User Guide for E Plus E models including: EE600 Differential Pressure Sensor, EE600, Differential Pressure Sensor, Pressure Sensor

Wolfgang Aichberger | E E Elektronik Ges.m.b.H.

EE600 nyomáskülönbség távadó gyors használati utasítás

Nyomáskülönbség távadók | HVAC | Sensortech-Pro

Quick Guide


File Info : application/pdf, 2 Pages, 753.34KB

PDF preview unavailable. Download the PDF instead.

EE600-nyomaskulonbseg-tavado-gyorshasznalati
Quick Guide
EE600 - Differential Pressure Sensor
PLEASE NOTE Find this document and further product information on our website at www.epluse.com/ee600.

Electrical Connection
WARNING
Incorrect installation, wiring or power supply may cause overheating and therefore personal injuries or damage to property. It is essential that the cables are not under voltage during installation. No voltage must be applied when the product is connected or disconnected. For correct cabling of the device, always observe the presented wiring diagram for the product version used. The manufacturer cannot be held responsible for personal injuries or damage to property as a result of incorrect handling, installation, wiring, power supply and maintenance of the device.

Analogue Output
P1o5w-e3r5sVupDpCly 2244 VVAACC ±±2200 %% 15 - 35 V DC

Digital Output

+

Power supply

~

24 V AC ±20 %

15 - 35 V DC

-

~

V+

1

GND

2

A (=D+)

3

RS485

B (=D-)

4

Installation
Pressure Connection

Mounting Examples

Use a Ø7.5 mm drill for installing the pressure connection nipples into the duct.

User Interface - LED Indication

Green LED Flashing (1 s interval)
One flash (2 s) Off Fast flashing (0.2 s interval)

EE600 operates normally, the measured data is within the selected measuring range Confirms adjustment or return to factory settings No power supply or electronics failure Auto-zero is executed, first time 10 s after start / reset

Red LED Flashing (1 s interval)
One flash (2 s)

The measured data is out of the selected range (overload or reversed pressure connection) Indicates the failure of the attempt to adjust zero point or span point, or to return to factory adjustment

EE600 with Analogue Output

S1 S2 MR1) S3 S4 Time S5 S6 Unit S7 DPB2) S8

Output

S9 Setting3)

0

0 100 % 0

0 50 ms 0

0

Pa

0 on 0 0 - 10 V/ 4 - 20 mA 0 DIP switches

1

0 75 % 1

0 500 ms 1

0

mbar

1 off 1 0 - 5 V / 0 - 20 mA 1

PCS10

0

1 50 % 0

1

2 s

0

1 inch WC

1

1 25 % 1

1

4 s

1

1

kPa

1) Measuring range 2) Display backlight 3) These and further settings can be changed with PCS10 via USB configuration adapter (HA011066) while DIP switch S9 = 1. Only available with version with 10 DIP switches.

E+E Elektronik Ges.m.b.H. Langwiesen 7 4209 Engerwitzdorf | Austria T +43 7235 605-0 F +43 7235 605-8 info@epluse.com www.epluse.com

QG_EE600 | Version v1.6 | 10-2024 | All rights reserved | 350197

EE600 with RS485 Interface Electronics Board Layout
The bus termination shall be realized with the 120  resistor (slide switch on board).

Termination resistor 120  slide switch: 1=ON, 0=OFF

Status LED USB configuration adapter

Address switch
Push buttons for span and zero point adjustment

Display connector
Supply and RS485 terminals

Quick Guide EE600

Address Setting
Address Switch
1 0 00000 000
1 0 11010 000

Option
Address setting via PCS10 Product Configuration Software (= factory setting) All DIP switches at position 0  factory-set default address (43DEC, 0x2B) applicable, can be changed via software (PCS10 or Modbus protocol, permitted values: 1...247). Example: Address is set via configuration software.
Address setting via DIP switches DIP switches in any other position than 0 indicate the effective Modbus address which overrules the factory setting and any Modbus address set via PCS10 or Modbus command (permitted values: 1...247). Example: Address set to 11DEC (0000 1011BIN).

Communication Setttings
Modbus

Baud rate Data bits Parity Stop bits Modbus address

Factory settings As specified in the order code 8 Even 1 43

User selectable values (via PCS10) 9 600, 19 200, 38 400, 57 600, 76 800, 115 200 8 None, odd, even 1, 2 1...247

Modbus Protocol
The recommended settings for multiple devices in a Modbus RTU network are 9600, 8, even, 1.
Address, Baud rate, parity and stop bits can be set via:
 PCS10, Product Configuration Software and the USB configuration adapter HA011066.  Modbus protocol in the register 1 (0x00) and 2 (0x01).
Refer to Application Note Modbus AN0103 (available on www.epluse.com/ee600).
The measured values are saved as 32 bit floating point value and as 16 bit signed integer value, see Modbus register map below.

Modbus Register Map

FLOAT 32

Parameter

Unit

Register number1) [DEC]

Register address2) [HEX]

Read register: function code 0x03 / 0x04

Differential pressure Differential pressure

mm H2O mbar

1211 1213

4BA 4BC

Differential pressure

Pa

1215

4BE

Differential pressure

kPa

1217

4C0

Differential pressure inch WC

1219

4C2

Air velocity

m/s

1041

410

Air velocity

ft/min

1043

412

Volume flow

m3/h

1055

41E

Volume flow

l/s

1057

420

Volume flow

m3/s

1059

422

Volume flow

ft3/min

1181

49C

Filter monitoring

%

1075

432

Level indicator

cm

1077

434

Level indicator

inch

1079

436

1) Register number starts from 1 2) Register address starts from 0 3) 1xx is scale. E.g. for 1:100, reading of 2550 is equivalent to 25.5

Scale3)
10 100
1 1000 100 100
1 1 1 1000 1 10 10 10

INT16

Register number1)

Register address2)

[DEC]

[HEX]

4106 4107 4108 4109 4110 4021 4022 4028 4029 4030 4091 4038 4039 4040

1009 100A 100B 100C 100D FB4 FB5 FBB FBC FBD FFA FC5 FC6 FC7



References