas con desescarche natural por tiempo Apl. 2 Enfriam. Media temperaturas unidades de ref. ventiladas con desescarche natural por tiempo Apl. 3 Enfriam. Media temperaturas unidades de ref. ventiladas con desescarche natural por tiempo Apl. 4 Enfriam. Media temperaturas unidades de ref. ventiladas con desescarche natural por tiempo Apl. 5 Enfriam. Media temperaturas unidades de ref. ventiladas con desescarche natural por tiempo Apl. 6 Enfriam. Estas aplicaciones no cambian ningún valor, sólo reducen la cantidad de parámetros que se desea modificar. APP 1 DI1 DI2 Sair APP 2/3 DI1 DI2 Sair Temp. Tipo deses. Fin deses. (2 6 °C) Natural Tiempo (0 4 °C) Eléctrico Tiempo (-26 -20 °C) Eléctrico Tiempo (0 4 °C) Eléctrico Temperaturas (-26 -20 °C) Eléctrico Temperaturas APP 4/5 DI1 DI2 S5 Sair 230 V AC DO1 DO2 DO3 | 50 230 V AC DO1 DO2 DO3 Instruction sheet | ERC 213 230 V AC DO1 DO2 DO3 DKRCE.PI.RL0.G5.ML/520H11075 ESPAÑOL 9 - Listado de parámetros Nombre del parámetro - ERC 213 Código Mín. Máx. Unidad Configuración cFg Interruptor principal -1=mantenimiento, 0=desactivado, 1=activado r12 -1 1 Aplicaciones predefinidas AP0, AP1, AP2, AP3, AP4, AP5, AP6 o61 AP0 AP6 Selección de tipo de sensor n5=NTC 5 K, n10=NTC 10 K, Ptc=PTC, Pt1=Pt1000 o06 n5 Pt1 Referencia/termostato r-- Punto de ajuste de temperatura r00 -100.0 200.0 C/F Diferencial r01 0.1 20.0 K Límite mín. del punto de ajuste r02 -100.0 200.0 C/F Límite máx. del punto de ajuste r03 -100.0 200.0 C/F Desviación en pantalla (corrección de la temperatura mostrada en la pantalla) r04 -10.0 10.0 K Unidad de pantalla (°C/°F) r05 -C -F Calibración de Sair (desviación de la calibración de la temperatura del aire) r09 -20.0 20.0 K Interruptor principal -1=mantenimiento, 0=desactivado, 1=activado r12 -1 1 Reducción nocturna (desviación de la temperatura en el modo nocturno) r13 -50.0 50.0 K Desviación de temperatura del desplazamiento de referencia del termostato r40 -50.0 50.0 K Tiempo de vaciado r96 0 960 min Límite de temperatura de vaciado r97 -100.0 200.0 C/F Nota: Los parámetros ocultos se muestran atenuados. Apl. 0 Pred. 1 AP0 n10 2.0 2.0 -35.0 50.0 0.0 -C 0.0 1 0.0 0.0 0 0.0 Aplic. 1 1 AP1 n10 4.0 2.0 2.0 6.0 0.0 -C 0.0 1 0.0 0.0 0 0.0 Aplic. 2 1 AP2 n10 2.0 2.0 0.0 4.0 0.0 -C 0.0 1 0.0 0.0 0 0.0 Aplic. 3 1 AP3 n10 -24.0 2.0 -26.0 -20.0 0.0 -C 0.0 1 0.0 0.0 0 0.0 Aplic. 4 1 AP4 n10 2.0 2.0 0.0 4.0 0.0 -C 0.0 1 0.0 0.0 0 0.0 Aplic. 5 1 AP5 n10 -24.0 2.0 -26.0 -20.0 0.0 -C 0.0 1 0.0 0.0 0 0.0 Aplic. 6 1 AP6 n10 2.0 2.0 -35.0 50.0 0.0 -C - - 0.0 - DKRCE.PI.RL0.G5.ML/520H11075 Instruction sheet | ERC 213 | 51 ESPAÑOL Nombre del parámetro - ERC 213 Código Mín. Alarma A-- Retardo de la alarma de temperatura en condiciones normales A03 Retardo de la alarma de temperatura durante el vaciado/arranque/desescarche A12 Límite de alarma de alta temperatura (arcón/sala) A13 Límite de alarma de baja temperatura A14 Retardo de la entrada digital DI1 (retardo de la función asignada a la entrada A27 digital DI1) Retardo de la entrada digital DI2 (retardo de la función asignada a la entrada A28 digital DI2) Límite de alarma de condensador por nivel alto A37 Límite de bloqueo de condensador por nivel alto A54 Protección de tensión A72 Tensión de conexión mínima A73 Tensión de desconexión mínima A74 Tensión máxima A75 Desescarche d-- Método de desescarche no=sin desescarche, nAt=natural, d01 EL=eléctrico, gAS=gas caliente Temperatura de parada del desescarche d02 Intervalos deses. d03 Tiempo máx. de desescarche d04 Retardo del desescarche al encender (o con señal DI) d05 Retardo de goteo d06 Retardo del ventilador tras el desescarche d07 Nota: Los parámetros ocultos se muestran atenuados. 0 0 -100.0 -100.0 0 0 0 0 no 0 0 0 no 0.0 0 0 0 0 0 Máx. Unidad Apl. 0 Pred. 240 min 30 240 min 60 200.0 C/F 8.0 200.0 C/F -30.0 240 min 30 240 min 30 200 C/F 80 200 C/F 85 yES no 270 V 0 270 V 0 270 V 270 gAS EL 50.0 C/F 6.0 240 horas 8 480 min 30 240.0 min 0 60 min 0 60 min 0 Aplic. 1 45 90 10.0 0.0 30 30 80 85 no 0 0 270 nAt 6 45 0 0 0 Aplic. 2 30 60 8.0 -2.0 30 30 80 85 no 0 0 270 EL 8 15 0 0 0 Aplic. 3 30 60 -15.0 -30.0 30 30 80 85 no 0 0 270 EL 12 15 0 0 0 Aplic. 4 30 60 8.0 -2.0 30 30 80 85 no 0 0 270 EL 6.0 8 30 0 0 0 Aplic. 5 30 60 -15.0 -30.0 30 30 80 85 no 0 0 270 EL 6.0 12 30 0 0 0 Aplic. 6 30 60 8.0 -30.0 30 30 - no 0 0 270 EL 6.0 8 30 5 5 | 52 Instruction sheet | ERC 213 DKRCE.PI.RL0.G5.ML/520H11075 ESPAÑOL Nombre del parámetro - ERC 213 Código Mín. Máx. Unidad Apl. 0 Pred. Aplic. 1 Aplic. 2 Aplic. 3 Aplic. 4 Aplic. 5 Aplic. 6 Temperatura de arranque del ventilador tras el desescarche d08 -50.0 0.0 C/F -5.0 - - - -5.0 -5.0 - Ventilador durante el desescarche d09 oFF on on on on on on on on Configuración del sensor de parada del desescarche non=tiempo, Air=Sair (temperatura del aire), dEF=S5 (sensor de desescarche) d10 non dEF non non non non dEF dEF non Tiempo de funcionamiento acumulado del compresor antes de iniciar el d18 0 96 horas 0 0 0 0 0 0 - desescarche, 0 = desactivado Desescarche bajo demanda 20,0=desactivado d19 0.0 20.0 K 20.0 - - - 20.0 20.0 - Retardo del desescarche tras el vaciado 0=desactivado d30 0 960 min 0 0 0 0 0 0 - Control del ventilador F-- Ventilador al desconectar el compresor FFc=ventilador tras compresor, FAo=ventilador siempre activo, FPL=ventilador por pulsos F01 FFc FPL FAo FAo FAo FAo FAo FAo FAo Temperatura del evaporador a la que se detiene el ventilador 50.0=desactivado F04 -50.0 50.0 C/F 50.0 - - - 50.0 50.0 - Ciclo de activación del ventilador F07 0 15 min 2 2 2 2 2 2 2 Ciclo de desactivación del ventilador F08 0 15.0 min 2 2 2 2 2 2 2 Compresor c-- Tiempo mínimo de activación del compresor C01 0 30 min 0 0 0 0 0 0 0 Tiempo mínimo de desactivación del compresor C02 0 30 min 2 2 2 2 2 2 2 Retardo de desactivación del compresor al abrir la compuerta C04 0 15 min 0 0 0 0 0 0 1 Selección de cruce por cero C70 no yES yES yES yES yES yES yES yES Otras aplicaciones o-- Retardo de las salidas al arrancar o01 0 600 min 5 5 5 5 5 5 5 Nota: Los parámetros ocultos se muestran atenuados. DKRCE.PI.RL0.G5.ML/520H11075 Instruction sheet | ERC 213 | 53 ESPAÑOL Nombre del parámetro - ERC 213 Código Mín. Configuración de la entrada digital DI1 oFF=no se usa, Sdc=salida de pantalla de estado, doo=alarma de compuerta con reanudación, doA=alarma de compuerta sin reanudación, SCH=interruptor principal, o02 oFF nig=modo diurno/nocturno, rFd=desplazamiento de referencia, EAL=alarma externa, dEF=desescarche, Pud=vaciado, Sc=sensor de condensador Dirección serie o03 0 Contraseña o05 no Selección de tipo de sensor n5=NTC 5 K, n10=NTC 10 K, Ptc=PTC, Pt1=Pt1000 o06 n5 Resolución de la pantalla 0.1=intervalos de 0.1 °C, 0.5=intervalos de 0.5 °C, o15 0.1 1.0=intervalos de 1.0 °C Relé 1, contador (1 cuenta=100 ciclos de funcionamiento) o23 0 Relé 2, contador (1 cuenta=100 ciclos de funcionamiento) o24 0 Relé 3, contador (1 cuenta=100 ciclos de funcionamiento) o25 0 Configuración de la entrada digital DI2 oFF=no se usa, Sdc=salida de pantalla de estado, doo=alarma de compuerta con reanudación, doA=alarma de compuerta sin reanudación, SCH=interruptor o37 oFF principal, nig=modo diurno/nocturno, rFd=desplazamiento de referencia, EAL=alarma externa, dEF=desescarche, Pud=vaciado Aplicaciones predefinidas o61 AP0 Guardar configuración como predeterminada ADVERTENCIA: Se sobrescribirá la anterior o67 no configuración predeterminada Nota: Los parámetros ocultos se muestran atenuados. Máx. Unidad Sc 247 999 Pt1 1.0 999 999 999 Pud AP6 yES Apl. 0 Pred. oFF 0 no n10 0.1 0 0 0 oFF AP0 no Aplic. Aplic. Aplic. Aplic. Aplic. Aplic. 1 2 3 4 5 6 oFF oFF oFF oFF oFF oFF 0 0 0 0 0 - no no no no no no n10 n10 n10 n10 n10 - 0.1 0.1 0.1 0.1 0.1 0.1 0 0 0 0 0 - 0 0 0 0 0 - 0 0 0 0 0 - oFF oFF oFF oFF oFF oFF AP1 AP2 AP3 AP4 AP5 - no no no no no - | 54 Instruction sheet | ERC 213 DKRCE.PI.RL0.G5.ML/520H11075 ESPAÑOL Nombre del parámetro - ERC 213 Código Mín. Máx. Unidad Apl. 0 Pred. Aplic. 1 Aplic. 2 Aplic. 3 Aplic. 4 Aplic. 5 Aplic. 6 Configuración de DO2 (dEF=defrost, ALA=alarm) o71 dEF ALA dEF ALA dEF dEF dEF dEF dEF Pantalla durante el desescarche Air=temperatura real del aire, FrE=temperatura de congelación, -d-=la pantalla muestra "-d-" o91 Air -d- -d- -d- -d- -d- -d- -d- -d- Polaridad P-- Polaridad de la entrada digital DI1 nc=normalmente cerrada, no=normalmente abierta P73 nc no no no no no no no no Polaridad de la entrada digital DI2 nc=normalmente cerrada, no=normalmente abierta P74 nc no no no no no no no no Relé de alarma invertido 0=normal, 1=acción de relé invertida P75 0 1 0 0 - - - - - Bloqueo de teclado P76 no yES no no no no no no - Lecturas u-- Estado del controlador S0=refrigeración activa/calefacción activa, S2=esperando que transcurra el tiempo de activación del compresor, S3=esperando que transcurra el tiempo de desactivación del compresor/tiempo de reinicio, S4=retardo de desactivación de goteo tras el desescarche, S10=refrigeración detenida por interruptor principal=desactivado, S11=refrigeración detenida u00 S0 S32 -- por termostato/calefacción=desactivado, S14=estado del desescarche, S15=estado de retardo del ventilador tras el desescarche, S17=compuerta abierta (entrada digital DI), S20=refrigeración de emergencia, S25=control manual de las salidas, S30=ciclo continuo/vaciado, S32=retardo de las salidas al encender Nota: Los parámetros ocultos se muestran atenuados. DKRCE.PI.RL0.G5.ML/520H11075 Instruction sheet | ERC 213 | 55 ESPAÑOL Nombre del parámetro - ERC 213 Código Mín. Temperatura del aire (Sair) u01 Lectura de la referencia de regulación actual u02 Temperatura de desescarche (S5) u09 Entrada digital DI1 u10 Estado de funcionamiento nocturno u13 Entrada digital DI2 u37 Temperatura del condensador (Sc) U09 Estado del relé del compresor u58 Estado del relé del ventilador u59 Estado del relé de desescarche u60 Estado del relé de iluminación u63 Lectura de la versión de firmware u80 Alarm status Error del sensor de temperatura del aire Sair E29 Error del sensor de desescarche S5 E27 Error del sensor del condensador Sc E30 Alarma de alta temperatura A01 Alarma de baja temperatura A02 Alarma de alta tensión A99 Alarma de baja tensión AA1 Alarma del condensador A61 Alarma de compuerta A04 Alarma en espera A45 Alarma externa de entrada digital DI A15 Nota: Los parámetros ocultos se muestran atenuados. -100.0 -100.0 -100.0 oFF oFF oFF -100.0 oFF oFF oFF oFF 000 Máx. Unidad 200.0 C/F 200.0 C/F 200.0 C/F on on on 200.0 C/F on on on on 999 Apl. 0 Pred. ------------------------- Aplic. 1 - Aplic. 2 - Aplic. 3 - Aplic. 4 Aplic. 5 Aplic. 6 | 56 Instruction sheet | ERC 213 DKRCE.PI.RL0.G5.ML/520H11075 ESPAÑOL Instrucciones de seguridad Compruebe que la tensión de alimentación sea correcta antes de conectar el instrumento. No exponer al agua ni la humedad: use el controlador sólo dentro de sus límites de funcionamiento, evitando los cambios bruscos de temperatura con humedad atmosférica elevada para impedir la formación de condensación. Eliminación del producto El aparato (o producto) debe eliminarse de acuerdo con la legislación local en materia de eliminación de residuos. Patente de diseño de la UE 002566703-0001 Danfoss no acepta ninguna responsabilidad por posibles errores en sus catálogos, folletos u otros materiales impresos. Danfoss se reserva el derecho a alterar sus productos sin aviso previo. Esto se aplica también a los productos ya pedidos, suponiendo que tales alteraciones se puedan realizar sin que sean necesarios cambios subsiguientes en las especificaciones ya acordadas. Todas las marcas registradas de este material son propiedad de sus respectivos titulares. Danfoss y el logotipo de Danfoss son marcas registradas de Danfoss A/S. Todos los derechos reservados. DKRCE.PI.RL0.G5.ML/520H11075 Instruction sheet | ERC 213 | 57 ERC 213 , 3 . . 1 - y : , , . y : 16 : 2 .. ( 0,65 230 0,85 115). . y : , . y : , / . | 58 Instruction sheet | ERC 213 DKRCE.PI.RL0.G5.ML/520H11075 2 - : FACTORY RESET ( ) ( "FAC") : BACK () : PULL-DOWN () : TEMPERATURE SETPOINT/OK ( /OK) : MENU () : UP () : ON/OFF (/) : DOWN () : DEFROST () ( ) ( ) (°C °F) DKRCE.PI.RL0.G5.ML/520H11075 Instruction sheet | ERC 213 | 59 3 - y 1: y 2: 30 "<" BACK () 3 . "r12" OFF (). y 3: "o61" "o61". SET () . (, "AP0"). , UP/DOWN (/), SET () . . : AP0 AP6, , ( ) . App 0 . 1 . 2 . 3 . 4 . 5 . 6 ( ) . . (2 6 °C), . . (0 4 °C), . (-26 -20 °C), . . (0 4 °C), ( ) . (-26 -20 °C), ( ) ( ) | 60 Instruction sheet | ERC 213 DKRCE.PI.RL0.G5.ML/520H11075 y 4: "o06" "o06". SET () . (, "n10") , UP/DOWN (/) (n5=NTC 5 K, n10=NTC 10 K, Ptc=PTC, Pt1=Pt1000), SET () . : . DKRCE.PI.RL0.G5.ML/520H11075 Instruction sheet | ERC 213 | 61 | 62 4 - 1) SET (): 3 , ( ) SET 2) SET 3) 1-2-3-4-5-6 0 6-5-4-3-2-1 Instruction sheet | ERC 213 DKRCE.PI.RL0.G5.ML/520H11075 5 - "cFg" y SET () , . y "CFg" SET (), . "r12" ( ). y (r12=0) . y UP/DOWN (/) . y "o61" : - SET () "o61"; - UP/DOWN (/) (AP0 = ); - SET () , "o61". y , ( "o06" ) "cFg". DKRCE.PI.RL0.G5.ML/520H11075 Instruction sheet | ERC 213 | 63 6 - ( ) SET () UP/DOWN (/): ( ). SET (): . DEFROST (): 3 . DEFROST (): 3 . DEFROST (). | 64 Instruction sheet | ERC 213 DKRCE.PI.RL0.G5.ML/520H11075 PULL DOWN (): 3 . "Pud": 3 . PULL DOWN (). PULL DOWN (): 3 . , . . - 5 ( P76=). - , "LoC". - UP () DOWN () 3 . "unl" 3 . DKRCE.PI.RL0.G5.ML/520H11075 Instruction sheet | ERC 213 | 65 7 - , 115 . /230 . 50/60 , 0,7 4 : 2 , 1 / 1 NTC 5000 Ohm 25 °C, ( =3980 25/100 °C - EKS 211) NTC 10000 Ohm 25 °C, ( =3435 25/85 °C - EKS 221) PTC 990 Ohm 25 °C, ( EKS 111) Pt1000, ( AKS 11, AKS 12, AKS 21) NTC 10000 25 °C, =1,5 : -40 105 °C ( -40 221 °F) : +/-1 K -35 °C, +/-0.5 K -35 25 °C, +/-1 K 25 °C DO1: 16 A, 16 (16) A, EN 60730 10 FLA/60 LRA 230 , UL60730 16 FLA/72 LRA 115 , UL60730 DO2: 8 A, 2 FLA/12 LRA, UL60730 8 A, 2 (2 A), EN60730 DO3: 3 A, 2 FLA/12 LRA, UL60730 3 A, 2 (2 A), EN60730 | 66 Instruction sheet | ERC 213 DKRCE.PI.RL0.G5.ML/520H11075 - , 3 , , °C + °F -10 55 °C ( 14 131 °F), 90% -40 70 °C ( -40 158 °F), 90% : IP65 ( ) : IP00 II, D (UL94-V0) I UL (US & Canada) (UL 60730) ENEC (EN 60730) CQC CE (LVD & EMC Directive) EAC (GHOST) NSF ROHS2.0 HACCP EN134785 Class I, AKS 12 DKRCE.PI.RL0.G5.ML/520H11075 Instruction sheet | ERC 213 | 67 8 - . . 0 . 1 . 2 . 3 . 4 . 5 . 6 ( ) . . . . . . ( ) . ( ) ( ) . . . (2 6 °C) (0 4 °C) (-26 -20 °C) (0 4 °C) (-26 -20 °C) . . APP 1 DI1 DI2 Sair APP 2/3 DI1 DI2 Sair APP 4/5 DI1 DI2 S5 Sair 230 V AC DO1 DO2 DO3 230 V AC DO1 DO2 DO3 | 68 Instruction sheet | ERC 213 230 V AC DO1 DO2 DO3 DKRCE.PI.RL0.G5.ML/520H11075 9 - - ERC 213 . . cFg -1=, 0=, 1= r12 -1 1 AP0, AP1, AP2, AP3, AP4, AP5, AP6 o61 AP0 AP6 n5=NTC 5 K, n10=NTC 10 K, Ptc=PTC, Pt1=Pt1000 o06 n5 Pt1 / r-- r00 -100.0 200.0 r01 0.1 20.0 . r02 -100.0 200.0 . r03 -100.0 200.0 ( ) r04 -10.0 10.0 . . (°C/°F) r05 -C -F Sair ( ) r09 -20.0 20.0 -1=, 0=, 1= r12 -1 1 r13 -50.0 50.0 ( ) r40 -50.0 50.0 r96 0 960 r97 -100.0 200.0 : . . C/F K C/F C/F K K K K C/F . 0 . 1 AP0 n10 2.0 2.0 -35.0 50.0 0.0 -C 0.0 1 0.0 0.0 0 0.0 . 1 1 AP1 n10 4.0 2.0 2.0 6.0 0.0 -C 0.0 1 0.0 0.0 0 0.0 . 2 1 AP2 n10 2.0 2.0 0.0 4.0 0.0 -C 0.0 1 0.0 0.0 0 0.0 . 3 1 AP3 n10 -24.0 2.0 -26.0 -20.0 0.0 -C 0.0 1 0.0 0.0 0 0.0 . 4 1 AP4 n10 2.0 2.0 0.0 4.0 0.0 -C 0.0 1 0.0 0.0 0 0.0 . 5 1 AP5 n10 -24.0 2.0 -26.0 -20.0 0.0 -C 0.0 1 0.0 0.0 0 0.0 . 6 1 AP6 n10 2.0 2.0 -35.0 50.0 0.0 -C - - 0,0 - DKRCE.PI.RL0.G5.ML/520H11075 Instruction sheet | ERC 213 | 69 - ERC 213 . . A-- A03 0 240 A12 0 240 / / (/ ) A13 -100.0 200.0 A14 -100.0 200.0 DI1 ( DI1) A27 0 240 DI2 ( DI2) A28 0 240 A37 0 200 A54 0 200 A72 no yES A73 0 270 A74 0 270 A75 0 270 d-- no= , nAt=, EL=, gAS= d01 no gAS d02 0.0 50.0 d03 0 240 . d04 0 480 ( DI) d05 0 240.0 d06 0 60 d07 0 60 : . . C/F C/F C/F C/F V V V C/F . 0 . 30 60 8.0 -30.0 30 30 80 85 no 0 0 270 EL 6.0 8 30 0 0 0 . 1 45 90 10.0 0.0 30 30 80 85 no 0 0 270 nAt 6 45 0 0 0 . 2 30 60 8.0 -2.0 30 30 80 85 no 0 0 270 EL 8 15 0 0 0 . 3 30 60 -15.0 -30.0 30 30 80 85 no 0 0 270 EL 12 15 0 0 0 . 4 30 60 8.0 -2.0 30 30 80 85 no 0 0 270 EL 6.0 8 30 0 0 0 . 5 30 60 -15.0 -30.0 30 30 80 85 no 0 0 270 EL 6.0 12 30 0 0 0 . 6 30 60 8.0 -30.0 30 30 - no 0 0 270 EL 6.0 8 30 5 5 | 70 Instruction sheet | ERC 213 DKRCE.PI.RL0.G5.ML/520H11075 - ERC 213 . . d08 -50.0 0.0 d09 oFF on non=, Air=Sair ( ), d10 non dEF dEF=S5 ( ) 0 = d18 0 96 20,0= d19 0.0 20.0 0= d30 0 960 F-- FFc= , F01 FFc FPL FAo= , FPL= , 50,0= F04 -50.0 50.0 F07 0 15 F08 0 15.0 c-- C01 0 30 C02 0 30 C04 0 15 C70 no yES o-- o01 0 600 : . . C/F K C/F . 0 . -5.0 on non 0 20.0 0 FAo 50.0 2 2 0 2 0 yES 5 . 1 on non 0 0 FAo 2 2 0 2 0 yES 5 . 2 on non 0 0 FAo 2 2 0 2 0 yES 5 . 3 on non 0 0 FAo 2 2 0 2 0 yES 5 . 4 -5.0 on dEF 0 20.0 0 FAo 50.0 2 2 0 2 0 yES 5 . 5 -5.0 on dEF 0 20.0 0 FAo 50.0 2 2 0 2 0 yES 5 . 6 on non - FAo 2 2 0 2 1 yES 5 DKRCE.PI.RL0.G5.ML/520H11075 Instruction sheet | ERC 213 | 71 - ERC 213 . . DI1 oFF= , Sdc= , doo= , doA= , SCH= , o02 oFF Sc nig=/ , rFd= , EAL= , dEF=, Pud=, Sc= o03 0 247 o05 no 999 n5=NTC 5 K, n10=NTC 10 K, Ptc=PTC, Pt1=Pt1000 o06 n5 Pt1 0,1= 0,1 °C, 0,5= 0,5 °C, 1,0= 1,0 °C o15 0.1 1.0 1 (1 =100 ) o23 0 999 2 (1 =100 ) o24 0 999 3 (1 =100 ) o25 0 999 DI2 oFF= , Sdc= , doo= , doA= , SCH= , nig=/ , rFd= , EAL= , dEF=, Pud= o37 oFF Pud o61 AP0 AP6 ! o67 no yES : . . . 0 . oFF 0 no n10 0.1 0 0 0 oFF AP0 no . 1 oFF 0 no n10 0.1 0 0 0 oFF AP1 no . 2 oFF 0 no n10 0.1 0 0 0 oFF AP2 no . 3 oFF 0 no n10 0.1 0 0 0 oFF AP3 no . 4 oFF 0 no n10 0.1 0 0 0 oFF AP4 no . 5 oFF 0 no n10 0.1 0 0 0 oFF AP5 no . 6 oFF no 0.1 - oFF - | 72 Instruction sheet | ERC 213 DKRCE.PI.RL0.G5.ML/520H11075 - ERC 213 . . DO2 (dEF=defrost, ALA=alarm) o71 dEF ALA Air= , FrE= , -d-= "-d-" o91 Air -d- P-- DI1 nc= , no= P73 nc no DI2 nc= , no= P74 nc no 0= , 1= P75 0 1 P76 no yES u-- S0= / , S2=, , S3=, - , S4= , S10= =, S11= u00 S0 S32 / , S14= , S15= , S17= ( DI), S20= , S25= , S30= / , S32= , : . . . 0 . dEF -d- no no 0 no -- . 1 ALA -d- no no 0 no . 2 dEF -d- no no no . 3 dEF -d- no no no . 4 dEF -d- no no no . 5 dEF -d- no no no . 6 dEF -d- no no - DKRCE.PI.RL0.G5.ML/520H11075 Instruction sheet | ERC 213 | 73 - ERC 213 . . (Sair) u01 -100.0 200.0 u02 -100.0 200.0 (S5) u09 -100.0 200.0 DI1 u10 oFF on u13 oFF on DI2 u37 oFF on (Sc) U09 -100.0 200.0 u58 oFF on u59 oFF on u60 oFF on u63 oFF on u80 000 999 Sair E29 S5 E27 Sc E30 A01 A02 A99 AA1 A61 A04 A45 DI A15 : . . C/F C/F C/F C/F . 0 . --- --- --------------------- . 1 - . 2 - . 3 - . 4 . 5 . 6 | 74 Instruction sheet | ERC 213 DKRCE.PI.RL0.G5.ML/520H11075 , . : , . ( ) . 002566703-0001 Danfoss , . Danfoss . , , . . Danfoss Danfoss Danfoss A/S. . DKRCE.PI.RL0.G5.ML/520H11075 Instruction sheet | ERC 213 | 75 PORTUGUÊS O ERC 213 é um controlador de refrigeração multifunções com controle de temperatura e degelo, disponível com 3 relés. Este controlador foi projetado para atender às necessidades atuais das aplicações de refrigeração comercial. 1 - Destaques técnicos y Fácil utilização: Quatro botões, estrutura de menus simples, soluções de aplicação pré-instaladas para garantir o nível máximo de utilização. y Instalação simples: O relé de 16 A de alta performance permite a ligação direta de cargas pesadas sem a utilização de relés intermediários: compressores de até 2 HP, dependendo do fator de potência e eficiência do motor (acima de 0,65 para 230 V e acima de 0,85 para 115 V). Diversos tipos de sensores e conexões terminais de parafuso compatíveis garantem uma elevada flexibilidade de instalação. y Proteção da unidade: As funcionalidades de software especiais, como proteção do compressor contra oscilações na fonte de alimentação ou contra temperaturas elevadas de condensação, garantem o funcionamento seguro da unidade. y Eficiência energética: O degelo programado, o modo dia/noite e o controle do ventilador do dispositivo de evaporação garantem a eficiência energética. | 76 Instruction sheet | ERC 213 DKRCE.PI.RL0.G5.ML/520H11075 PORTUGUÊS 2 - Interface do usuário Função da tecla Pressionar prolongadamente na inicialização: RESET DE FÁBRICA (Aparece "FAC" no visor) Pressionar brevemente: VOLTAR Pressionar prolongadamente: PULL-DOWN Pressionar brevemente: SETPOINT DE TEMPERATURA/OK Pressionar prolongadamente: MENU Pressionar brevemente: PARA CIMA Pressionar prolongadamente: LIGAR/DESLIGAR Pressionar brevemente: PARA BAIXO Pressionar prolongadamente: DEGELO Ícones do visor Modo noturno (Economia de energia) Compressor em funcionamento Flashes no modo pull-down DKRCE.PI.RL0.G5.ML/520H11075 Ventilador em funcionamento Alarme ativo Instruction sheet | ERC 213 Degelo Unidade (°C ou °F) | 77 PORTUGUÊS 3 - Configuração rápida durante a inicialização y PASSO 1: Ligar a alimentação y PASSO 2: Selecionar o menu de configuração rápida Até 30 segundos depois de ligar a alimentação, pressione "<" VOLTAR durante 3 segundos. O interrutor principal "r12" DESLIGA automaticamente. y PASSO 3: Selecionar aplicação pré-instalada "o61" O visor mostra automaticamente o parâmetro de seleção da aplicação "o61". Pressione SET para selecionar a aplicação pré-instalada. O visor mostra o valor padrão (por ex., "AP0" intermitente). Escolha o tipo de aplicação pressionando PARA CIMA/PARA BAIXO e SET para confirmar. O controlador apresenta valores de parâmetro pré-definidos de acordo com a aplicação selecionada e oculta parâmetros não relevantes. Dica: Você pode facilmente mudar entre as aplicações AP0 e AP6, e assim selecionar a lista de parâmetros simplificada através do botão de seta superior. Aplicação Aplic 0 Aplic 1 Aplic 2 Aplic 3 Aplic 4 Aplic 5 Aplic 6 Descrição Não há aplicação predefinida Unidades de refrigeração ventiladas de temperatura média (2 a 6 °C), com degelo natural temporizado Unidades de refrigeração ventiladas de temperatura média (0 a 4 °C), com degelo elétrico temporizado Unidades de refrigeração ventiladas de baixa temperatura (-26 a -20 °C), com degelo elétrico temporizado Unidades de refrigeração ventiladas de temperatura média (0 a 4 °C), com degelo elétrico (por temperatura) Unidades de refrigeração ventiladas de baixa temperatura (-26 a -20 °C), com degelo elétrico (por temperatura) Não há aplicação predefinida com lista simplificada de parâmetros | 78 Instruction sheet | ERC 213 DKRCE.PI.RL0.G5.ML/520H11075 PORTUGUÊS Configuração rápida durante a inicialização y PASSO 4: Selecionar tipo de sensor "o06" O visor mostra automaticamente o parâmetro de seleção de sensor "o06". Pressione SET para selecionar o tipo de sensor. O visor mostra o valor padrão (por ex., "n10" intermitente). Escolha o tipo de sensor apertando PARA CIMA/PARA BAIXO (n5=NTC 5 K, n10=NTC 10 K, Ptc=PTC, Pt1=Pt1000) e pressione SET para confirmar. NOTA: Todos os sensores devem ser do mesmo tipo. DKRCE.PI.RL0.G5.ML/520H11075 Instruction sheet | ERC 213 | 79 | 80 PORTUGUÊS 4 - Estrutura do menu 1) Grupos de parâmetros SET: pressione por 3 segundos para acessar status, configuração e serviço Senha (se ativada) Entrada de status 2) Nome do parâmetro SET Configuração Interrutor principal SET Aplicação 3) Valor Aplicação 1-2-3-4-5-6 Aplicação 0 Tipo de sensor Ver lista de parâmetros Aplicação 6-5-4-3-2-1 Instruction sheet | ERC 213 DKRCE.PI.RL0.G5.ML/520H11075 Percorrer o grupo de parâmetros PORTUGUÊS 5 - Configuração rápida através do Menu "cFg" y Pressione SET durante três segundos para acessar os grupos de parâmetros. y Selecione o menu "CFg" e pressione SET para entrar. O primeiro menu "r12" (interrutor principal) aparece na tela. y DESLIGUE o interrutor principal (r12=0) para alterar a aplicação pré-instalada. y Pressione PARA CIMA/PARA BAIXO para percorrer a lista de parâmetros. y Configure o parâmetro "o61" para selecionar uma aplicação pré-instalada - Pressione SET para acessar o parâmetro "o61". - Pressione PARA CIMA/PARA BAIXO para selecionar uma aplicação (AP0= não existe uma aplicação selecionada). - Pressione SET para confirmar, aparece "o61" na tela. y Continue definindo os parâmetros seguintes ("tipo de sensor o06" ) no menu "cFg". DKRCE.PI.RL0.G5.ML/520H11075 Instruction sheet | ERC 213 | 81 PORTUGUÊS 6 - Operação básica Ajustar setpoint de temperatura (Pressionar brevemente) SET: ajusta o setpoint de temperatura. PARA CIMA/PARA BAIXO: altera o setpoint de temperatura (no modo de configuração, o setpoint fica intermitente). Iniciar degelo manual SET: salva o setpoint de temperatura. DEGELO: pressione por 3 segundos para iniciar degelo. DEGELO: pressione por 3 segundos para parar o degelo manual. O ícone de DEGELO aparece durante o degelo. | 82 Instruction sheet | ERC 213 DKRCE.PI.RL0.G5.ML/520H11075 PORTUGUÊS Operação Básica - 02 Iniciar pull-down PULL-DOWN: pressione por 3 segundos para iniciar o pull-down. <Pud>: é o que aparece no visor por 3 segundos para indicar o pull-down. O ícone de PULL-DOWN fica piscando durante o pull-down. PULL-DOWN: pressione por 3 segundos para encerrar o pull-down. Ver um alarme ativo Os códigos de temperatura e alarme ficam piscando até que o alarme seja resolvido. Aparece o ícone da campainha. Desbloquear teclado - Após 5 minutos sem atividade, o teclado é bloqueado (se P76=sim). - Enquanto o teclado estiver bloqueado, qualquer botão pressionado mostrará <<LoC>> no visor. - Pressione simultaneamente os botões PARA CIMA e PARA BAIXO por 3 segundos para desbloquear o teclado. O visor mostra <<unl>> por 3 segundos. DKRCE.PI.RL0.G5.ML/520H11075 Instruction sheet | ERC 213 | 83 PORTUGUÊS 7 - Dados técnicos CARACTERÍSTICAS Fonte de alimentação Potência nominal Entradas Tipos de sensor permitidos Sensores incluídos na Solução Kit Precisão DESCRIÇÃO 115 VCA / 230 VCA 50/60 Hz, fonte de alimentação de baixa tensão isolada galvanicamente Inferior a 0.7 W 4 entradas: 2 analógica, 1 analógica/digital e 1 digital NTC 5000 Ohm a 25 °C, (Beta value=3980 a 25/100 °C - ex. EKS 211) NTC 10000 Ohm a 25 °C, (Beta value=3435 a 25/85 °C - ex. EKS 221) PTC 990 Ohm a 25 °C, (ex. EKS 111) Pt1000, (ex. AKS 11, AKS 12, AKS 21) NTC 10000 Ohm a 25 °C, cabo de 1.5 m Faixa de medição: -40 a 105 °C (-40 a 221 °F) Precisão do controlador: +/- 1 K abaixo de -35 °C, +/- 0.5 K entre -35 e 25 °C, +/- 1 K acima de 25 °C | 84 Instruction sheet | ERC 213 DKRCE.PI.RL0.G5.ML/520H11075 CARACTERÍSTICAS Saída Visor Condições de funcionamento Condições de armazenamento Proteção Ambiente Resistência ao calor e ao fogo Categoria EMC Aprovações DKRCE.PI.RL0.G5.ML/520H11075 DESCRIÇÃO Relé do compressor DO1: 16 A, 16 (16) A, EN 60730 10 FLA/60 LRA at 230 V, UL60730 16 FLA/72 LRA at 115 V, UL60730 Relé de degelo DO2: 8 A, 2 FLA/12 LRA, UL60730 8 A, 2 (2 A), EN60730 Relé do ventilador DO3: 3 A, 2 FLA/12 LRA, UL60730 3 A, 2 (2 A), EN60730 Visor LED, 3 dígitos, ponto decimal e ícones com várias funcionalidades, escala °C + °F -10 55 °C (14 131 °F), 90% Hr -40 70 °C (-40 158 °F), 90% Hr Parte frontal: IP65 (gaxeta integrada). Parte posterior: IP00 Grau de poluição II, não condensante Categoria D (UL94-V0) Categoria I Homologação UL (US & Canada) (UL 60730) ENEC (EN 60730) CQC CE (LVD & EMC Directive) EAC (GHOST) NSF ROHS2.0 Monitoramento de temperatura HACCP de acordo com a norma EN134785 Classe I, quando utilizado com o sensor AKS12 Instruction sheet | ERC 213 | 85 PORTUGUÊS PORTUGUÊS 8 - Configuração de aplicações pré-definidas Aplic. Aplic. 0 Aplic. 1 Aplic. 2 Aplic. 3 Aplic. 4 Aplic. 5 Aplic. 6 Modo resfriamento resfriamento resfriamento resfriamento resfriamento resfriamento resfriamento Descrição Não há aplicação predefinida Unidades de refrigeração ventiladas de temperatura média com degelo natural temporizado Unidades de refrigeração ventiladas de temperatura média com degelo elétrico temporizado Unidades de refrigeração ventiladas de baixa temperatura com degelo elétrico temporizado Unidades de refrigeração ventiladas de temperatura média com degelo elétrico (por temperatura) Unidades de refrigeração ventiladas de baixa temperatura com degelo elétrico (por temperatura) Não há aplicação predefinida com lista simplificada de parâmetros Temp. (2 6 °C) (0 4 °C) (-26 -20 °C) (0 4 °C) (-26 -20 °C) Tipo deg. Natural Elétric. Elétric. Elétric. Elétric. Fim deg. Tempo Tempo Tempo Temp. Temp. APP 1 DI1 DI2 Sair APP 2/3 DI1 DI2 Sair APP 4/5 DI1 DI2 S5 Sair 230 V AC DO1 DO2 DO3 | 86 230 V AC DO1 DO2 DO3 Instruction sheet | ERC 213 230 V AC DO1 DO2 DO3 DKRCE.PI.RL0.G5.ML/520H11075 PORTUGUÊS 9 - Lista de parâmetros Nome do parâmetro - ERC 213 Código Configuração cFg Interrutor principal -1=serviço, 0=DESLIGADO,1=LIGADO r12 Aplicações pré-definidas AP0, AP1, AP2, AP3, AP4, AP5, AP6 o61 Seleção do tipo de sensor n5=NTC 5 K, n10=NTC 10 K, o06 Ptc=PTC, Pt1=Pt1000 Referência/Termostato r-- Setpoint de temperatura r00 Diferencial r01 Limite mín. de setpoint r02 Limite máx. de setpoint r03 Offset do display (valor de correção na temperatura apresentada) r04 Unidade do display (°C/°F) r05 Calibração de temperatura do ar (Sair) (offset de calibração da temperatura do ar) r09 Interrutor principal -1=serviço, 0=DESLIGADO,1=LIGADO r12 Definição no modo noturno (offset de temperatura durante o modo r13 noturno) Offset de temperatura para o deslocamento referencial do r40 termostato Duração do pull-down r96 Temperatura limite do pull-down r97 Nota: os parâmetros ocultados estão em cinza Mín. -1 AP0 n5 -100.0 0.1 -100.0 -100.0 -10.0 -C -20.0 -1 -50.0 -50.0 0 -100.0 Máx. 1 AP6 Pt1 200.0 20.0 200.0 200.0 10.0 -F 20.0 1 50.0 50.0 960 200.0 Unidade C/F K C/F C/F K K K K min C/F App. 0 (Def.) App. 1 App. 2 App. 3 App. 4 App. 5 App. 6 1 1 1 1 1 1 1 AP0 AP1 AP2 AP3 AP4 AP5 AP6 n10 n10 n10 n10 n10 n10 n10 2.0 4.0 2.0 2.0 -35.0 2.0 50.0 6.0 0.0 0.0 -C -C 0.0 0.0 1 1 0.0 0.0 2.0 -24.0 2.0 -24.0 2.0 2.0 2.0 2.0 2.0 2.0 0.0 -26.0 0.0 -26.0 -35.0 4.0 -20.0 4.0 -20.0 50.0 0.0 0.0 0.0 0.0 0.0 -C -C -C -C -C 0.0 0.0 0.0 0.0 - 1 1 1 1 - 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 - 0 0 0 0 0 0 - 0.0 0.0 0.0 0.0 0.0 0.0 - DKRCE.PI.RL0.G5.ML/520H11075 Instruction sheet | ERC 213 | 87 PORTUGUÊS Nome do parâmetro - ERC 213 Código Alarme A-- Delay para o alarme de temperatura em condições normais A03 Delay para o alarme de temperatura durante pull-down/start-up/degelo A12 Limite de alarme de alta temperatura (vitrine/câmara) A13 Limite de alarme de baixa temperatura A14 Delay DI1 (tempo de delay para função DI1 selecionada) A27 Delay DI2 (tempo de delay para função DI2 selecionada) A28 Limite superior de alarme do condensador A37 Limite superior de bloqueio do condensador A54 Ativação da proteção de tensão A72 Tensão de transição mínima A73 Tensão de desconexão mínima A74 Tensão máxima A75 Degelo d-- Método de degelo no=sem degelo, nAt=natural, d01 EL=elétrico, gAS=gás quente Temperatura final do degelo d02 Faixa de degelo d03 Tempo máx. de degelo d04 Delay de degelo na inicialização (ou sinal DI) d05 Delay de gotejamento d06 Delay do ventilador após degelo d07 Temperatura de arranque do ventilador após degelo d08 Ventilador durante o degelo d09 Nota: os parâmetros ocultados estão em cinza Mín. 0 0 -100.0 -100.0 0 0 0 0 no 0 0 0 no 0.0 0 0 0 0 0 -50.0 oFF Máx. Unidade 240 min 240 min 200.0 C/F 200.0 C/F 240 min 240 min 200 C/F 200 C/F yES 270 V 270 V 270 V gAS 50.0 C/F 240 horas 480 min 240.0 min 60 min 60 min 0.0 C/F on App. 0 (Def.) App. 1 App. 2 App. 3 App. 4 App. 5 App. 6 30 45 30 30 30 30 30 60 90 60 60 60 60 60 8.0 10.0 -30.0 0.0 30 30 8.0 -15.0 -2.0 -30.0 30 30 8.0 -15.0 8.0 -2.0 -30.0 -30.0 30 30 30 30 30 30 30 30 30 30 80 80 80 80 80 80 - 85 85 85 85 85 85 - no no no no no no no 0 0 0 0 0 0 0 0 0 0 0 0 0 0 270 270 270 270 270 270 270 EL nAt EL EL EL EL EL 6.0 - - - 6.0 6.0 6.0 8 6 8 12 8 12 8 30 45 15 15 30 30 30 0 0 0 0 0 0 - 0 0 0 0 0 0 5 0 0 0 0 0 0 5 -5.0 - - - -5.0 -5.0 - on on on on on on on | 88 Instruction sheet | ERC 213 DKRCE.PI.RL0.G5.ML/520H11075 PORTUGUÊS Nome do parâmetro - ERC 213 Código Mín. Máx. Unidade App. 0 (Def.) App. 1 App. 2 App. 3 App. 4 App. 5 App. 6 Configuração do sensor de parada de degelo non=tempo, Air=Sair (temperatura do ar), d10 dEF=S5 (sensor de degelo) non dEF non non non non dEF dEF non Tempo de funcionamento do compressor para iniciar o degelo 0=DESLIGADO d18 0 96 horas 0 0 0 0 0 0 - Degelo on demand 20.0=DESLIGADO d19 0.0 20.0 K 20.0 - - - 20.0 20.0 - Delay para degelo após pulldown 0=DESLIGADO d30 0 960 min 0 0 0 0 0 0 - Controle do ventilador F-- Ventilador na disjunção do compressor FFc=ventilador segue compressor, FAo=ventilador sempre LIGADO, FPL= ventilador pulsante F01 FFc FPL FAo FAo FAo FAo FAo FAo FAo Temperatura de parada do evaporador 50,0=DESLIGADO F04 -50.0 50.0 C/F 50.0 - - - 50.0 50.0 - Ciclo de ventilador LIGADO F07 0 15 min 2 2 2 2 2 2 2 Ciclo de ventilador DESLIGADO F08 0 15.0 min 2 2 2 2 2 2 2 Compressor c-- Tempo mín. de compressor ligado C01 0 30 min 0 0 0 0 0 0 0 Tempo mín. do compressor DESLIGADO C02 0 30 min 2 2 2 2 2 2 2 Delay ao DESLIGAR o compressor na abertura da porta C04 0 15 min 0 0 0 0 0 0 1 Seleção de passagem por zero C70 no yES yES yES yES yES yES yES yES Nota: os parâmetros ocultados estão em cinza DKRCE.PI.RL0.G5.ML/520H11075 Instruction sheet | ERC 213 | 89 PORTUGUÊS Nome do parâmetro - ERC 213 Código Mín. Outros o-- Delay de saídas no start-up o01 0 Configuração DI1 oFF=não utilizado, Sdc=status de saída do visor, doo=alarme da porta com recomeço, doA=alarme da porta sem recomeço, SCH=interrutor principal, nig=modo dia/noite, o02 oFF rFd=deslocamento de referência, EAL=alarme externo, dEF=degelo, Pud=pull-down, Sc= sensor do condensador Endereço de série o03 0 Senha o05 no Seleção de tipo de sensor n5=NTC 5 K, n10=NTC 10 K, Ptc=PTC, Pt1=Pt1000 o06 n5 Resolução do visor 0.1=passos de 0.1 °C, 0,5=passos de 0.5 °C, 1.0=passos de 1.0 °C o15 0.1 Contador relé 1 (1 contagem=100 ciclos de operação) o23 0 Contador relé 2 (1 contagem=100 ciclos de operação) o24 0 Contador relé 3 (1 contagem=100 ciclos de operação) o25 0 Configuração DI2 oFF=não utilizado, Sdc=status de saída do visor, doo=alarme da porta com recomeço, doA=alarme da porta sem recomeço, o37 oFF SCH=interrutor principal, nig=modo dia/noite, rFd=deslocamento de referência, EAL=alarme externo, dEF=degelo, Pud=pull-down Aplicações pré-definidas o61 AP0 Nota: os parâmetros ocultados estão em cinza Máx. Unidade App. 0 (Def.) App. 1 App. 2 App. 3 App. 4 App. 5 App. 6 600 min 5 5 5 5 5 5 5 Sc oFF oFF oFF oFF oFF oFF oFF 247 0 0 0 0 0 0 - 999 no no no no no no no Pt1 n10 n10 n10 n10 n10 n10 - 1.0 0.1 0.1 0.1 0.1 0.1 0.1 0.1 999 0 0 0 0 0 0 - 999 0 0 0 0 0 0 - 999 0 0 0 0 0 0 - Pud oFF oFF oFF oFF oFF oFF oFF AP6 AP0 AP1 AP2 AP3 AP4 AP5 - | 90 Instruction sheet | ERC 213 DKRCE.PI.RL0.G5.ML/520H11075 PORTUGUÊS Nome do parâmetro - ERC 213 Código Mín. Máx. Unidade App. 0 (Def.) App. 1 App. 2 App. 3 App. 4 App. 5 App. 6 Salvar pré-definições AVISO: As definições de fábrica anteriores serão substituídas o67 no yES no no no no no no - Configuração DO2 dEF=degelo, ALA=alarme o71 dEF ALA dEF ALA dEF dEF dEF dEF dEF Display no degelo Air=temperatura de ar real, FrE=temperatura congelada, -d-="-d-" aparece na tela o91 Air -d- -d- -d- -d- -d- -d- -d- -d- Polaridade P-- Polaridade de entrada DI1 nc=normalmente fechado, no=normalmente aberto P73 nc no no no no no no no no Polaridade de entrada DI2 nc=normalmente fechado, no=normalmente aberto P74 nc no no no no no no no no Inverter relé de alarme 0=normal, 1=inverter ação de relé P75 0 1 0 0 - - - - - Ativar bloqueio do teclado P76 no yES no no no no no no - Leituras u-- Status do controlador S0=Resfriamento LIGADO/Aquecimento LIGADO, S2=aguardar que o tempo do compressor LIGADO decorra, S3=aguardar que o tempo do compressor DESLIGADO decorratempo de reinício, S4=delay de gotejamento DESLIGADO após degelo, S10=resfriamento parado pelo interrutor principal=DESLIGADO, u00 S0 S32 -- S11=resfriamento parado pelo termostato/ aquecimento DESLIGADO, S14=status de degelo, S15=status de delay do ventilador após degelo, S17=porta aberta (entrada DI), S20=resfriamento de emergência, S25=controle manual de saídas, S30=Suspensão/ciclo contínuo, S32=delay de saídas no arranque Nota: os parâmetros ocultados estão em cinza DKRCE.PI.RL0.G5.ML/520H11075 Instruction sheet | ERC 213 | 91 PORTUGUÊS Nome do parâmetro - ERC 213 Temperatura do ar (Sair) Ler a referência de regulamentação existente Temperatura de degelo (S5) Entrada DI1 Status de operação no modo noturno Entrada DI2 Temperatura do condensador (Sc) Status do relé do compressor Status do relé do ventilador Status do relé de degelo Status do relé de iluminação Leitura da versão de firmware Status do alarme Erro no sensor da temperatura de ar Sair Erro no sensor de degelo S5 Erro no sensor do condensador Sc Alarme de temperatura elevada Alarme de temperatura baixa Alarme de alta tensão Alarme de baixa tensão Alarme do condensador Alarme da porta Alarme em modo de standby Alarme externo DI Nota: os parâmetros ocultados estão em cinza Código u01 u02 u09 u10 u13 u37 U09 u58 u59 u60 u63 u80 Mín. -100.0 -100.0 -100.0 oFF oFF oFF -100.0 oFF oFF oFF oFF 000 Máx. Unidade 200.0 C/F 200.0 C/F 200.0 C/F on on on 200.0 C/F on on on on 999 App. 0 (Def.) App. 1 App. 2 App. 3 App. 4 App. 5 App. 6 --- --- --- - - - --- --- --- --- --- --- --- --- --- E29 E27 E30 A01 A02 A99 AA1 A61 A04 A45 A15 | 92 Instruction sheet | ERC 213 DKRCE.PI.RL0.G5.ML/520H11075 PORTUGUÊS Normas de segurança Verifique se a fonte de alimentação está correta antes de ligar o instrumento. Não exponha à água nem à umidade: Utilize o controlador apenas dentro dos limites de funcionamento, evitando alterações súbitas da temperatura com elevada umidade atmosférica, de forma a evitar a formação de condensação. Eliminação do produto O dispositivo (ou o produto) deve ser eliminado de acordo com a legislação local relativa à eliminação de resíduos. Registo de design na UE 002566703-0001 A Danfoss não se responsabiliza por possíveis erros em catálogos, brochuras ou outros materiais impressos. A Danfoss se reserva o direito de alterar os seus produtos sem aviso prévio. Isto se aplica a produtos já encomendados desde que essas alterações não afetem especificações já acordadas. Todas as marcas comerciais nestes materiais são propriedade das respectivas empresas. Danfoss e o logotipo Danfoss são marcas comerciais da Danfoss A/S. Todos os direitos reservados. DKRCE.PI.RL0.G5.ML/520H11075 Instruction sheet | ERC 213 | 93 POLSKI ERC 213 to 3-przekanikowy inteligentny sterownik sterujcy temperatur i odtajaniem urzdzenia chlodniczego. Sterownik spelnienia wymagania dzisiejszych komercyjnych ukladów chlodniczych. 1. Glówne zalety techniczne y Latwo obslugi: Cztery przyciski, prosta struktura menu i predefiniowane aplikacje zapewniaj latw obslug. y Prosta instalacja: Przekanik 16 A umoliwia bezporednie podlczanie duych obcie bez porednich przekaników: sprarka o mocy do 1,5 kW w zalenoci od jej wspólczynnika mocy i sprawnoci silnika (powyej 0,65 dla 230 V i powyej 0,85 dla 115 V). Szeroka gama rodzajów kompatybilnych czujników oraz przylcza z zaciskami rubowymi zapewniaj du elastyczno instalacji. Ochrona urzdzenia: Specjalne funkcje oprogramowania, takie jak zabezpieczenie sprarki przed wahaniami napicia zasilania lub zabezpieczenie przed wysok temperatur skraplania, zapewniaj bezpieczn prac urzdzenia. y Energooszczdno: Odtajanie wg potrzeb, tryb dzienny/nocny i inteligentne sterowanie prac wentylatora chlodnicy zapewniaj oszczdno energii. | 94 Instruction sheet | ERC 213 DKRCE.PI.RL0.G5.ML/520H11075 POLSKI 2. Interfejs uytkownika Najwaniejsze funkcje Dlugie nacinicie podczas wlczania zasilania: RESETOWANIE DO USTAWIE FABRYCZNYCH (wywietlany jest komunikat "FAC") Krótkie nacinicie: WSTECZ Dlugie nacinicie: WYCHLADZANIE Krótkie nacinicie: NASTAWA TEMPERATURY/OK Dlugie nacinicie: MENU Krótkie nacinicie: GÓRA Dlugie nacinicie: WL./WYL. Krótkie nacinicie: DÓL Dlugie nacinicie: ODTAJANIE Ikony wywietlacza Tryb nocny (energooszczdny) Sprarka pracuje Miga w trybie wychladzania DKRCE.PI.RL0.G5.ML/520H11075 Wentylator pracuje Aktywny alarm Instruction sheet | ERC 213 Odtajanie Jednostka (°C lub °F) | 95 POLSKI 3. Szybka konfiguracja po wlczeniu zasilania y KROK 1: Wlcz zasilanie. y KROK 2: Wybierz menu szybkiej konfiguracji. W cigu 30 sekund po wlczeniu zasilania nacinij i przytrzymaj przez 3 sekundy przycisk "<" (WSTECZ). Wylcznik glówny "r12" jest automatycznie ustawiany na WYL. y KROK 3: Wybierz predefiniowan aplikacj "o61". Wywietlacz automatycznie pokazuje parametr wyboru aplikacji "o61". Nacinij przycisk SET (Ustawianie), aby wybra predefiniowan aplikacj. Na wywietlaczu pokazana jest warto domylna (np. migajcy komunikat "AP0"). Wybierz typ aplikacji przyciskami GÓRA/DÓL i nacinij przycisk SET (Ustawianie), aby potwierdzi. Sterownik ustawia wlaciwe dla wybranej aplikacji wartoci parametrów i ukrywa parametry niezwizane z t aplikacj. Wskazówka: Mona latwo przej z AP0 do AP6,czyli wybra uproszczon list parametrów naciskajc przycisk GÓRA (przewijana lista) Aplikacja Aplikacja 0 Aplikacja 1 Aplikacja 2 Aplikacja 3 Aplikacja 4 Aplikacja 5 Aplikacja 6 Opis Brak (brak zaprogramowanej aplikacji) MT redniotemperaturowe (od 2 do 6°C), urzdzenia chlodnicze, wentylowane z uruchamianym co okrelony czas odtajaniem naturalnym MT redniotemperaturowe (od 0 do 4°C), urzdzenia chlodnicze, wentylowane z uruchamianym co okrelony czas odtajaniem elektrycznym LT niskotemperaturowe (od -26 do -20°C), urzdzenia chlodnicze, wentylowane z uruchamianym co okrelony czas odtajaniem elektrycznym MT redniotemperaturowe (od 0 do 4°C), urzdzenia chlodnicze, wentylowane z odtajaniem elektrycznym (z temperatur koca odtajania) LT niskotemperaturowe (od -26 do -20°C), urzdzenia chlodnicze, wentylowane z odtajaniem elektrycznym (z temperatur koca odtajania) Brak (nie ustawiona aplikacja) z uproszczonej listy parametrów | 96 Instruction sheet | ERC 213 DKRCE.PI.RL0.G5.ML/520H11075 POLSKI Szybka konfiguracja po wlczeniu zasilania y KROK 4: Wybierz typ czujnika "o06". Wywietlacz automatycznie pokazuje parametr wyboru czujnika "o06". Nacinij przycisk SET (Ustawianie), aby wybra typ czujnika. Na wywietlaczu pokazana jest warto domylna (np. migajcy komunikat "N10"). Wybierz typ czujnika przyciskami GÓRA/DÓL (N5 = NTC 5K, n10 = NTC 10K, Ptc = PTC, Pt1 = Pt1000) i nacinij przycisk SET (Ustawianie), aby potwierdzi. UWAGA: Wszystkie czujniki musz by tego samego typu. DKRCE.PI.RL0.G5.ML/520H11075 Instruction sheet | ERC 213 | 97 | 98 4. Struktura menu 1) Grupy parametrów POLSKI SET (Ustawianie): nacisnij przycisk i przytrzymaj go przez 3 sekundy, aby uzyskac dostep do stanu, konfiguracji i serwisu. Haslo (jesli jest ustawione) Stan: wejscie SET 2) Nazwa parametru Konfiguracja Wylacznik glówny SET Aplikacja 3) Wartosc Aplikacja 1-2-3-4-5-6 Aplikacja 0 Typ czujnika Przewijanie listy z nazwami parametrów Aplikacja 6-5-4-3-2-1 Instruction sheet | ERC 213 DKRCE.PI.RL0.G5.ML/520H11075 Przewijanie listy z grupami parametrów POLSKI 5. Szybka konfiguracja za porednictwem menu "cFg" y Nacinij i przytrzymaj przez trzy sekundy przycisk SET (Ustawianie), aby uzyska dostp do grup parametrów. y Wybierz menu "CFg" i nacinij przycisk SET (Ustawianie), aby wej. Wywietlane jest pierwsze menu "r12" (wylcznik glówny). y Ustaw wylcznik glówny w poloeniu WYL. (r12 = 0), aby zmieni predefiniowan aplikacj. y Naciskaj przyciski GÓRA/DÓL, aby przewija list parametrów. y Skonfiguruj parametr "o61", aby wybra predefiniowan aplikacj. - Nacinij przycisk SET (Ustawianie), aby uzyska dostp do parametru "o61". - Naciskaj przyciski GÓRA/DÓL, aby wybra aplikacj (AP0 = nie wybrano aplikacji). - Nacinij przycisk SET (Ustawianie), aby potwierdzi -- wywietlany jest parametr "o61". y Kontynuuj ustawianie nastpnych parametrów (typ czujnika "o06") w menu "cFg". DKRCE.PI.RL0.G5.ML/520H11075 Instruction sheet | ERC 213 | 99 POLSKI 6. Obsluga podstawowa Modykowanie nastawy temperatury SET (Ustawianie) (krótkie nacisniecie): rozpocznij modyfikowanie nastawy temperatury GÓRA/DÓL: zmien nastawe temperatury (w trybie ustawiania nastawa miga). SET (Ustawianie): zapisz nastawe temperatury. Inicjowanie recznego odtajania ODTAJANIE: nacisnij przycisk i przytrzymaj go przez 3 sekundy, aby rozpoczac odtajanie ODTAJANIE: nacisnij przycisk i przytrzymaj go przez 3 sekundy, aby zatrzymac reczne odtajanie. Podczas odtajania wyswietlana jest ikona ODTAJANIA. | 100 Instruction sheet | ERC 213 DKRCE.PI.RL0.G5.ML/520H11075 POLSKI Obsluga podstawowa -- 02 Inicjowanie wychladzania WYCHLADZANIE: nacisnij przycisk i przytrzymaj go przez 3 sekundy, aby rozpoczac wychladzanie. Przez 3 sekundy wyswietlany jest komunikat ,,Pud" sygnalizujacy wychladzanie. Podczas wychladzania miga ikona WYCHLADZANIA. WYCHLADZANIE: nacisnij przycisk i przytrzymaj go przez 3 sekundy, aby zatrzymac wychladzanie. Wyswietlanie aktywnego alarmu Wyswietlane sa na przemian temperatura i kody alarmów, az do usuniecia przyczyn alarmów. Wyswietlana jest ikona dzwonka alarmu. Odblokowywanie klawiatury - Po 5 minutach bezczynnosci blokowana jest klawiatura (jesli wartosc parametru P76 = yes (tak)). - Gdy klawiatura jest zablokowana, nacisniecie dowolnego przycisku powoduje wyswietlenie na wyswietlaczu komunikatu ,,LOC". - Aby odblokowac klawiature, nacisnij jednoczesnie przyciski GÓRA i DÓL i przytrzymaj je przez 3 sekundy. Przez 3 sekundy wyswietlany jest komunikat ,,unl". DKRCE.PI.RL0.G5.ML/520H11075 Instruction sheet | ERC 213 | 101 POLSKI 7. Dane techniczne PARAMETRY Zasilanie Moc znamionowa Wejcia Dozwolone typy czujników Czujniki w zestawie Rozwizanie Dokladno Wyjcia OPIS 115 V AC / 230 V AC, 50/60 Hz galwanicznie odizolowane od niskiego napicia Mniejsza ni 0,7 W 4 wejcia: 2 analogowe, 1 analogowo-cyfrowe i 1 cyfrowe NTC 5000 Ohm a 25 °C, (Beta value=3980 a 25/100 °C - przyklad EKS 211) NTC 10000 Ohm a 25 °C, (Beta value=3435 a 25/85 °C - przyklad EKS 221) PTC 990 Ohm a 25 °C, (ex. EKS 111) Pt1000, (przyklad AKS 11, AKS 12, AKS 21) NTC 10000 Ohm przy 25 0C, dlugo kabla=1.5m Zakres pomiarowy: Od -40 do 105 °C (od -40 do 221°F) Dokladno sterownika: +/-1 K poniej -35 °C, +/-0.5 K od -35 do 25 °C, +/-1 K powyej 25 °C DO1 -- przekanik sprarki: 16 A, 16 (16) A, EN 60730 10 FLA/60 LRA przy 230 V, UL60730 16 FLA/72 LRA przy 115 V, UL60730 DO2 -- przekanik odtajania: 8 A, 2 FLA/12 LRA, UL60730 8 A, 2 (2 A), EN60730 DO3 -- przekanik wentylatora: 3 A, 2 FLA/12 LRA, UL60730 3 A, 2 (2 A), EN60730 | 102 Instruction sheet | ERC 213 DKRCE.PI.RL0.G5.ML/520H11075 POLSKI PARAMETRY Wywietlacz Warunki pracy Warunki przechowywania Ochrona Wplyw na rodowisko Odporno na cieplo i ogie Kategoria EMC Certyfikaty OPIS 3-cyfrowy wywietlacz LED z separatorem dziesitnym i ikonami wielofunkcyjnymi oraz skalami °C i °F Od -10 do 55 °C (od 14 do 131 °F), wilgotno wzgldna 90% Od -40 do 70 °C (od -40 do 158 °F), wilgotno wzgldna 90% Przód: IP65 (zintegrowana uszczelka), Tyl: IP00 Stopie zanieczyszczenia II, bez kondensacji Kategoria D (UL94-V0) Kategoria I UL Dopuszczenia (US & Canada) (UL 60730) ENEC (EN 60730) CQC CE (LVD & EMC Directive) EAC (GHOST) NSF ROHS2.0 HACCP monitoring temperatury zgodny z EN134785 klasa I, gdy zastosowany z czujnikiem AKS 12 DKRCE.PI.RL0.G5.ML/520H11075 Instruction sheet | ERC 213 | 103 POLSKI 8. Konfiguracja predefiniowanych aplikacji Aplikacja Tryb Aplik. 0 chlodzenie Aplik. 1 chlodzenie Aplik. 2 chlodzenie Aplik. 3 chlodzenie Aplik. 4 chlodzenie Aplik. 5 chlodzenie Aplik. 6 chlodzenie Opis Tempera- Typ Zakoc. tura odtajania odtajania Brak (brak zaprogramowanej aplikacji) MT redniotemperaturowe, urzdzenia chlodnicze, wentylowane z uruchamianym co okrelony czas odtajaniem naturalnym (2 6 °C) Naturalne Czasowe MT redniotemperaturowe, urzdzenia chlodnicze, wentylowane z uruchamianym co okrelony czas odtajaniem elektrycznym (0 4 °C) Elektryczne Czasowe LT niskotemperaturowe, urzdzenia chlodnicze, wentylowane z uruchamianym co okrelony czas odtajaniem elektrycznym (-26 -20 °C) Elektryczne Czasowe MT redniotemperaturowe, urzdzenia chlodnicze, wentylowane z odtajaniem elektrycznym (z temperatur koca odtajania) (0 4 °C) Elektryczne Temperaturowe LT niskotemperaturowe, urzdzenia chlodnicze, wentylowane z odtajaniem elektrycznym (z temperatur koca odtajania) (-26 -20 °C) Elektryczne Temperaturowe Brak (nie ustawiona aplikacja) z uproszczonej listy parametrów APP 1 DI1 DI2 Sair APP 2/3 DI1 DI2 Sair APP 4/5 DI1 DI2 S5 Sair 230 V AC DO1 DO3 DO4 | 104 230 V AC DO1 DO2 DO3 DO4 Instruction sheet | ERC 213 230 V AC DO1 DO2 DO3 DO4 DKRCE.PI.RL0.G5.ML/520H11075 POLSKI 9. Lista parametrów Nazwa parametru Kod Konfiguracja cFg Wylcznik glówny -1 = serwis, 0 = WYL., 1 = WL. r12 Predefiniowane aplikacje AP0, AP1, AP2, AP3, AP4, AP5, AP6 o61 Wybór typu czujnika n5=NTC 5 K, n10=NTC 10 K, o06 Ptc=PTC, Pt1=Pt1000 Reference/thermostat r-- Nastawa temperatury r00 Rónica zalcze r01 Minimalne ograniczenie nastawy r02 Maksymalne ograniczenie nastawy r03 Korekcja wywietlanej temperatury (warto korekcji wywietlanej temperatury) r04 Wywietlana jednostka (°C/ °F) r05 Kalibracja czujnika Sair (kompensacja uywana do kalibracji r09 czujnika temperatury powietrza) Wylcznik glówny -1=serwis, 0=WYL., 1=WL. r12 Nocne obnienie temperatury (przesunicie nastawy temperatury w r13 trybie nocnym) Przesunicie temperatury odniesienia termostatu r40 Czas trwania wychladzania r96 Graniczna temperatura wychladzania r97 Alarm A-- Opónienie alarmu temperatury podczas normalnych warunków pracy A03 Uwaga: ukryte parametry s wyszarzone Minimalna maksymalna Jednost. Apli. 0 (dom.) Apli. 1 Apli. 2 Apli. 3 Apli. 4 Apli. 5 Apli. 6 -1 1 AP0 AP6 n5 Pt1 1 1 1 1 1 1 1 AP0 AP1 AP2 AP3 AP4 AP5 AP6 n10 n10 n10 n10 n10 n10 n10 -100.0 200.0 C/F 2.0 4.0 0.1 20.0 K 2.0 2.0 -100.0 200.0 C/F -35.0 2.0 -100.0 200.0 C/F 50.0 6.0 -10.0 10.0 K 0.0 0.0 -C -F -C -C -20.0 20.0 K 0.0 0.0 -1 1 1 1 -50.0 50.0 K 0.0 0.0 -50.0 50.0 K 0.0 0.0 0 960 min 0 0 -100.0 200.0 C/F 0.0 0.0 0 240 min 30 45 2.0 -24.0 2.0 -24.0 2.0 2.0 2.0 2.0 2.0 2.0 0.0 -26.0 0.0 -26.0 -35.0 4.0 -20.0 4.0 -20.0 50.0 0.0 0.0 0.0 0.0 0.0 -C -C -C -C -C 0.0 0.0 0.0 0.0 - 1 1 1 1 - 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 - 0 0 0 0 - 0.0 0.0 0.0 0.0 - 30 30 30 30 30 DKRCE.PI.RL0.G5.ML/520H11075 Instruction sheet | ERC 213 | 105 POLSKI Nazwa parametru Kod Opónienie alarmu temperatury podczas wychladzania/uruchamiania/odtajania A12 Próg alarmu, wysoka temperatura (przestrze chlodzona) A13 Próg alarmu, niska temperatura A14 Opónienie DI1 (czas opónienia dla wybranej funkcji A27 wejcia DI1) Opónienie DI2 (czas opónienia dla wybranej funkcji A28 wejcia DI2) Próg alarmu, wysoka temperatura skraplania A37 Górny próg blokowania, wysoka temperatura skraplania A54 Wlczone zabezpieczenie napiciowe A72 Minimalne napicie zalczenia A73 Minimalne napicie wylczenia A74 Maksymalne napicie A75 Odtajanie d-- Metoda odtajania no=bez odtajania, nAt=naturalne, d01 EL=elektryczne, gAS=gorcym gazem Temperatura koca odtajania d02 Przerwa midzy startami kolejnych odtaja d03 Maksymalny czas odtajania d04 Opónienie odtajania po wlczaniu zasilania (lub sygnale DI) d05 Opónienie ze wzgldu na ociekanie d06 Opónieniezalczeniawentylatorapoodtajaniu d07 Temperaturazalczeniawentylatorapoodtajaniu d08 Praca wentylatora podczas odtajania d09 Uwaga: ukryte parametry s wyszarzone Minimalna maksymalna Jednost. Apli. 0 (dom.) Apli. 1 Apli. 2 Apli. 3 Apli. 4 Apli. 5 Apli. 6 0 240 min 60 90 60 60 60 60 60 -100.0 200.0 C/F 8.0 10.0 -100.0 200.0 C/F -30.0 0.0 8.0 -15.0 -2.0 -30.0 8.0 -15.0 8.0 -2.0 -30.0 -30.0 0 240 min 30 30 30 30 30 30 30 0 240 min 30 30 30 30 30 30 30 0 200 C/F 80 80 80 80 80 80 - 0 200 C/F 85 85 85 85 85 85 - no yES no no no no no no no 0 270 V 0 0 0 0 0 0 0 0 270 V 0 0 0 0 0 0 0 0 270 V 270 270 270 270 270 270 270 no gAS EL nAt EL EL EL EL EL 0.0 50.0 C/F 6.0 - - - 6.0 6.0 6.0 0 240 godz. 8 6 8 12 8 12 8 0 480 min 30 45 15 15 30 30 30 0 240.0 min 0 0 0 0 0 0 - 0 60 min 0 0 0 0 0 0 5 0 60 min 0 0 0 0 0 0 5 -50.0 0.0 C/F -5.0 - - - -5.0 -5.0 - oFF on on on on on on on on | 106 Instruction sheet | ERC 213 DKRCE.PI.RL0.G5.ML/520H11075 POLSKI Nazwa parametru Kod Minimalna maksymalna Jednost. Apli. 0 (dom.) Apli. 1 Apli. 2 Apli. 3 Apli. 4 Apli. 5 Apli. 6 Konfiguracja czujnika koca odtajania non=wedlug czasu, Air=czujnik Sair (czujnik przestrzeni chlodzonej), dEF=S5 (czujnik odtajania) d10 non dEF non non non non dEF dEF non Sumaryczny czas pracy sprarki do rozpoczcia odtajania, 0=WYL. d18 0 96 godz. 0 0 0 0 0 0 - Odtajanie wg potrzeb 20.0=WYL. d19 0.0 20.0 K 20.0 - - - 20.0 20.0 - Opónienie odtajania po wychladzaniu 0=WYL. d30 0 960 min 0 0 0 0 0 0 - Sterowanie wentylatorem F-- Wentylator przy wylczaniu sprarki FFc=wentylator pracuje zgodnie ze sprark, FAo=wentylator jest zawsze wlczony, F01 FFc FPL FPL=wentylator pracuje pulsacyjnie FAo FAo FAo FAo FAo FAo FAo Temperatura parownika, przy której nastpuje wylczenie wentylatora, 50.0=WYL. F04 -50.0 50.0 C/F 50.0 - - - 50.0 50.0 - Cykl pracy wentylatora F07 0 15 min 2 2 2 2 2 2 2 Cykl zatrzymania wentylatora F08 0 15.0 min 2 2 2 2 2 2 2 Sprarka c-- Minimalny czas pracy sprarki C01 0 30 min 0 0 0 0 0 0 0 Minimalny czas postoju sprarki C02 0 30 min 2 2 2 2 2 2 2 Opónienie zatrzymania sprarki po otwarciu drzwi C04 0 15 min 0 0 0 0 0 0 1 Wybór funkcji "zero crossing" C70 no yES yES yES yES yES yES yES yES Inne o-- Opónienie zalczenia przekaników (wyj) podczas rozruchu o01 0 600 min 5 5 5 5 5 5 5 Uwaga: ukryte parametry s wyszarzone DKRCE.PI.RL0.G5.ML/520H11075 Instruction sheet | ERC 213 | 107 POLSKI Nazwa parametru Konfiguracja wejcia DI1 oFF=nieuywane, Sdc=monitorowanie stanu wyjcia, doo=alarm otwartych drzwi ze wznowieniem chlodzenia, doA=alarm otwartych drzwi bez wznowienia chlodzenia, SCH=wylcznik glówny, nig=tryb dzienny/ nocny, rFd=przesunicie temperatury odniesienia, EAL=alarm zewntrzny, dEF=odtajanie, Pud=wychladzanie, Sc=czujnik skraplacza Adres portu szeregowego Haslo Wybór typu czujnika n5 = NTC 5 K, n10 = NTC 10 K, Ptc = PTC, Pt1 = Pt1000 Rozdzielczo wywietlania temperatury 0.1=z dokladnoci do 0.1°C, 0.5=z dokladnoci do 0.5°C, 1.0=z dokladnoci do 1.0°C Licznik przekanika 1 (zwikszenie wskazania o 1=100 cykli pracy) Relay 2 counter (zwikszenie wskazania o 1=100 cykli pracy) Licznik przekanika 3 (zwikszenie wskazania o 1=100 cykli pracy) Konfiguracja wejcia DI2 oFF=nieuywane, Sdc=monitorowanie stanu wyjcia, doo=alarm otwartych drzwi ze wznowieniem chlodzenia, doA=alarm otwartych drzwi bez wznowienia chlodzenia, SCH=wylcznik glówny, nig=tryb dzienny/ nocny, rFd=przesunicie temperatury odniesienia, EAL=alarm zewntrzny, dEF=odtajanie, Pud=wychladzanie Predefiniowane aplikacje Uwaga: ukryte parametry s wyszarzone Kod Minimalna maksymalna Jednost. Apli. 0 (dom.) Apli. 1 Apli. 2 Apli. 3 Apli. 4 Apli. 5 Apli. 6 o02 oFF Sc oFF oFF oFF oFF oFF oFF oFF o03 0 247 o05 no 999 o06 n5 Pt1 o15 0.1 1.0 o23 0 999 o24 0 999 o25 0 999 0 0 0 0 0 0 - no no no no no no no n10 n10 n10 n10 n10 n10 - 0.1 0.1 0.1 0.1 0.1 0.1 0.1 0 0 0 0 0 0 - 0 0 0 0 0 0 - 0 0 0 0 0 0 - o37 oFF Pud o61 AP0 AP6 oFF oFF oFF oFF oFF oFF oFF AP0 AP1 AP2 AP3 AP4 AP5 - | 108 Instruction sheet | ERC 213 DKRCE.PI.RL0.G5.ML/520H11075 Nazwa parametru Kod Zapisanie biecych ustawie jako ustawie fabrycznych. OSTRZEENIE: Wczeniejsze ustawienia o67 fabryczne s zastpowane nowymi Konfiguracja DO2 (dEF=odtajania, ALA=alarmu) o71 Wywietlacz podczas odtajania Air=temperatura przestrzeni chlodzonej, FrE=temp. przed rozpoczciem procesu o91 odtajania, -d-=wywietlany jest symbol "-d-" Polaryzacja P-- Polaryzacja wejcia DI1 nc=rozwierne, no=zwierne P73 Polaryzacja wejcia DI2 nc=rozwierne, no=zwierne P74 Odwrócenie dzialania przekanika alarmu 0=normalne dzialanie, P75 1=odwrotne dzialanie przekanika Wlczona blokada klawiatury P76 Odczyty u-- Stan sterownika S0=zalczone chlodzenie/zalczone ogrzewanie, S2=oczekiwanie na uplynicie czasu pracy sprarki, S3=oczekiwanie na uplynicie czasu postoju sprarki -- czas ponownego uruchomienia, S4=opónienie wlczenia po odtajaniu ze wzgldu na ociekanie , S10=chlodzenie zatrzymane przez ustawienie wylcznika glównego w pozycji WYL., S11=chlodzenie zatrzymane przez wylczenie u00 termostatu/ogrzewania, S14=stan odtajania, S15=stan opónienia wlczenia wentylatora po odtajaniu, S17=otwarte drzwi (wejcie DI), S20=chlodzenie awaryjne, S25=rczne sterowanie wyjciami, S30=praca cigla sprarki/ wychladzanie, S32=opónienie zalaczenia przekaników (wyj) po wlczeniu zasilania Uwaga: ukryte parametry s wyszarzone DKRCE.PI.RL0.G5.ML/520H11075 Minimalna maksymalna Jednost. Apli. 0 (dom.) Apli. 1 Apli. 2 Apli. 3 Apli. 4 Apli. 5 Apli. 6 no yES no no no no no no - dEF ALA dEF ALA dEF dEF dEF dEF dEF Air -d- -d- -d- -d- -d- -d- -d- -d- nc no nc no 0 1 no yES no no no no no no no no no no no no no no 0 0 - - - - - no no no no no no - S0 S32 -- Instruction sheet | ERC 213 | 109 POLSKI POLSKI Nazwa parametru Kod Minimalna maksymalna Jednost. Apli. 0 (dom.) Apli. 1 Apli. 2 Apli. 3 Apli. 4 Apli. 5 Apli. 6 Temperatura powietrza (czujnik Sair) u01 -100.0 200.0 C/F --- Odczyt biecej temperatury odniesienia u02 -100.0 200.0 C/F --- Temperatura odtajania (czujnik S5) u09 -100.0 200.0 C/F --- - - - Wejcie DI1 u10 oFF on --- Stan pracy nocnej u13 oFF on --- Wejcie DI2 u37 oFF on --- Temperatura skraplacza (Sc) U09 -100.0 200.0 C/F --- Stan przekanika sprarki u58 oFF on --- Stan przekanika wentylatora u59 oFF on --- Stan przekanika odtajania u60 oFF on --- Stan przekanika owietlenia u63 oFF on --- Odczyt wersji oprogramowania sprztowego u80 000 999 --- Stan alarmu Bld czujnika temperatury powietrza Sair E29 Bld czujnika odtajania S5 E27 Bld czujnika skraplacza Sc E30 Alarm wysokiej temperatury A01 Alarm niskiej temperatury A02 Alarm wysokiego napicia A99 Alarm niskiego napicia AA1 Alarm wysokiej temperatury skraplacza A61 Alarm drzwi A04 Alarm stanu gotowoci A45 Alarm zewntrzny z wejcia DI A15 Uwaga: ukryte parametry s wyszarzone | 110 Instruction sheet | ERC 213 DKRCE.PI.RL0.G5.ML/520H11075 POLSKI Normy bezpieczestwa Przed podlczeniem urzdzenia sprawdzi, czy napicie zasilania jest prawidlowe. Chroni urzdzenie przed wod i wilgoci: uytkowa sterownik tylko w zakresie eksploatacyjnych wartoci granicznych, nie dopuszczajc do naglych zmian temperatury przy wysokiej wilgotnoci powietrza atmosferycznego, aby zapobiec skraplaniu si pary wodnej. Utylizacja produktu Urzdzenie (lub produkt) musi zosta poddane utylizacji zgodnie z lokalnymi przepisami dotyczcymi utylizacji odpadów. Numer rejestracji konstrukcji w UE 002566703-0001 Firma Danfoss nie ponosi adnej odpowiedzialnoci za potencjalne bldy w katalogach, broszurach i innych wydrukowanych materialach. Firma Danfoss zastrzega sobie prawo do dokonywania zmian w swoich produktach bez powiadomienia. Dotyczy to równie produktów ju zamówionych, z zastrzeeniem, e takie zmiany mona wprowadzi bez koniecznoci zmieniania ju uzgodnionych specyfikacji. Wszelkie znaki towarowe znajdujce si w tym dokumencie s wlasnoci odpowiednich firm. Nazwa Danfoss i logotyp Danfoss s znakami towarowymi firmy Danfoss A/S. Wszelkie prawa zastrzeone. DKRCE.PI.RL0.G5.ML/520H11075 Instruction sheet | ERC 213 | 111 ITALIANO L'ERC 213 è un regolatore per la refrigerazione intelligente e multifunzione, per la gestione di temperatura e sbrinamento, disponibile con 3 relè. Il regolatore è stato progettato per soddisfare i requisiti delle odierne applicazioni di refrigerazione commerciale. 1 - Caratteristiche tecniche y Facilità d'uso: i quattro pulsanti, la struttura di menu di facile lettura e le soluzioni applicative preinstallate assicurano un'usabilità ottimale. y Semplice installazione: il relè da 16 A consente la connessione diretta di grandi carichi senza l'utilizzo di un relè intermedio: compressori fino a 2 HP in base al fattore di potenza e all'efficienza del motore (superiore a 0,65 per 230 V e superiore a 0,85 per 115 V). Una vasta gamma di tipologie di sensori e di morsetti a vite compatibili assicurano un'installazione altamente flessibile. y Protezione dell'unità: funzioni software speciali, come la protezione del compressore dalle fluttuazioni nell'alimentazione elettrica o un'alta temperatura di condensazione, assicurano il funzionamento sicuro dell'unità. y Efficienza energetica: sbrinamento su richiesta, modalità giorno/notte e una gestione intelligente della ventola dell'evaporatore garantiscono la massima efficienza energetica. | 112 Instruction sheet | ERC 213 DKRCE.PI.RL0.G5.ML/520H11075 2 - Interfaccia utente Funzione tasto Premere senza rilasciare all'accensione: RIPRISTINO IMPOSTAZIONI DI FABBRICA ("FAC" viene visualizzato) Premere per un secondo: INDIETRO Premere senza rilasciare: PULL-DOWN Premere per un secondo: SETPOINT TEMPERATURA/OK Premere senza rilasciare: MENU Premere per un secondo: SU Premere senza rilasciare: ON/OFF Premere per un secondo: GIÙ Premere senza rilasciare: SBRINAMENTO Icone display Modalità notturna (risparmio energetico) Compressore in funzione Lampeggia in modalità pull-down Ventola in funzione Allarme attivo DKRCE.PI.RL0.G5.ML/520H11075 Instruction sheet | ERC 213 Sbrinamento Unità (°C o °F) ITALIANO | 113 ITALIANO 3 - Configurazione rapida all'accensione y PASSO 1: Accensione y PASSO 2: Selezionare il menu di configurazione rapida Entro 30 secondi dall'accensione, premere "<" INDIETRO per 3 secondi L'interruttore principale "r12" viene automaticamente impostato su OFF. y PASSO 3: Selezionare l'applicazione preinstallata "o61" Il display visualizza automaticamente il parametro di selezione dell'applicazione "o61". Premere SET per selezionare l'applicazione preinstallata. Il display visualizza il valore di default (per es. "AP0", lampeggiante). Scegliere il tipo di applicazione premendo SU/GIÙ e premere SET per confermare. Il regolatore preimposta i valori dei parametri in funzione dell'applicazione selezionata e nasconde i parametri non pertinenti. Suggerimento: è possibile passare facilmente da AP0 a AP6 e quindi selezionare l'elenco semplificato dei parametri, premendo il tasto SU (elenco circolare). App App 0 App 1 App 2 App 3 App 4 App 5 App 6 Descrizione Nessuna (nessuna applicazione preimpostata) Unità ref. ventilate temperatura media (2 6 °C), con sbrinamento naturale temporizzato Unità ref. ventilate temperatura media (0 4 °C), con sbrinamento elettrico temporizzato Unità ref. ventilate temperatura bassa (-26 -20 °C), con sbrinamento elettrico temporizzato Unità ref. ventilate temperatura media (0 4 °C), con sbrinamento elettrico temporizzato (in base alla temp.) Unità ref. ventilate temperatura bassa (-26 -20 °C), con sbrinamento elettrico temporizzato (in base alla temp.) Nessuna (nessuna applicazione preimpostata) con elenco parametri semplificato | 114 Instruction sheet | ERC 213 DKRCE.PI.RL0.G5.ML/520H11075 ITALIANO Configurazione rapida all'accensione y PASSO 4: Selezionare il sensore tipo "o06" Il display visualizza automaticamente il parametro di selezione del sensore "o06". Premere SET per selezionare il tipo di sensore. Il display visualizza il valore di default (per es. "n10", lampeggiante). Scegliere il tipo di sensore premendo SU/GIÙ (n5=NTC 5 K, n10=NTC 10 K, Ptc=PTC, Pt1=Pt1000) e premere SET per confermare. NOTA: tutti i sensori devono essere dello stesso tipo. DKRCE.PI.RL0.G5.ML/520H11075 Instruction sheet | ERC 213 | 115 | 116 ITALIANO 4 - Struttura del menu 1) Gruppi parametri SET (imposta): premere per 3 secondi per accedere allo stato, impostazioni e servizio Password (se abilitata) Stato ingressi 2) Nome parametri SET Configurazione Interruttore principale SET Applicazione 3) Valore Applicazione 1-2-3-4-5-6 Applicazione 0 Tipo sensore Per scorrere i nomi dei parametri Applicazione 6-5-4-3-2-1 Instruction sheet | ERC 213 DKRCE.PI.RL0.G5.ML/520H11075 Per scorrere i gruppi dei parametri ITALIANO 5 - Configurazione rapida tramite il menu "cFg" y Premere SET per tre secondi per accedere ai gruppi di parametri. y Selezionare il menu "cFg" e premere SET per accedere. Viene visualizzato il primo menu "r12" (interruttore principale). y Impostare l'interruttore principale su OFF (r12=0) per cambiare l'applicazione preinstallata. y Premere SU/GIÙ per scorrere l'elenco dei parametri. y Configurare il parametro "o61" per selezionare un'applicazione preinstallata - Premere SET per accedere al parametro "o61". - Premere SU/GIÙ per selezionare un'applicazione (AP0= nessuna applicazione). - Premere SET per confermare; "o61" viene visualizzato. y Continuare a impostare i parametri successivi (tipo di sensore "o06") nel menu "cFg". DKRCE.PI.RL0.G5.ML/520H11075 Instruction sheet | ERC 213 | 117 ITALIANO 6 - Funzionamento di base Regolazione della temperatura di setpoint (pressione breve) SET: regola la temperatura di setpoint. SU/GIÙ: modifica il setpoint della temperatura (in modalità impostazione, il setpoint lampeggia). SET: salva il setpoint della temperatura. Avvio di uno sbrinamento manuale SBRINAMENTO: premere per 3 secondi per avviare lo sbrinamento. SBRINAMENTO: premere per 3 secondi per arrestare lo sbrinamento manuale. L'icona SBRINAMENTO viene visualizzata durante lo sbrinamento. | 118 Instruction sheet | ERC 213 DKRCE.PI.RL0.G5.ML/520H11075 ITALIANO Funzionamento di base - 02 Avvio di un pull down (raffreddamento rapido) PULL DOWN: premere per 3 secondi per avviare il pull down. "Pud" viene visualizzato per 3 secondi a indicare il pull down. L'icona PULL DOWN lampeggia durante il pull down. PULL DOWN: premere per 3 secondi per arrestare il pull down. Visualizzazione di un allarme attivo I codici di temperatura e di allarme lampeggiano alternativamente fino a quando il problema correlato all'allarme non viene risolto. Il campanello dell'allarme viene visualizzato. Sblocco della tastiera - Dopo 5 minuti di inattività, la tastiera viene bloccata (se P76 = YES). - Quando la tastiera è bloccata, qualsiasi selezione di un tasto visualizza "LoC" sul display. - Premere simultaneamente i pulsanti SU e GIÙ per 3 secondi per sbloccare la tastiera. "unl" viene visualizzato per 3 secondi. DKRCE.PI.RL0.G5.ML/520H11075 Instruction sheet | ERC 213 | 119 ITALIANO 7 - Dati tecnici CARATTERISTICHE Alimentazione elettrica Potenza nominale Ingressi Tipi sensore consentiti Sensori inclusi in "Kit Solution" Precisione DESCRIZIONE Alimentazione a bassa tensione, regolata, isolata galvanicamente, da 115 V CA o 230V CA, 50/60 Hz Inferiore a 0,7 W 4 ingressi: 2 analogici, 1 analogico/digitale e 1 digitale NTC 5000 Ohm a 25 °C (valore beta = 3.980 a 25/100 °C - per es. EKS 211) NTC 10000 Ohm a 25 °C (valore beta = 3.435 a 25/85 °C - per es. EKS 221) PTC 990 Ohm a 25 °C (per es. EKS 111) Pt1000 (per es. AKS 11, AKS 12, AKS 21) NTC 10000 Ohm a 25 °C, lunghezza cavo = 1,5 m Campo di misura: -40 105 °C (-40 221 °F) Precisione regolatore: +/-1 K al di sotto di -35 °C, +/-0,5 K fra -35 25 °C, +/-1 K al di sopra di 25 °C | 120 Instruction sheet | ERC 213 DKRCE.PI.RL0.G5.ML/520H11075 CARATTERISTICHE Uscita Display Condizioni di funzionamento Condizioni di immagazzinamento Protezione Dati ambientali Resistenza al calore e al fuoco Categoria EMC Approvazioni DKRCE.PI.RL0.G5.ML/520H11075 DESCRIZIONE Relè compressore DO1: 16 A, 16 (16) A, EN 60730 10 FLA / 60 LRA a 230 V, UL60730 16 FLA / 72 LRA a 115 V, UL60730 Relè sbrinamento DO2: 8 A, 2 FLA / 12 LRA, UL60730 8 A, 2 (2 A), EN60730 Relè ventola DO3: 3 A, 2 FLA/12 LRA, UL60730 3 A, 2 (2 A), EN60730 Display a LED, 3 cifre, punto decimale e icone multifunzione, scala °C + °F -10 55 °C (14 131 °F), 90% Rh -40 70 °C (-40 158 °F), 90% Rh Anteriore: IP65 (con guarnizione) Posteriore: IP00 Grado d'inquinamento II, senza condensa Categoria D (UL94-V0) Categoria I Riconoscimento UL (USA e Canada) (UL 60730) ENEC (EN 60730) CQC EC (Direttiva LVD e EMC) EAC (GHOST) NSF ROHS2.0 Monitoraggio della temperatura HACCP in conformità a EN134785 Classe I se utilizzato con sensore AKS 12 Instruction sheet | ERC 213 | 121 ITALIANO ITALIANO 8 - Impostazione applicazione predefinita App Modalità Descrizione App 0 App 1 App 2 App 3 App 4 App 5 App 6 Refrigeraz. Refrigeraz. Refrigeraz. Refrigeraz. Refrigeraz. Refrigeraz. Refrigeraz. Nessuna (nessuna applicazione preimpostata) Unità refrigeranti ventilate temperatura media, con sbrinamento naturale temporizzato Unità refrigeranti ventilate temperatura media, con sbrinamento elettrico temporizzato Unità refrigeranti ventilate temperatura bassa, con sbrinamento elettrico temporizzato Unità refrigeranti ventilate temperatura media, con sbrinamento elettrico temporizzato (in base alla temp.) Unità refrigeranti ventilate temperatura bassa, con sbrinamento elettrico temporizzato (in base alla temp.) Nessuna (nessuna applicazione preimpostata) con elenco parametri semplificato Temperatura Tipo sbrinamento Fine sbrinamento (2 6 °C) (0 4 °C) (-26 -20 °C) (0 4 °C) (-26 -20 °C) Naturale Elettrico Elettrico Elettrico Elettrico Tempo Tempo Tempo Temperatura Temperatura APP 1 DI1 DI2 Sair APP 2/3 DI1 DI2 Sair APP 4/5 DI1 DI2 S5 Sair 230 V CA DO1 DO2 DO3 | 122 230 V CA DO1 DO2 DO3 Instruction sheet | ERC 213 230 V CA DO1 DO2 DO3 DKRCE.PI.RL0.G5.ML/520H11075 ITALIANO 9 - Lista parametri Nome parametro - ERC 213 Configurazione Interruttore principale -1=servizio, 0=OFF, 1=ON Applicazioni predefinite AP0, AP1, AP2, AP3, AP4, AP5, AP6 Selezione tipo sensore n5=NTC 5 K, n10=NTC 10 K, Ptc=PTC, Pt1=Pt1000 Riferimento/termostato Setpoint temperatura Differenziale Limitazione setpoint min. Limite setpoint max. Offset display (valore di correzione della temperatura a display) Unità display (°C/°F) Calibrazione di Sair (offset per la calibrazione della temperatura dell'aria) Interruttore principale -1=servizio, 0=OFF, 1=ON Setback notturno (offset di temperatura in modalità notturna) Spostamento di riferimento termostato (offset di temperatura) Durata pull-down Limite temperatura pull-down Nota: i parametri nascosti sono in grigio Codice Min. cFg r12 -1 Max. 1 Unità App. 0 (Sbr.) App. 1 App. 2 App. 3 App. 4 App. 5 App. 6 1 1 1 1 1 1 1 o61 AP0 AP6 AP0 AP1 AP2 AP3 AP4 AP5 AP6 o06 n5 Pt1 n10 n10 r-- r00 -100.0 200.0 C/F 2.0 4.0 r01 0.1 20.0 K 2.0 2.0 r02 -100.0 200.0 C/F -35.0 2.0 r03 -100.0 200.0 C/F 50.0 6.0 r04 -10.0 10.0 K 0.0 0.0 r05 -C -F -C -C r09 -20.0 20.0 K 0.0 0.0 n10 n10 n10 n10 n10 2.0 -24.0 2.0 -24.0 2.0 2.0 2.0 2.0 2.0 2.0 0.0 -26.0 0.0 -26.0 -35.0 4.0 -20.0 4.0 -20.0 50.0 0.0 0.0 0.0 0.0 0.0 -C -C -C -C -C 0.0 0.0 0.0 0.0 - r12 -1 1 1 1 1 1 1 1 - r13 -50.0 50.0 K 0.0 0.0 0.0 0.0 0.0 0.0 0.0 r40 -50.0 50.0 K 0.0 0.0 0.0 0.0 0.0 0.0 - r96 0 960 min 0 0 0 0 0 0 - r97 -100.0 200.0 C/F 0.0 0.0 0.0 0.0 0.0 0.0 - DKRCE.PI.RL0.G5.ML/520H11075 Instruction sheet | ERC 213 | 123 ITALIANO Nome parametro - ERC 213 Allarme Ritardo allarme temperatura in condizioni normali Ritardo allarme temperatura durante pull-down/avvio/sbrinamento Limite allarme alta temperatura (Cabinet/Ambiente) Limite allarme bassa temperatura Ritardo DI1 (ritardo temporale per la funzione DI1 selezionata) Ritardo DI2 (ritardo temporale per la funzione DI2 selezionata) Limite superiore allarme temperatura condensatore Limite superiore allarme temperatura condensatore e blocco compressore Abilitazione protezione tensione Tensione inserimento minima Tensione disinserimento minima Tensione massima Sbrinamento Metodo di sbrinamento no=nessun sbrinamento, nAt=naturale, EL=elettrico, gAS=gas caldo Temperatura arresto sbrinamento Intervallo sbrinamento Tempo sbrinamento max. Ritardo sbrinamento ad accensione (o segnale DI) Nota: i parametri nascosti sono in grigio | 124 Codice Min. A-A03 0 Max. 240 Unità App. 0 (Sbr.) App. 1 App. 2 App. 3 App. 4 App. 5 App. 6 min 30 45 30 30 30 30 30 A12 0 240 min 60 90 60 60 60 60 60 A13 -100.0 200.0 C/F 8.0 10.0 8.0 -15.0 8.0 -15.0 8.0 A14 -100.0 200.0 C/F -30.0 0.0 -2.0 -30.0 -2.0 -30.0 -30.0 A27 0 240 min 30 30 30 30 30 30 30 A28 0 240 min 30 30 30 30 30 30 30 A37 0 200 C/F 80 80 80 80 80 80 - A54 0 200 C/F 85 85 85 85 85 85 - A72 no yES no no no no no no no A73 0 270 V 0 0 0 0 0 0 0 A74 0 270 V 0 0 0 0 0 0 0 A75 0 270 V 270 270 270 270 270 270 270 d-- d01 no gAS EL nAt EL EL EL EL EL d02 0.0 50.0 C/F 6.0 - - - 6.0 6.0 6.0 d03 0 240 ore 8 6 8 12 8 12 8 d04 0 480 min 30 45 15 15 30 30 30 d05 0 240.0 min 0 0 0 0 0 0 - Instruction sheet | ERC 213 DKRCE.PI.RL0.G5.ML/520H11075 ITALIANO Nome parametro - ERC 213 Ritardo gocciolamento Ritardo ventola dopo sbrinamento Temperatura avvio ventola dopo sbrinamento Ventola durante lo sbrinamento Configurazione del sensore di arresto sbrinamento non=a tempo, Air=Sair (temperatura aria), dEF=S5 (sensore sbrinamento) tempo accumulato di attivazione compressore per avvio sbrinamento 0=OFF Sbrinamento su richiesta 20.0=OFF Ritardo sbrinamento dopo pull-down 0=OFF Controllo ventola Ventola a disinserimento compressore FFc=ventola segue compressore, FAo=ventola sempre ON, FPL= pulsazione ventola Temperatura evaporatore arresto ventola 50.0=OFF Ciclo ventola ON Ciclo ventola OFF Compressore Tempo minimo ON compressore Tempo minimo OFF compressore Ritardo compressore OFF con porta aperta Selezione zero crossing Nota: i parametri nascosti sono in grigio Codice Min. d06 0 d07 0 d08 -50.0 d09 oFF Max. 60 60 0.0 on Unità min min App. 0 (Sbr.) App. 1 App. 2 App. 3 App. 4 App. 5 App. 6 0 0 0 0 0 0 5 0 0 0 0 0 0 5 C/F -5.0 - - - -5.0 -5.0 - on on on on on on on d10 non dEF non non non non dEF dEF non d18 0 96 ore 0 0 0 0 0 0 - d19 0.0 20.0 K 20.0 - - - 20.0 20.0 - d30 0 960 min 0 0 0 0 0 0 - F-- F01 FFc FPL FAo FAo FAo FAo FAo FAo FAo F04 -50.0 50.0 C/F 50.0 - - - 50.0 50.0 - F07 0 15 min 2 2 2 2 2 2 2 F08 0 15.0 min 2 2 2 2 2 2 2 c-- C01 0 30 min 0 0 0 0 0 0 0 C02 0 30 min 2 2 2 2 2 2 2 C04 0 15 min 0 0 0 0 0 0 1 C70 no yES yES yES yES yES yES yES yES DKRCE.PI.RL0.G5.ML/520H11075 Instruction sheet | ERC 213 | 125 ITALIANO Nome parametro - ERC 213 Altri Ritardo uscite all'avviamento Configurazione DI1 oFF=non utilizzata, Sdc=visualizzazione stato uscita, doo=allarme porta con riavvio, doA=allarme porta senza riavvio, SCH = interruttore principale, nig=modalità giorno/notte, rFd=spostamento del riferimento di temperatura, EAL=allarme esterno, dEF=sbrinamento, Pud=pull-down, Sc=sensore condensatore Indirizzo seriale Password Selezione tipo sensore n5=NTC 5 K, n10=NTC 10 K, Ptc=PTC, Pt1=Pt1000 Risoluzione display 0.1=passi di 0,1 °C, 0.5=passi di 0,5 °C, 1.0=passi di 1,0 °C Contatore Relè 1 (1 conteggio=100 cicli di funzionamento) Contatore Relè 2 (1 conteggio=100 cicli di funzionamento) Contatore Relè 3 (1 conteggio=100 cicli di funzionamento) Configurazione DI2 oFF=non utilizzata, Sdc=visualizzazione stato uscita, doo=allarme porta con riavvio, doA=allarme porta senza riavvio, SCH=interruttore principale, nig=modalità giorno/notte, rFd=spostamento del riferimento di temperatura, EAL=allarme esterno, dEF=sbrinamento, Pud=pull-down Nota: i parametri nascosti sono in grigio Codice Min. o-o01 0 o02 oFF o03 0 o05 no o06 n5 o15 0.1 o23 0 o24 0 o25 0 o37 oFF Max. 600 Sc 247 999 Pt1 1.0 999 999 999 Pud Unità App. 0 (Sbr.) App. 1 App. 2 App. 3 App. 4 App. 5 App. 6 min 5 5 5 5 5 5 5 oFF oFF oFF oFF oFF oFF oFF 0 0 0 0 0 0 - no no no no no no no n10 n10 n10 n10 n10 n10 - 0.1 0.1 0.1 0.1 0.1 0.1 0.1 0 0 0 0 0 0 - 0 0 0 0 0 0 - 0 0 0 0 0 0 - oFF oFF oFF oFF oFF oFF oFF | 126 Instruction sheet | ERC 213 DKRCE.PI.RL0.G5.ML/520H11075 ITALIANO Nome parametro - ERC 213 Codice Min. Applicazioni predefinite o61 AP0 Salvataggio impostazioni come predefinite ATTENZIONE: le impostazioni predefinite o67 no precedenti saranno sovrascritte Configurazione DO2 dEF=sbrinamento, ALA=allarme o71 dEF Display allo sbrinamento Air=temperatura aria effettiva, FrE=temperatura o91 Air congelamento, -d-="-d-" è visualizzato Polarità P-- Polarità ingresso DI1 nc=normalmente chiuso, no=normalmente aperto P73 nc Polarità ingresso DI2 nc=normalmente chiuso, no=normalmente aperto P74 nc Relè allarme inversione 0=normale, 1=inversione azione relè P75 0 Abilitazione blocco tastiera P76 no Letture u-- Stato regolatore S0=refrigerazione ON/Riscaldamento ON, S2=attesa fine tempo ON compressore, S3=attesa fine tempo OFF compressore-tempo riavvio, S4=ritardo gocciolamento OFF, S10=arresto refrigerazione S11=refrigerazione arrestata da OFF termostato/riscaldamento, u00 S0 S14=sbrinamento, S15=ritardo ventola dopo sbrinamento, S17=porta aperta (ingresso DI), S20=refrigerazione d'emergenza, S25=controllo manuale uscite, S30=ciclo continuo/Pull-down, S32=ritardo uscite ad accensione Nota: i parametri nascosti sono in grigio Max. AP6 yES ALA -d- no no 1 yES S32 Unità App. 0 (Sbr.) App. 1 App. 2 App. 3 App. 4 App. 5 App. 6 AP0 AP1 AP2 AP3 AP4 AP5 - no no no no no no - dEF ALA dEF dEF dEF dEF dEF -d- -d- -d- -d- -d- -d- -d- no no no no no no no no no no no no no no 0 0 - - - - - no no no no no no - -- DKRCE.PI.RL0.G5.ML/520H11075 Instruction sheet | ERC 213 | 127 ITALIANO Nome parametro - ERC 213 Temperatura aria (Sair) Lettura del rifer. di regolazione attuale Temperatura sbrinamento (S5) DI1 input Status of night operation DI2 input Condenser temperature (Sc) Stato relè compressore Stato relè ventola Stato relè sbrinamento Stato relè luci Lettura versione firmware Stato allarme Errore sensore temperatura aria Sair Errore sensore sbrinamento S5 Errore sensore condensatore Sc Allarme alta temperatura Allarme bassa temperatura Allarme tensione alta Allarme tensione bassa Allarme condensatore Allarme porta Allarme standby Allarme DI esterno Nota: i parametri nascosti sono in grigio Codice Min. u01 -100.0 u02 -100.0 u09 -100.0 u10 oFF u13 oFF u37 oFF U09 -100.0 u58 oFF u59 oFF u60 oFF u63 oFF u80 000 Max. 200.0 200.0 200.0 on on on 200.0 on on on on 999 Unità C/F C/F C/F C/F App. 0 (Sbr.) App. 1 App. 2 App. 3 App. 4 App. 5 --- --- --- - - - --- --- --- --- --- --- --- --- --- App. 6 E29 E27 E30 A01 A02 A99 AA1 A61 A04 A45 A15 | 128 Instruction sheet | ERC 213 DKRCE.PI.RL0.G5.ML/520H11075 ITALIANO Standard di sicurezza Controllare che la tensione di alimentazione sia corretta prima di collegare lo strumento. Non esporre all'acqua o all'umidità: usare il regolatore solo nei limiti di funzionamento previsti, evitando cambi di temperatura repentini ad alta umidità atmosferica per evitare la formazione di condensa. Smaltimento del prodotto L'apparecchiatura (o il prodotto) deve essere smaltita in conformità con le leggi locali sullo smaltimento dei rifiuti. Registrazione design UE 002566703-0001 Danfoss non accetta alcuna responsabilità per eventuali errori nei cataloghi, opuscoli e altro materiale stampato. Danfoss si riserva il diritto di modificare i suoi prodotti senza preavviso. Questo si applica anche ai prodotti già in ordine a condizione che tali modifiche siano necessarie nelle specifiche già concordate. Tutti i marchi in questo materiale sono di proprietà della società. Danfoss e il logotipo Danfoss sono marchi di fabbrica di Danfoss A / S. Tutti i diritti sono riservati. DKRCE.PI.RL0.G5.ML/520H11075 Instruction sheet | ERC 213 | 129 DEUTSCH Der ERC 213 ist ein intelligenter multifunktionaler Kühlstellenregler mit Temperatur- und Abtauregelung. Er ist mit drei Relais erhältlich. Der Regler ist so konstruiert, dass er die heutigen Anforderungen an moderne Gewerbekälteanwendungen erfüllt. 1 - Technische Highlights y Benutzerfreundlichkeit: Vier Tasten, eine leicht verständliche Menüstruktur und vorinstallierte Anwendungslösungen bieten eine überragende Benutzerfreundlichkeit. y Einfache Installation: Ein leistungsfähiges 16-A-Relais ermöglicht den direkten Anschluss von hohen Lasten ohne Zwischenrelais: Bis zu zwei Hochdruckverdichter, je nach Leistungsfaktor und Motorwirkungsgrad, sind möglich (größer als 0,65 für 230 V und größer als 0,85 für 115 V). Ein breites Spektrum an kompatiblen Fühlertypen und Schraubanschlüssen garantiert höchste Flexibilität bei der Installation. A wide range of compatible types of sensors and screw connection terminals ensure highly flexible installation. y Schutzfunktionen: Spezielle Softwarefunktionen wie der Schutz des Verdichters vor Schwankungen der Versorgungsspannung oder vor hohen Verflüssigungstemperaturen stellen einen sicheren und zuverlässigen Betrieb der Anlage sicher. y Energieeffizienz: Die Bedarfsabtauung, der Tag-/Nachtmodus und das intelligente Verdampferlüftermanagement sorgen für eine hohe Energieeffizienz. | 130 Instruction sheet | ERC 213 DKRCE.PI.RL0.G5.ML/520H11075 2 - Benutzeroberfläche Tastenfunktion Beim Einschalten drücken und gedrückt halten: RÜCKSETZUNG AUF WERKSEINSTELLUNGEN (,,FAC" wird angezeigt) Eine Sekunde lang drücken: ZURÜCK Drücken und gedrückt halten: SCHNELLABKÜHLUNG Eine Sekunde lang drücken: TEMPERATURSOLLWERT/OK Drücken und gedrückt halten: MENÜ Eine Sekunde lang drücken: NACH OBEN Drücken und gedrückt halten: EIN/AUS Eine Sekunde lang drücken: NACH UNTEN Drücken und gedrückt halten: ABTAUUNG Angezeigte Symbole Nachtmodus (energiesparend) Verdichter in Betrieb Blinkt im Schnellabkühlungsbetrieb Lüfter in Betrieb Alarm aktiv DKRCE.PI.RL0.G5.ML/520H11075 Instruction sheet | ERC 213 Abtauung Einheit (°C oder °F) DEUTSCH | 131 DEUTSCH 3 - Schnellkonfiguration bei Einschaltung y SCHRITT 1: Einschalten y SCHRITT 2: Schnellkonfigurationsmenü auswählen Innerhalb von 30 Sekunden nach dem Einschalten,,<" (ZURÜCK) drei Sekunden lang drücken. Der Hauptschalter ,,r12" wird automatisch ausgeschaltet. y SCHRITT 3: Vorinstallierte Anwendung ,,o61" auswählen Das Display zeigt automatisch den Anwendungsauswahlparameter ,,o61" an. SET drücken, um die vorinstallierte Anwendung auszuwählen. Das Display zeigt den Standardwert an (z. B. blinkt,,AP0" auf ). Den Anwendungstyp auswählen, indem die Taste für NACH OBEN/UNTEN und dann zur Bestätigung SET gedrückt wird. Der Regler stellt vorab die Parameterwerte entsprechend der ausgewählten Anwendung ein und zeigt alle relevanten Parameter an. Tipp: Durch Drücken der Taste für NACH OBEN kann leicht von AP0 nach AP6 gewechselt und so die vereinfachte Parameterliste (Ringliste) ausgewählt werden. Anw. Anw. 0 Anw. 1 Anw. 2 Anw. 3 Anw. 4 Anw. 5 Anw. 6 Beschreibung Keine (keine voreingestellte Anwendung) Mediumstemperatur (2 bis 6 °C), entlüftete Kälteanlagen mit zeitlich festgelegter natürlicher Abtauung Mediumstemperatur (0 bis 4 °C), entlüftete Kälteanlagen mit zeitlich festgelegter elektrischer Abtauung Tieftemperatur (-26 bis -20 °C), entlüftete Kälteanlagen mit zeitlich festgelegter elektrischer Abtauung Mediumstemperatur (0 bis 4 °C), entlüftete Kälteanlagen mit elektrischer Abtauung (über die Temperatur) Tieftemperatur (-26 bis -20 °C), entlüftete Kälteanlagen mit elektrischer Abtauung (über die Temperatur) Keine (keine voreingestellte Anwendung), mit vereinfachter Parameterliste | 132 Instruction sheet | ERC 213 DKRCE.PI.RL0.G5.ML/520H11075 DEUTSCH Schnellkonfiguration bei Einschaltung y SCHRITT 4: Fühlertyp ,,o06" auswählen Das Display zeigt automatisch den Fühlerauswahlparameter ,,o06" an. SET drücken, um den Fühlertyp auszuwählen. Das Display zeigt den Standardwert an (z. B. blinkt,,n10" auf ). Den Fühlertyp auswählen, indem die Taste für NACH OBEN/UNTEN (n5 = NTC 5 K, n10 = NTC 10 K, Ptc = PTC, Pt1 = Pt1000) und dann zur Bestätigung SET gedrückt wird. HINWEIS: Alle Fühler müssen vom gleichen Typ sein. DKRCE.PI.RL0.G5.ML/520H11075 Instruction sheet | ERC 213 | 133 | 134 DEUTSCH 4 - Menüstruktur 1) Parametergruppen SET: Drei Sekunden lang drücken, um Zugang zum Status, zur Einstellung und zum Service zu erhalten Passwort (falls aktiviert) Statuseingabe 2) Parametername SET Konfiguration Hauptschalter SET Anwendung 3) Wert Anwendung 12345-6 Anwendung 0 Fühlertyp Die Parameternamen durchsehen Anwendung 6-5-4-3-2-1 Instruction sheet | ERC 213 DKRCE.PI.RL0.G5.ML/520H11075 Die Parametergruppen durchsehen DEUTSCH 5 - Schnellkonfiguration über das ,,cFg"-Menü y Drei Sekunden lang SET drücken, um Zugang zu den Parametergruppen zu erhalten. y Das,,cFg"-Menü auswählen und SET drücken, um es zu öffnen. Das erste Menü,,r12" (Hauptschalter) wird angezeigt. y Den Hauptschalter ausschalten (r12 = 0), um die vorinstallierte Anwendung zu ändern. y Die Taste für NACH OBEN/UNTEN drücken, um die Parameterliste einzusehen.. y Zum Auswählen einer vorinstallierten Anwendung den Parameter,,o61" konfigurieren: - SET drücken, um Zugriff auf den Parameter ,,o61" zu erhalten. - Die Taste für NACH OBEN/UNTEN drücken, um eine Anwendung auszuwählen (AP0 = keine Anwendung ausgewählt). - SET drücken, um zu bestätigen, dass ,,o61" angezeigt wird. y Im,,cFg"-Menü mit der Einstellung der anderen Parameter (,,o06" = Fühlertyp) fortfahren. DKRCE.PI.RL0.G5.ML/520H11075 Instruction sheet | ERC 213 | 135 DEUTSCH 6 - Grundlegende Bedienung Temperatursollwert einstellen SET (kurzes Drücken): Temperatursollwert einstellen. NACH OBEN/UNTEN: Temperatursollwert ändern (im Einstellmodus blinkt der Sollwert). SET: Temperatursollwert speichern. Eine manuelle Abtauung auslösen ABTAUUNG: Drei Sekunden lang drücken, um eine manuelle Abtauung auszulösen. ABTAUUNG: Drei Sekunden lang drücken, um die manuelle Abtauung zu beenden Während der Abtauung wird das ABTAUUNGssymbol angezeigt | 136 Instruction sheet | ERC 213 DKRCE.PI.RL0.G5.ML/520H11075 DEUTSCH Grundlegende Bedienung - 02 Eine Schnellabkühlung auslösen SCHNELLABKÜHLUNG: Drei Sekunden lang drücken, um eine Schnellabkühlung auszulösen. ,,Pud": Wird drei Sekunden lang angezeigt und steht für eine Schnellabkühlung Während der Schnellabkühlung wird das Schnellabkühlungssymbol angezeigt SCHNELLABKÜHLUNG: Drei Sekunden lang drücken, um die Schnellabkühlung zu beenden. Einen aktiven Alarm anzeigen Die Temperatur- und Alarmcodes blinken abwechselnd, bis die Alarmursache behoben wurde. Die Alarmglocke wird angezeigt. Bedienfeld entsperren - Nach fünf Minuten ohne Aktivität wird das Bedienfeld gesperrt (wenn P76 = ja). - Wenn das Bedienfeld gesperrt ist, wird durch das Drücken irgendeiner Taste ,,LoC" im Display angezeigt. - Die Tasten für NACH OBEN und NACH UNTEN gleichzeitig drei Sekunden lang drücken, um das Bedienfeld zu entsperren. Drei Sekunden lang wird dann ,,unl" angezeigt. DKRCE.PI.RL0.G5.ML/520H11075 Instruction sheet | ERC 213 | 137 DEUTSCH 7 - Technische Daten EIGENSCHAFTEN Versorgungsspannung Nennleistung Eingänge Zulässige Fühlertypen Im Bausatz enthaltene Fühler Genauigkeit Ausgang | 138 BESCHREIBUNG 115 V AC/230 V AC, 50/60 Hz, galvanisch getrennte niederspannungsgeregelte Versorgungsspannung Weniger als 0,7 W Vier Eingänge: Zwei Analogeingänge, Ein Analog-/Digitaleingang und ein Digitaleingang NTC, 5000 Ohm bei 25 °C (Beta-Wert = 3980 bei 25/100 °C; z. B. EKS 211) NTC, 10000 Ohm bei 25 °C (Beta-Wert = 3435 bei 25/85 °C; z. B. EKS 221) PTC, 990 Ohm bei 25 °C (z. B. EKS 111) Pt1000 (z. B. AKS 11, AKS 12, AKS 21) NTC, 10000 Ohm bei 25 °C, Kabellänge = 1,5 m Messbereich: -40 bis 105 °C (-40 bis 221 °F) Reglergenauigkeit: ±1 K unter -35 °C, ±0,5 K zwischen -35 bis 25 °C, ±1 K über 25 °C DO1-Verdichterrelais: 16 A, 16 (16) A, DIN EN 60730 10 FLA/60 LRA mit 230 V, UL 60730 16 FLA/72 LRA mit 115 V, UL 60730 DO2-Abtaurelais: 8 A, 2 FLA/12 LRA, UL 60730 8 A, 2 (2) A, DIN EN 60730 DO3-Lüfterrelais: 3 A, 2 FLA/12 LRA, UL 60730 3 A, 2 (2) A, DIN EN 60730 Instruction sheet | ERC 213 DKRCE.PI.RL0.G5.ML/520H11075 DEUTSCH EIGENSCHAFTEN Display Betriebsbedingungen Lagerbedingungen Schutzart Umweltfreundlichkeit Hitze- und Feuerbeständigkeit EMV-Kategorie Zulassungen BESCHREIBUNG LED-Display, 3-stellig, Dezimalpunkt und Multifunktionssymbole, °C- und °F-Skala -10 bis 55 °C (14 bis 131 °F), 90 % RF -40 bis 70 °C (-40 bis 158 °F), 90 % RF Vorderseite: IP65 (Dichtung integriert) Rückseite: IP00 Verschmutzungsgrad 2, nicht-kondensierend Kategorie D (UL94-V0) Kategorie 1 UL (USA und Kanada) (UL 60730) ENEC (DIN EN 60730) CQC CE (Niederspannungs- und EMV-Richtlinie) EAC (GOST) NSF RoHS 2.0 HACCP-Temperaturüberwachung in Übereinstimmung mit DIN EN 134785, Klasse 1, bei Verwendung mit dem Fühler AKS 12 DKRCE.PI.RL0.G5.ML/520H11075 Instruction sheet | ERC 213 | 139 DEUTSCH 8 - Vordefinierte Anwendungseinstellung Anw. Modus Anw. 0 Kühlung Anw. 1 Kühlung Anw. 2 Kühlung Anw. 3 Kühlung Anw. 4 Kühlung Anw. 5 Kühlung Anw. 6 Kühlung Beschreibung Temp. Keine (keine voreingestellte Anwendung) Mediumstemperatur, entlüftete Kälteanlagen mit zeitlich festgelegter natürlicher Abtauung (2 6 °C) Mediumstemperatur, entlüftete Kälteanlagen mit zeitlich festgelegter elektrischer Abtauung (0 4 °C) Tieftemperatur, entlüftete Kälteanlagen mit zeitlich festgelegter elektrischer Abtauung (-26 -20 °C) Mediumstemperatur, entlüftete Kälteanlagen mit elektrischer Abtauung (über die Temperatur) (0 4 °C) Tieftemperatur, entlüftete Kälteanlagen mit elektrischer Abtauung (über die Temperatur) (-26 -20 °C) Keine (keine voreingestellte Anwendung), mit vereinfachter Parameterliste Def. Art Natürlich Elektrisch Elektrisch Elektrisch Elektrisch Def. Ende Zeit Zeit Zeit Temperatur Temperatur APP 1 DI1 DI2 Sair APP 2/3 DI1 DI2 Sair APP 4/5 DI1 DI2 S5 Sair 230 V CA DO1 DO2 DO3 | 140 230 V CA DO1 DO2 DO3 Instruction sheet | ERC 213 230 V CA DO1 DO2 DO3 DKRCE.PI.RL0.G5.ML/520H11075 DEUTSCH 9 - Parameterliste Parametername ERC 213 Code Min. Max. Einheit Anw. 0 (Abtau- ung) Anw. 1 Anw. 2 Anw. 3 Anw. 4 Anw. 5 Anw. 6 Konfiguration cFg Hauptschalter -1 = Service, 0 = AUS, 1 = EIN r12 -1 1 1 1 1 1 1 1 1 Vordefinierte Anwendungen AP0, AP1, AP2, AP3, AP4, AP5, AP6 o61 AP0 AP6 AP0 AP1 AP2 AP3 AP4 AP5 AP6 Fühlertypauswahl n5 = NTC 5 K, n10 = NTC 10 K, Ptc = PTC, Pt1 = Pt1000 o06 n5 Pt1 n10 n10 n10 n10 n10 n10 n10 Referenz/Thermostat r-- Temperatursollwert r00 -100.0 200.0 C/F 2.0 4.0 2.0 -24.0 2.0 -24.0 2.0 Differenz r01 0.1 20.0 K 2.0 2.0 2.0 2.0 2.0 2.0 2.0 Begrenzung min. Sollwert r02 -100.0 200.0 C/F -35.0 2.0 0.0 -26.0 0.0 -26.0 -35.0 Begrenzung max. Sollwert r03 -100.0 200.0 C/F 50.0 6.0 4.0 -20.0 4.0 -20.0 50.0 Display-Offset (Korrekturwert der angezeigten Temperatur) r04 -10.0 10.0 K 0.0 0.0 0.0 0.0 0.0 0.0 0.0 Displayeinheit (°C/°F) r05 -C -F -C -C -C -C -C -C -C Sair-Kalibrierung (Offset zur Kalibrierung der Lufttemperatur) r09 -20.0 20.0 K 0.0 0.0 0.0 0.0 0.0 0.0 - Hauptschalter -1 = Service, 0 = AUS, 1 = EIN r12 -1 1 1 1 1 1 1 1 - Nachtabsenkung (Offset-Temperatur im Nachtmodus) r13 -50.0 50.0 K 0.0 0.0 0.0 0.0 0.0 0.0 0.0 Sollwertverschiebung Thermostat (Offset-Temperatur) r40 -50.0 50.0 K 0.0 0.0 0.0 0.0 0.0 0.0 - Dauer Schnellabkühlung r96 0 960 min 0 0 0 0 0 0 - Grenztemperatur Schnellabkühlung r97 -100.0 200.0 C/F 0.0 0.0 0.0 0.0 0.0 0.0 - Alarm A-- Verzögerung für den Temperaturalarm unter normalen Bedingungen A03 0 240 min 30 45 30 30 30 30 30 Verzögerung für den Temperaturalarm während der Schnellabkühlung/ A12 0 240 min 60 90 60 60 60 60 60 Inbetriebnahme/Abtauung Hinweis: Verborgene Parameter sind grau dargestellt. DKRCE.PI.RL0.G5.ML/520H11075 Instruction sheet | ERC 213 | 141 DEUTSCH Parametername ERC 213 Code Min. Max. Einheit Anw. 0 (Abtau- ung) Anw. 1 Anw. 2 Anw. 3 Anw. 4 Anw. 5 Anw. 6 Alarmgrenze Hochtemperatur (Schaltschrank/Raum) A13 -100.0 200.0 C/F 8.0 10.0 8.0 -15.0 8.0 -15.0 8.0 Alarmgrenze Tieftemperatur A14 -100.0 200.0 C/F -30.0 0.0 -2.0 -30.0 -2.0 -30.0 -30.0 DI1-Verzögerung (Zeitverzögerung für ausgewählte DI1- A27 0 240 min 30 30 30 30 30 30 30 Funktion) DI2-Verzögerung (Zeitverzögerung für ausgewählte DI2- A28 0 240 min 30 30 30 30 30 30 30 Funktion) Verflüssiger: oberer Grenzwert Alarm A37 0 200 C/F 80 80 80 80 80 80 - Verflüssiger: oberer Grenzwert Blockierung A54 0 200 C/F 85 85 85 85 85 85 - Spannungsschutz aktiviert A72 no yES no no no no no no no Minimale Einschaltspannung A73 0 270 V 0 0 0 0 0 0 0 Minimale Ausschaltspannung A74 0 270 V 0 0 0 0 0 0 0 Maximale Spannung A75 0 270 V 270 270 270 270 270 270 270 Abtauung d-- Abtaumethode no = keine Abtauung, nAt = natürliche Abtauung, EL = elektrische Abtauung, d01 no gAS EL nAt EL EL EL EL EL gAS = Abtauung mit Heißgas Temperatur Abtauung beendet d02 0.0 50.0 C/F 6.0 - - - 6.0 6.0 6.0 Abtauintervall d03 0 240 h 8 6 8 12 8 12 8 Max. Abtauzeit d04 0 480 min 30 45 15 15 30 30 30 Abtauverzögerung bei Einschaltung (oder DI-Signal) d05 0 240.0 min 0 0 0 0 0 0 - Abtropfzeit d06 0 60 min 0 0 0 0 0 0 5 Lüfterverzögerung nach Abtauung d07 0 60 min 0 0 0 0 0 0 5 Einschalttemperatur Lüfter nach Abtauung d08 -50.0 0.0 C/F -5.0 - - - -5.0 -5.0 - Lüfter während der Abtauung d09 oFF on on on on on on on on Fühler zum Beenden der Abtauung Konfiguration: non = Zeit, Air = Sair d10 non dEF non non non non dEF dEF non (Lufttemperatur), dEF = S5 (Abtaufühler) Hinweis: Verborgene Parameter sind grau dargestellt. | 142 Instruction sheet | ERC 213 DKRCE.PI.RL0.G5.ML/520H11075 DEUTSCH Parametername ERC 213 Code Min. Max. Einheit Anw. 0 (Abtau- ung) Anw. 1 Anw. 2 Anw. 3 Anw. 4 Anw. 5 Anw. 6 Gesamte Verdichter-Betriebszeit bis zum Auslösen der Abtauung d18 0 96 h 0 0 0 0 0 0 - 0 = AUS Bedarfsabtauung 0,0 = AUS d19 0.0 20.0 K 20.0 - - - 20.0 20.0 - Abtauverzögerung nach Schnellabkühlung 0 = AUS d30 0 960 min 0 0 0 0 0 0 - Lüfterregelung F-- Lüfter bei Verdichterabschaltung FFc = Lüfter folgt Verdichter,FAo = Lüfter immer F01 FFc FPL FAo FAo FAo FAo FAo FAo FAo eingeschaltet, FPL = Lüfter pulsiert Verdampfertemperatur Lüfterabschaltung 50,0 = AUS F04 -50.0 50.0 C/F 50.0 - - - 50.0 50.0 - Kreislauf mit Lüfter EIN F07 0 15 min 2 2 2 2 2 2 2 Kreislauf mit Lüfter AUS F08 0 15.0 min 2 2 2 2 2 2 2 Verdichter c-- Min. Zeit Verdichter-Einschaltung C01 0 30 min 0 0 0 0 0 0 0 Min. Zeit Verdichter-Abschaltung C02 0 30 min 2 2 2 2 2 2 2 Ausschaltverzögerung Verdichter bei geöffneter Tür C04 0 15 min 0 0 0 0 0 0 1 Auswahl Nulldurchgang C70 no yES yES yES yES yES yES yES yES Sonstige o-- Verzögerung der Ausgänge bei Einschaltung o01 0 600 min 5 5 5 5 5 5 5 DI1-Konfiguration oFF = nicht verwendet, Sdc = Status-Displayausgabe, doo = Türalarm mit erneuter Aktivierung, doA = Türalarm ohne erneute Aktivierung, o02 oFF Sc oFF oFF oFF oFF oFF oFF oFF SCH = Hauptschalter, nig = Tag-/Nachtmodus, rFd = Sollwertverschiebung, EAL = externer Alarm, dEF = Abtauung, Pud = Schnellabkühlung, Sc = Verflüssigerfühler Serielle Adresse o03 0 247 0 0 0 0 0 0 - Hinweis: Verborgene Parameter sind grau dargestellt. DKRCE.PI.RL0.G5.ML/520H11075 Instruction sheet | ERC 213 | 143 DEUTSCH Parametername ERC 213 Code Min. Max. Einheit Anw. 0 (Abtau- ung) Anw. 1 Anw. 2 Anw. 3 Anw. 4 Anw. 5 Anw. 6 Passwort o05 no 999 no no no no no no no Fühlertypauswahl n5 = NTC 5 K, n10 = NTC 10 K, o06 n5 Pt1 n10 n10 n10 n10 n10 n10 - Ptc = PTC, Pt1 = Pt1000 Displayauflösung 0.1 = Schritte von 0,1 °C 0.5 = Schritte von 0,5 °C o15 0.1 1.0 0.1 0.1 0.1 0.1 0.1 0.1 0.1 1.0 = Schritte von 1,0 °C Zähler Relais 1 (Eine Zählung = 100 Betriebszyklen) o23 0 999 0 0 0 0 0 0 - Zähler Relais 2 (Eine Zählung = 100 Betriebszyklen) o24 0 999 0 0 0 0 0 0 - Zähler Relais 3 (Eine Zählung = 100 Betriebszyklen) o25 0 999 0 0 0 0 0 0 - DI2-Konfiguration oFF = nicht verwendet, Sdc = Status- Displayausgabe, doo = Türalarm mit erneuter Aktivierung, doA = Türalarm ohne erneute Aktivierung, SCH = Hauptschalter, o37 oFF Pud oFF oFF oFF oFF oFF oFF oFF nig = Tag-/Nachtmodus, rFd = Sollwertverschiebung, EAL = externer Alarm, dEF = Abtauung, Pud = Schnellabkühlung Vordefinierte Anwendungen o61 AP0 AP6 AP0 AP1 AP2 AP3 AP4 AP5 - Einstellungen als Werkseinstellungen speichern ACHTUNG: Die früheren Werkseinstellungen o67 no yES no no no no no no - werden überschrieben. DO2-Konfiguration dEF=Abtauen, ALA=Alarm o71 dEF ALA dEF ALA dEF dEF dEF dEF dEF Anzeige bei Abtauung Air = aktuelle Lufttemperatur, FrE = Gefriertemperatur, o91 Air -d- -d- -d- -d- -d- -d- -d- -d- -d- = ,,-d-" wird angezeigt Hinweis: Verborgene Parameter sind grau dargestellt. | 144 Instruction sheet | ERC 213 DKRCE.PI.RL0.G5.ML/520H11075 DEUTSCH Parametername ERC 213 Code Min. Max. Einheit Anw. 0 (Abtau- ung) Anw. 1 Anw. 2 Anw. 3 Anw. 4 Anw. 5 Anw. 6 Polarität P-- DI1-Eingangspolarität nc = stromlos geschlossen, P73 nc no no no no no no no no no = stromlos geöffnet DI2-Eingangspolarität nc = stromlos geschlossen, P74 nc no no no no no no no no no = stromlos geöffnet Invertiertes Alarmrelais 0 = normal, 1 = invertierte Relais-Aktion P75 0 1 0 0 - - - - - Sperrung des Bedienfelds aktiviert P76 no yES no no no no no no - Anzeigen u-- Reglerstatus S0 = Kühlung aktiviert/Beheizung aktiviert, S2 = auf Ablaufen der Verdichter- Aktivierungszeit warten, S3 = auf Ablaufen der Verdichter-Deaktivierungs-/-Neustartzeit warten, S4 = Verzögerung der Tropfenbildung nach Abtauung, S10 = Kühlung beendet, S11 = Kühlung über Thermostat beendet/ Deaktivierung der Beheizung, u00 S0 S32 -- S14 = Abtaustatus, S15 = Lüfterverzögerungsstatus nach Abtauung, S17 = Tür geöffnet (DI-Eingang), S20 = Notkühlung, S25 = manuelle Übersteuerung der Ausgänge, S30 = Dauerbetrieb/Schnellabkühlung, S32 = Verzögerung der Ausgänge bei Einschaltung Lufttemperatur (Sair) u01 -100.0 200.0 C/F --- Auslesen des vorhandenen Regelsollwerts u02 -100.0 200.0 C/F --- Abtautemperatur (S5) u09 -100.0 200.0 C/F --- - - - DI1-Eingang u10 oFF on --- Status des Nachtbetriebs u13 oFF on --- DI2-Eingang u37 oFF on --- Hinweis: Verborgene Parameter sind grau dargestellt. DKRCE.PI.RL0.G5.ML/520H11075 Instruction sheet | ERC 213 | 145 DEUTSCH Parametername ERC 213 Code Min. Max. Einheit Anw. 0 (Abtau- ung) Anw. 1 Anw. 2 Anw. 3 Anw. 4 Anw. 5 Anw. 6 Verflüssigertemperatur (Sc) U09 -100.0 200.0 C/F --- Status Verdichterrelais u58 oFF on --- Status Lüfterrelais u59 oFF on --- Status Abtaurelais u60 oFF on --- Status Beleuchtungsrelais u63 oFF on --- Anzeige Firmware-Version u80 000 999 --- Alarmstatus Fehler Sair-Lufttemperaturfühler E29 Fehler S5-Abtaufühler E27 Fehler Sc-Verflüssigerfühler E30 Hochtemperaturalarm A01 Tieftemperaturalarm A02 Hochspannungsalarm A99 Tiefspannungsalarm AA1 Verflüssigeralarm A61 Türalarm A04 Standby-Alarm A45 Externer Alarm DI A15 Hinweis: Verborgene Parameter sind grau dargestellt. | 146 Instruction sheet | ERC 213 DKRCE.PI.RL0.G5.ML/520H11075 DEUTSCH Sicherheitsstandards Vor dem Anschließen des Geräts ist zu prüfen, ob die Versorgungsspannung ordnungsgemäß ist. Das Gerät darf keinem Wasser und keiner Feuchtigkeit ausgesetzt werden. Der Regler ist nur innerhalb der Betriebsgrenzen zu verwenden, wobei plötzliche Temperaturschwankungen und eine hohe Luftfeuchte zu vermeiden sind, um die Bildung von Kondensat zu verhindern Entsorgung des Produkts Das Gerät (oder das Produkt) ist entsprechend den örtlich geltenden Vorschriften zur Abfallbeseitigung zu entsorgen. EU-Designregistrierung 002566703-0001 Die in Katalogen, Prospekten und anderen schriftlichen Unterlagen, wie z.B. Zeichnungen und Vorschlägen enthalten Angaben und technischen Daten sind vom Käufer vor Übernahme und Anwendung zu prüfen. Der Käufer kann aus diesen Unterlagen und zusätzlichen Diensten keinerlei Ansprüche gegenüber Danfoss oder Danfoss-Mitarbeiter ableiten, es sei denn, dass diese vorsätzlich oder grob fahrlässig gehandelt haben. Danfoss behält sich das Recht vor, ohne vorherige Bekanntmachung im Rahmen des Angemessenen und Zumutbaren Änderungen an Ihren Produkten - auch an bereits in Auftrag genommenen - vorzunehmen. Alle in dieser Publikation enthaltenen Warenzeichen sind Eigentum der jeweiligen Firmen. Danfoss und das Danfoss- Logo sind Warenzeichen der Danfoss A/S. Alle Rechte vorbehalten. DKRCE.PI.RL0.G5.ML/520H11075 Instruction sheet | ERC 213 | 147 Notes | 148 Instruction sheet | ERC 213 DKRCE.PI.RL0.G5.ML/520H11075 Notes DKRCE.PI.RL0.G5.ML/520H11075 Instruction sheet | ERC 213 | 149 Notes | 150 Instruction sheet | ERC 213 DKRCE.PI.RL0.G5.ML/520H11075 Notes DKRCE.PI.RL0.G5.ML/520H11075 Instruction sheet | ERC 213 | 151 KoolCode App Download the KoolCode App on your app store. More and more from your ERC controller! Scan this code to find out more about the ERC 213 parameter © Danfoss | DCS (az) | 2016.04 Instruction sheet | ERC 213 Download ERC 21X series www.danfoss.com/erc DKRCE.PI.RL0.G5.ML/520H11075