Quick Guide
EE600 - Differential Pressure Sensor

PLEASE NOTE Find this document and further product information on our website at www.epluse.com/ee600.

Electrical Connection
WARNING
Incorrect installation, wiring or power supply may cause overheating and therefore personal injuries or damage to property. It is essential that the cables are not under voltage during installation. No voltage must be applied when the product is connected or disconnected. For correct cabling of the device, always observe the presented wiring diagram for the product version used. The manufacturer cannot be held responsible for personal injuries or damage to property as a result of incorrect handling, installation, wiring, power supply and maintenance of the device.

Analogue Output
P1o5w-e3r5sVupDpCly 15 - 35 V DC
OUT1

Installation
Pressure Connection

Mounting Examples

Use a Ø7.5 mm drill for installing the pressure connection nipples into the duct.

User Interface - LED Indication

Green LED

Flashing (1 s interval) EE600 operates normally, the

measured data is within the selected

measuring range

One flash (2 s)

Confirms adjustment or return to

factory settings

Off

No power supply or

electronics failure

Fast flashing

Auto-zero is executed

(0.2 s interval)

(first time 90 min after start / reset)

Red LED Flashing (1 s interval)
One flash (2 s)

The measured data is out of the selected range (overload or reversed pressure connection) Indicates the failure of the attempt to adjust zero point or span point, or to return to factory adjustment

EE600 with 2-wire Analogue Output

S1 S2 MR1) S3 S4 Time S5 S6 Unit

0 0 100 % 0 0 50 ms 0 0

Pa

1 0 75 % 1 0 500 ms 1 0 mbar

S72) S8 -0 -1

Auto-zero3) On Off

S9 Setting4) S10 0 DIP switches 0 1 PCS10 1

MD5) Bidirectional Unidirectional

0 1 50 % 0 1 2 s 0 1 inch WC

1 1 25 % 1 1 4 s 1 1 kPa

1) Measuring range 2) No function 3) Auto-zero version only 4) These and further settings can be changed with PCS10 via USB configuration adapter (HA011066) while DIP switch S9 = 1 5) Measuring direction

Measuring range examples: S1 = 1, S2 = 0, S9 = 0, S10 = 1 S1 = 0, S2 = 0, S9 = 0, S10 = 0

0...750 Pa or 0...7 500 Pa ±1 000 Pa or ±10 000 Pa or customised measuring range

PLEASE NOTE

With the 2-wire version, manual zero point adjustment is only possible every 90 minutes if an auto-zero valve is present.

E+E Elektronik Ges.m.b.H. Langwiesen 7 4209 Engerwitzdorf | Austria T +43 7235 605-0 F +43 7235 605-8 info@epluse.com www.epluse.com

QG_EE600_bidirectional | Version v1.0 | 10-2024 | All rights reserved | 350212

