E plus E EE600 Differential Pressure Sensor
Quick Guide
EE600 – Differential Pressure Sensor
your partner in sensor technology.
PLEASE NOTE
Find this document and further product information on our website at www.epluse.com/ee600.
Electrical Connection
WARNING
Incorrect installation, wiring or power supply may cause overheating and therefore personal injuries or damage to property. It is essential that the cables are not under voltage during installation. No voltage must be applied when the product is connected or disconnected. For correct cabling of the device, always observe the presented wiring diagram for the product version used. The manufacturer cannot be held responsible for personal injuries or damage to property as a result of incorrect handling, installation, wiring, power supply and maintenance of the device.
Analogue Output
Installation
Pressure Connection
Mounting Examples
Use a Ø7.5 mm drill for installing the pressure connection nipples into the duct.
User Interface – LED Indication
Green LED | Red LED | |||
Flashing (1 s interval) | EE600 operates normally, the measured data is within the selected measuring range | Flashing (1 s interval) | The measured data is out of the selected range (overload or reversed pressure connection) | |
One flash (2 s) | Confirms adjustment or return to
factory settings |
One flash (2 s) | Indicates the failure of the attempt to adjust zero point or span point, or to return to factory adjustment | |
Off | No power supply or electronics failure | |||
Fast flashing (0.2 s interval) | Auto-zero is executed (first time 90 min after start / reset) |
EE600 with 2-wire Analogue Output
S1 | S2 | MR1) | S3 | S4 | Time | S5 | S6 | Unit | S72) | S8 | Auto-zero3) | S9 | Setting4) | S10 | MD5) |
0 | 0 | 100 % | 0 | 0 | 50 ms | 0 | 0 | Pa | – | 0 | On | 0 | DIP switches | 0 | Bidirectional |
1 | 0 | 75 % | 1 | 0 | 500 ms | 1 | 0 | mbar | – | 1 | Off | 1 | PCS10 | 1 | Unidirectional |
0 | 1 | 50 % | 0 | 1 | 2 s | 0 | 1 | inch WC | |||||||
1 | 1 | 25 % | 1 | 1 | 4 s | 1 | 1 | kPa |
- Measuring range 2) No function 3) Auto-zero version only 4) These and further settings can be changed with PCS10 via USB configuration adapter (HA011066) while DIP switch S9 = 1 5) Measuring direction
Measuring range examples: S1 = 1, S2 = 0, S9 = 0, S10 = 1 S1 = 0, S2 = 0, S9 = 0, S10 = 0 0…750 Pa or 0…7 500 Pa ±1 000 Pa or ±10 000 Pa or customised measuring range
PLEASE NOTE
With the 2-wire version, manual zero point adjustment is only possible every 90 minutes if an auto-zero valve is present.
E+E Elektronik Ges.m.b.H. Langwiesen 7
4209 Engerwitzdorf | Austria T +43 7235 605-0
- F +43 7235 605-8
- info@epluse.com www.epluse.com
QG_EE600_bidirectional | Version v1.0 | 10-2024 | All rights reserved | 350212
FAQs
- Can the EE600 be used outdoors?
The sensor’s IP65/NEMA 4 enclosure makes it resistant to dust and moisture, suitable for some outdoor applications as long as it’s within the specified temperature range. - What gases can it measure?
It is compatible with air and non-flammable, non-aggressive gases only. - How is it calibrated or configured?
The device can be set up using DIP switches and push buttons or through an optional USB adapter with dedicated configuration software.