Elexant 450c-Modbus
Modbus Protocol Interface Mapping
Firmware nga bersyon V2.1.1
1. PASIUNA
This manual details the Modbus registers of the Raychem Elexant 450c-Modbus. It is intended to be used by the users’ system integrators who wish to interface with their external device (i.e. DCS or Building management system -BMS- system) to the using the Modbus protocol. The manual includes details of the system’s current configuration, availability resources, set-up parameters, current conditions, alarm status, log info and numerous other fixed and variable data points.
1.1 Giunsa Paggamit Kini nga Manwal
The Elexant 450c-Modbus register can be accessed by DCS or BMS systems. However, this should only be done by expert users who understand that the system makes use of extensive semaphore fields to assure synchronization between the possibility of multiple users and conflicting instructions. These portions of the Modbus register map provide access to the current set-up and real time values being measured by the system. A snap shot of the current conditions, data for trending, alarm status, the current setting for the alarm thresholds and setpoints can be easily read without any risk to the system performance.
Ang tibuok Modbus register map gilakip niini nga dokumento para sa pagkakompleto. Ang pagsulat sa database naa sa kapabilidad sa kadaghanan sa mga aparato sa host sa Modbus. Bisan pa, kusganon namon nga girekomenda nga ang mga integrator sa sistema nga nagsulat sa database kinahanglan nga hingpit nga sulayan ang ilang sistema aron masiguro nga kini nagtrabaho sa husto ug nga wala’y wala damha nga mga sangputanan.
1.2 Mga Komunikasyon sa Modbus
Ang controller naglihok isip Modbus ulipon device. Ang modbus master device makabasa ug makasulat sa controller. Gitugotan niini ang posibilidad sa pagmonitor, pag-configure ug view ang mga alarma sa layo. Ang protocol nga gigamit mao ang Modbus RTU pinaagi sa RS485.
Variable | Deskripsyon | Default | Range/mga kapilian |
Address | Modbus Station Address nga gigamit sa pag-ila sa controller. | 1 | 1 hangtod 247 |
Baud | Ang data rate diin ang mga komunikasyon mahitabo sa serial network. | 9600 | 2400, 4800, 9600, 19200 |
Pagkaparehas | Parity Naghubit sa matang sa parity bit nga gamiton sa bisan hain sa tulo ka serial communications ports. | Wala | Wala, Katingad-an, Bisan |
Hunong ang mga Bits | Naghubit sa gidaghanon sa mga stop bit nga gigamit sa bisan asa sa tulo ka serial communications ports. | 1 | 1,2 |
Ang mga default sa host mao ang:
- Adres sa Modbus: 1
- Rate sa Baud: 9600
Ang standard nga configuration mao ang: 8 data bits, walay parity ug one stop bit.
Ang dip switch (ubos sa terminal 26 ug 27):
Butang | Resistor |
1 – | Ibira paubos ang resistor |
2 – | Ipataas ang resistor |
3 – | Resistor sa pagtapos |
Iduso ang buton sa ON (sama sa gipakita sa pana) nga kilid magkonektar sa katugbang nga resistor sa.
2. MODBUS REGISTER MAP
2.1 Alarm Status Coils
Modbus Function Code: 1
Adres sa Pagsugod sa Modbus: 0
Gidak-on sa Modbus Block: 17
Gidaghanon sa mga Bloke: 1
Deskripsyon | Adres sa Modbus | Kalihokan | Mga komento |
High TS 1 Alarm | 0 | 1 | 0 = walay alarma, 1 = alarma |
Low TS 1 Alarm | 1 | 1 | 0 = walay alarma, 1 = alarma |
TS 1 Kapakyasan | 2 | 1 | 0 = walay alarma, 1 = alarma |
High TS 2 | 3 | 1 | 0 = walay alarma, 1 = alarma |
Low TS 2 | 4 | 1 | 0 = walay alarma, 1 = alarma |
TS 2 Kapakyasan | 5 | 1 | 0 = walay alarma, 1 = alarma |
Internal nga Sayop | 15 | 1 | 0 = walay internal nga sayop, 1 = internal nga sayop |
Status sa Alarm sa Panel | 16 | 1 | 0 = walay alarma, 1 = alarma |
2.2 Controller Setup Parameters
Modbus Function Code: 1,5,15
Adres sa Pagsugod sa Modbus: 145
Gidak-on sa Modbus Block: 9
Gidaghanon sa mga Bloke: 1
Deskripsyon | Adres sa Modbus | Kalihokan | Mga komento |
TS1 Fail Mode | 145 | 1, 5, 15 | 0 = Napakyas, 1 = Napakyas sa |
TS2 Fail Mode | 146 | 1, 5, 15 | 0 = Napakyas, 1 = Napakyas sa |
Programa sa Pagsulay | 147 | 1, 5, 15 | 0 = dili, 1 = oo, ang programa sa pagsulay nagdagan |
Alarm Buzzer | 148 | 1, 5, 15 | 0 = dili, buzzer off 1 = oo, buzzer on |
TS1 high alarm feature off | 149 | 1, 5, 15 | 0 = alarm active, 1 = alarm deactive |
TS1 high alarm feature off | 150 | 1, 5, 15 | 0 = alarm active, 1 = alarm deactive |
TS1 low alarm feature off | 151 | 1, 5, 15 | 0 = alarm active, 1 = alarm deactive |
TS1 low alarm feature off | 152 | 1, 5, 15 | 0 = alarm active, 1 = alarm deactive |
Pagkontrol sa Alarm sa Panel | 153 | 1, 5, 15 | 0 = alarma deaktibo, 1 = alarma aktibo |
2.3 Kahimtang sa Controller
Modbus Function Code: 2
Adres sa Pagsugod sa Modbus: 3
Gidak-on sa Modbus Block: 3
Gidaghanon sa mga Bloke: 1
Deskripsyon | Adres sa Modbus | Kalihokan | Mga komento |
Hilaw nga Switch Output1 | 3 | 2 | 0 = HC1 relay off, 1 = HC1 relay on |
Kahimtang sa Keylock | 4 | 2 | 0 = dili, 1 = oo, gi-lock |
Hilaw nga Switch Output2 | 5 | 2 | 0 = HC2 relay off, 1 = HC2 relay on |
2.4 INPUT Parameters
Modbus Function Code: 3, 6, 16
Adres sa Pagsugod sa Modbus: 0
Gidak-on sa Modbus Block: 20
Gidaghanon sa mga Bloke: 1
Deskripsyon | Adres sa Modbus | Kalihokan | Mga komento | Mga yunit | Pag-scale |
Control Temperature Setpoint 1 | 0 | 3, 6, 16 | 0°C to 80°C (0°C to 245°C for PT100) | °C | ika-10* |
PASC Minimum Pipe Size 2 | 1 | 3, 6, 16 | 10, 15, 20, 25, 32, 40, 50, 60, 70, 80, 100, 125 if invalid value 25 is used | DN | 1 |
Switch Control Mode | 2 | 3, 6, 16 | 4 = Line/Line, 5 = PASC/PASC, 6 = Line/PASC, 7 = PASC/Line, 8 = Line/OFF, 9 = PASC/OFF, 10 = OFF/Line, 11 = OFF/PASC, 12 = OFF/OFF |
– | 1 |
Deadband 1 | 3 | 3, 6, 16 | 1.0°C hangtod sa 5°C | °C | ika-10* |
PASC Minimum Ambient Temperature 1 | 4 | 3, 6, 16 | -40°C hangtod 0°C | °C | ika-10* |
PASC Minimum Pipe Size 1 | 5 | 3, 6, 16 | 10, 15, 20, 25, 32, 40, 50, 60, 70, 80, 100, 125 if invalid value 25 is used | DN | 1 |
PASC Power Adjust | 6 | 3, 6, 16 | 70,80,90,100,110,120,130,140 | % | 1 |
Pag-setup sa Sensor | 7 | 3, 6, 16 | bit 1 = TS 1 assign alang sa Circuit 1 bit 2 = TS 2 assign alang sa Circuit 1 bit 5 = TS 1 assign alang sa Circuit 2 bit 6 = TS 2 assign alang sa Circuit 2 gamay 0,3,4,7 = NA 0 = Dili (Dili pilion) 1 = Oo (Pilia) |
– | 1 |
Pinulongan | 8 | 3, 6, 16 | 0 = DANISH, 1 = GERMAN, 2 = DUTCH, 3 = ENGLISH, 4 = FRENCH, 5 = ITALIAN, 6 = SWEDISH, 7 = NORWEGIAN, 8 = FINNISH, 9 = RUSSIAN, 10 = CZECH, 11 = POLISH |
– | 1 |
Nasud | 9 | 3, 6, 16 | 0 = GERMANY, 1 = AUSTRIA, 2 = SWITZERLAND, 3 = UK, 4 = FRANCE, 5 = ITALY, 6 = POLAND, 7 = CZECH_REPUBLIC, 8 = DENMARK, 9 = BELGIUM, 10 = RUSSIA, 11 = CHINA, 12 = JAPAN, 13 = SWEDEN, 14 = NORWAY, 15 = LITHUANIA, 16 = SLOVAKIA, 17 = NETHERLANDS, 18 = FINLAND, 19 = IRELAND |
– | 1 |
Uri sa kable 1 | 10 | 3, 6, 16 | 0 = 10XL2_ZH, 1 = 15XL2_ZH, 2 = 26XL2_ZH, 3 = 31XL2_ZH, 4 = FS_C10_2X, 5 = OTHER |
– | 1 |
Uri sa kable 2 | 11 | 3, 6, 16 | 0 = 10XL2_ZH, 1 = 15XL2_ZH, 2 = 26XL2_ZH, 3 = 31XL2_ZH, 4 = FS_C10_2X, 5 = OTHER |
– | 1 |
Deadband 2 | 12 | 3, 6, 16 | 1.0°C hangtod sa 5°C | °C | ika-10* |
Date-Year | 13 | 3, 6, 16 | 00 – 99 | tuig | 1 |
Date-Month | 14 | 3, 6, 16 | 1 – 12 | bulan | 1 |
Date-Day | 15 | 3, 6, 16 | 1 – 31 | adlaw | 1 |
Time-Hour | 16 | 3, 6, 16 | 0 – 23 | oras | 1 |
Time-Minute | 17 | 3, 6, 16 | 0 – 59 | minuto | 1 |
Control Temperature Setpoint 2 | 18 | 3, 6, 16 | 0°C to 80°C (0°C to 245°C for PT100) | °C | ika-10* |
PASC Minimum Ambient Temperature 2 | 19 | 3, 6, 16 | -40°C hangtod 0°C | °C | ika-10* |
* Temperatura nga gipakita sa 1/10th sa °C (exampug: 10°C = 100)
2.5 Temperature Sensor Parameters
Modbus Function Code: 3, 6, 16
Adres sa Pagsugod sa Modbus: 20
Gidak-on sa Modbus Block: 4
Gidaghanon sa mga Bloke: 1
Deskripsyon | Adres sa Modbus | Kalihokan | Mga komento | Mga yunit | Pag-scale |
High TS 1 Alarm Setpoint** | 20 | 3, 6, 16 | 2°C – 90°C (2°C to 250°C for PT100) |
°C | ika-10* |
Low TS 1 Alarm Setpoint** | 21 | 3, 6, 16 | -40°C – 78°C (-40°C to +245°C for PT100) |
°C | ika-10* |
High TS 2 Alarm Setpoint** | 22 | 3, 6, 16 | 2°C – 90°C (2°C to 250°C for PT100) |
°C | ika-10* |
Low TS 2 Alarm Setpoint** | 23 | 3, 6, 16 | -40°C – 78°C (-40°C to 245°C for PT100) |
°C | ika-10* |
* Temperatura nga gipakita sa 1/10th sa °C (exampug: 10°C = 100)
** Can be disabled through section 2.2
2.6 I-override
Modbus Function Code: 3, 6, 16
Adres sa Pagsugod sa Modbus: 34
Gidak-on sa Modbus Block: 2
Gidaghanon sa mga Bloke: 1
Deskripsyon | Adres sa Modbus | Kalihokan | Mga komento | Mga yunit | Pag-scale |
Hilit nga Override Status 1 | 34 | 3, 6, 16 | 0 = Dili aktibo ang override 1 = Aktibo ang Force on Override 2 = Puwersa nga off Override aktibo |
– | – |
Hilit nga Override Status 2 | 35 | 3, 6, 16 | 0 = Dili aktibo ang override 1 = Aktibo ang Force on Override 2 = Puwersa nga off Override aktibo |
– | – |
2.7 Controller’s Identification Tag
Modbus Function Code: 3, 6, 16
Adres sa Pagsugod sa Modbus: 90
Gidak-on sa Modbus Block: 10
Gidaghanon sa mga Bloke: 1
Deskripsyon | Adres sa Modbus | Kalihokan | Mga komento | Mga yunit | Pag-scale |
Pag-ila sa Controller Tag | 90 hangtod 99 | 3, 6, 16 | Letters(A-Z) numbers(0-9), /.()_-# Two characters per address. String terminators = Null or space Note: LSByte of 99 is always Null. Isulod ang ascii code alang sa mga karakter sa ibabaw, alang sa example, input 0x4142 (Hex or 16706 in Dec) for register 90, and 0x3031 (in Hex or 12337 in Dec) for register 91, then the controller ID will be AB01. |
– | – |
2.8 Console Parameters
Modbus Function Code: 3, 6, 16
Adres sa Pagsugod sa Modbus: 120
Gidak-on sa Modbus Block: 2
Gidaghanon sa mga Bloke: 1
Deskripsyon | Adres sa Modbus | Kalihokan | Mga komento | Mga yunit | Pag-scale |
Keylock Passcode | 120 | 3, 6, 16 | 1 hangtod 9999: Incorrect passcode input will be ignored, and correct input will be valid for 2 minutes. (used to enter the code to unlock access to register 121) |
– | – |
Lock Enable/ Disable | 121 | 3, 6, 16 | 0 = Keylock dili aktibo, 1 = Aktibo ang keylock |
– | – |
2.9 Temperature Sensor Parameters
Modbus Function Code: 3, 6, 16
Adres sa Pagsugod sa Modbus: 147
Gidak-on sa Modbus Block: 1
Gidaghanon sa mga Bloke: 1
Deskripsyon | Adres sa Modbus | Kalihokan | Mga komento | Mga yunit | Pag-scale |
Communications Activity Time-out | 147 | 3, 6, 16 | Used for load shedding and remote override 0-255 | sec | 1 |
2.10 General Controller Information
Modbus Function Code: 4
Adres sa Pagsugod sa Modbus: 0
Gidak-on sa Modbus Block: 4
Gidaghanon sa mga Bloke: 1
Deskripsyon | Adres sa Modbus | Kalihokan | Mga komento | Mga yunit | Pag-scale |
Type sa Device | 0 | 4 | Gitakdang bili = 450 | – | 1 |
Bersyon sa Firmware | 1 | 4 | Firmware Version-Major 0-255 | – | 1 |
Bersyon sa Firmware | 2 | 4 | Firmware Version-Minor 0-255 | – | 1 |
Bersyon sa Firmware | 3 | 4 | Firmware Version-Build 0-255 | – | 1 |
2.11 Dynamic Output Status
Modbus Function Code: 4
Adres sa Pagsugod sa Modbus: 50
Gidak-on sa Modbus Block: 15
Gidaghanon sa mga Bloke: 1
Deskripsyon | Adres sa Modbus | Kalihokan | Mga komento | Mga yunit | Pag-scale |
Control Output Duty Cycle 1 | 50 | 4 | 0 = full off, 100 = full on | % | 1 |
Pagsubay sa Kahimtang sa Pagkontrol | 51 | 4 | 2 digit, ang una para sa circuit 1 ug ang ikaduha para sa circuit 2 (alang sa example, 0 means both are normal, 15 means circuit 1 = force off, circuit 2 = force on) 0 = normal nga pagkontrol sa temperatura 1 = output override force off 2 = test program in progress 5 = output override pwersa sa |
– | 1 |
PASC On-Count 1 | 52 | 4 | sec | 1 | |
PASC Off-Count 1 | 53 | 4 | sec | 1 | |
PASC Next Switch Count 1 | 54 | 4 | sec | 1 | |
PASC Percent On 1 | 55 | 4 | 0 = full off, 100 = full on | % | 1 |
PASC Output State 1 | 56 | 4 | 0 = Off, 1 = On | – | 1 |
PASC Total Time 1 | 57 | 4 | sec | 1 | |
Control Output Duty Cycle 2 | 58 | 4 | 0 = full off, 100 = full on | % | 1 |
PASC On-Count 2 | 59 | 4 | sec | 1 | |
PASC Off-Count 2 | 60 | 4 | sec | 1 | |
PASC Next Switch Count 2 | 61 | 4 | sec | 1 | |
PASC Percent On 2 | 62 | 4 | 0=full off, 100=full on | % | 1 |
PASC Output State 2 | 63 | 4 | 0 = Off, 1 = On | – | 1 |
PASC Total Time 2 | 64 | 4 | sec | 1 |
2.12 Analog Readings
Modbus Function Code: 4
Adres sa Pagsugod sa Modbus: 81
Gidak-on sa Modbus Block: 2
Gidaghanon sa mga Bloke: 1
Deskripsyon | Adres sa Modbus | Kalihokan | Mga komento | Mga yunit | Pag-scale |
Current TS 1 Temperature | 81 | 4 | TS 1 kapakyasan = +3000.0°C TS 1 wala gigamit = +3200.0°C | °C | ika-10* |
Current TS 2 Temperature | 82 | 4 | TS 2 kapakyasan = +3000.0°C TS 2 wala gigamit = +3200.0°C | °C | ika-10* |
* Temperatura nga gipakita sa 1/10th sa °C (exampug: 10°C = 100)
2.13 Disclaimer
MODBUS map information is proprietary and confidential. Use of this information is permitted solely in order to implement a communications link between customer equipment and Raychem controllers. It may not be used for any other purpose, and it is not to be disclosed to 3rd parties without the written consent of Chemelex Thermal LLC.
Belgium / Belgium
Tel +32 16 21 35 02
Fax +32 16 21 36 04
SalesBelux@chemelex.com
Bulgaria
Tel +359 2 973 33 73
SalesEE@chemelex.com
Česká Republika
Tel +420 606 069 618 (Comm)
+420 602 232 969 (Ind)
infoCZ@chemelex.com
Danmark
Tel +45 70 11 04 00
SalesDK@chemelex.com
Deutschland
Tel 0800 181 82 05
SalesDE@chemelex.com
España
Tel +34 911 59 30 60
Fax +34 900 98 32 64
SalesES@chemelex.com
France
Tél 0800 90 60 45
SalesFR@chemelex.com
Hrvatska
Tel +385 51 225 073 (Comm)
+385 1 605 01 88 (Ind)
SalesEE@chemelex.com
Italy
Tel +39 02 577 61 51
Fax +39 02 577 61 55 28
SalesIT@chemelex.com
Lietuva/Latvija/Eesti
Tel +370 698 411 56
SalesEE@chemelex.com
Magyarország
Tel +36 1 253 76 17
SalesHU@chemelex.com
Nederland
Tel 0800 022 49 78
SalesNL@chemelex.com
Norge
Tel +47 66 81 79 90
SalesNO@chemelex.com
Österreich
Tel 0800 29 74 10
SalesAT@chemelex.com
Polska
Tel +48 22 331 29 50
Fax +48 22 331 29 51
SalesPL@chemelex.com
Казахстан
Tel +7 7112 31 67 03170
SalesKZ@chemelex.com
Serbia ug Montenegro
Tel +386 41 665 634 (Comm)
+381 230 439 519 (Ind)
SalesEE@chemelex.com
Schweiz/Suisse/Svizzera
Tel +41 (41) 766 30 80
Fax +41 (41) 766 30 81
infoCH@chemelex.com
Suomi
Puh 0800 11 67 99
SalesFI@chemelex.com
Sverige
Tel +46 31 335 58 00
SalesSE@chemelex.com
Türkiye
Tel +90 545 284 09 05
SalesEE@chemelex.com
UK / Ireland
Tel 0800 969 013
SalesUK@chemelex.com
©2025 Chemelex. Ang tanan nga mga marka ug logo sa Chemelex gipanag-iya o lisensyado sa Chemelex Europe GmbH o sa mga kaubanan niini. Ang tanan nga ubang mga marka sa pamatigayon gipanag-iya sa ilang tag-iya. Ang Chemelex adunay katungod sa pag-usab sa mga detalye nga walay pahibalo.
RAYCHEM-OM-EU1850-Elexant450cModbus-ML-2504