DAUDIN-LOGO

DAUDIN MELSEC-Q Modbus TCP Connection

DAUDIN MELSEC-Q Modbus TCP Connection-PRODUCT

Product Information

The 2302EN V2.0.0 and MELSEC-Q Modbus TCP Connection Operating Manual provides instructions on how to connect and configure a remote I/O module system using various components including a Modbus TCP-to-Modbus RTU/ASCII gateway, a Master Modbus RTU main controller, Digital Input and Output modules, and Power Supply modules. The gateway is used externally to connect with MELSEC-Q series’ communication port (Modbus TCP) and the main controller is in charge of the management and dynamic configuration of I/O parameters and so on. The power module is standard for remote I/Os and users can choose the model or brand of power module they prefer.

Product Usage Instructions

Remote I/O Module System Configuration List

The Remote I/O Module System Configuration List provides a list of the various modules that can be used to configure the system including the Gateway, Main Controller, Digital Input and Output modules, and Power Supply modules. Each module has a Part No., Specification, and Description.

Gateway Parameter Settings

The Gateway Parameter Settings section details how to connect a gateway to MELSEC-Q series. For detailed information regarding these settings, please refer to the Series Product Manual.

i-Designer Program Setup

  1. Make sure that the module is powered and connected to the gateway module using an Ethernet cable.
  2. Launch the i-Designer software.
  3. Select M Series Module Configuration.
  4. Click on the Setting Module icon.
  5. Enter the Setting Module page for M-series.
  6. Select the mode type based on the connected module.
  7. Click on Connect.
  8. Configure the Gateway Module IP Settings. Note: The IP address must be in the same domain as the MELSEC-Q controller.
  9. Configure the Gateway Module Operational Modes. Note: Set Group 1 as Slave and set the gateway to use the first set of RS485 port to connect to the main controller (GFMS-RM01N).

MELSEC-Q series Connection Setup

The MELSEC-Q series Connection Setup chapter explains how to use the GX Works2 program to use the QJ71MT91 module to connect MELSEC-Q series to a gateway module and add a remote I/O module. For detailed information, please refer to the MELSEC-Q Series Manual.

MELSEC-Q series Hardware Connections

  1. The QJ71MT91 module’s Ethernet port is at its bottom center and can be connected to the gateway.

MELSEC-Q series IP Address and Connection Setup

  1. Launch GX Works 2 and right-click on the Intelligent Function Module menu under Project on the left side.
  2. Click on New Module to create a QJ71MB91 module.

Remote I/O Module System Configuration List

Part No. Specification Description
GFGW-RM01N  

Modbus TCP-to-Modbus RTU/ASCII, 4 Ports

Gateway
GFMS-RM01S Master Modbus RTU, 1 Port Main Controller
GFDI-RM01N Digital Input 16 Channel Digital Input
GFDO-RM01N Digital Output 16 Channel / 0.5A Digital Output
GFPS-0202 Power 24V / 48W Power Supply
GFPS-0303 Power 5V / 20W Power Supply

Product Description

I. The gateway is used externally to connect with MELSEC-Q series’ communication port (Modbus TCP)
II. The main controller is in charge of the management and dynamic configuration of I/O parameters and so on.
III. The power module is standard for remote I/Os and users can choose the model or brand of power module they prefer.

Gateway Parameter Settings

This section details how to connect a gateway to MELSEC-Q series. For detailed information DAUDIN MELSEC-Q Modbus TCP Connection-FIG1, please refer to theDAUDIN MELSEC-Q Modbus TCP Connection-FIG1 Series Product Manual

Designer Program Setup

  1. Make sure that the module is powered and connected to the gateway module using an Ethernet cableDAUDIN MELSEC-Q Modbus TCP Connection-FIG2
  2. Click to launch the softwareDAUDIN MELSEC-Q Modbus TCP Connection-FIG3
  3. Select “M Series Module Configuration”DAUDIN MELSEC-Q Modbus TCP Connection-FIG4
  4. Click on the “Setting Module” iconDAUDIN MELSEC-Q Modbus TCP Connection-FIG5
  5. Enter the “Setting Module” page for M-seriesDAUDIN MELSEC-Q Modbus TCP Connection-FIG6
  6. Select the mode type based on the connected moduleDAUDIN MELSEC-Q Modbus TCP Connection-FIG7
  7. Click on “Connect”Note: The IP address must be in the same domain as the MELSEC-Q controllerDAUDIN MELSEC-Q Modbus TCP Connection-FIG8
  8. Gateway Module IP SettingsDAUDIN MELSEC-Q Modbus TCP Connection-FIG9Note: The IP address must be in the same domain as the MELSEC-Q controller
  9. Gateway Module Operational ModesDAUDIN MELSEC-Q Modbus TCP Connection-FIG10

Note: Set Group 1 as Slave and set the gateway to use the first set of RS485 port to connect to the main controller (GFMS-RM01N)

MELSEC-Q series Connection Setup

This chapter explains how to use the GX Works2 program to use the QJ71MT91 module to connect MELSEC-Q series to a gateway module and add a remote I/O module. For detailed information, please refer to the “MELSEC-Q Series Manual

MELSEC-Q series Hardware Connections

  1. The QJ71MT91 module’s Ethernet port is at its bottom center and can be connected to the gatewayDAUDIN MELSEC-Q Modbus TCP Connection-FIG11

MELSEC-Q series IP Address and Connection Setup

  1. Launch GX Works 2 and right click on the “Intelligent Function Module” menu under “Project” on the left side. Then click on “New Module” to create a “QJ71MB91” moduleDAUDIN MELSEC-Q Modbus TCP Connection-FIG12
  2. Launch GX Works 2 and select the “Intelligent Function Module” menu under “Project” on the left side. Then click on “Switch Setting” in the “QJ71MT91” menuDAUDIN MELSEC-Q Modbus TCP Connection-FIG13
  3. Set “IP Address” to the same domain as the gateway domain at 192.168.1.XXX.DAUDIN MELSEC-Q Modbus TCP Connection-FIG14
  4. Click on “Automatic_Communication_Parameter” to set up reading and writing methodsDAUDIN MELSEC-Q Modbus TCP Connection-FIG15
  5. Click on “Auto_Refresh” to set up the internal register for reading and writingDAUDIN MELSEC-Q Modbus TCP Connection-FIG16

Simple Program Demonstration using MELSEC-Q series and DAUDIN MELSEC-Q Modbus TCP Connection-FIG1

The DAUDIN MELSEC-Q Modbus TCP Connection-FIG1’s read register address is 4096, which is D0 for the corresponding internal register of the controller.
And the DAUDIN MELSEC-Q Modbus TCP Connection-FIG1’s write register address is 8192, which is D300 for the corresponding internal register of the controller.
Therefore, when you want to control the program, you can just use the internal register to control the writing and reading.

DAUDIN MELSEC-Q Modbus TCP Connection-FIG17

Documents / Resources

DAUDIN MELSEC-Q Modbus TCP Connection [pdf] User Manual
MELSEC-Q Modbus TCP Connection, MELSEC-Q, Modbus TCP Connection, Modbus

References

Leave a comment

Your email address will not be published. Required fields are marked *