1. PASIUNA

This manual details the Modbus registers of the Raychem Elexant 450c-Modbus. It is intended to be used by the users’ system integrators who wish to interface with their external device (i.e. DCS or Building management system -BMS- system) to the using the Modbus protocol. The manual includes details of the system’s current configuration, availability resources, set-up parameters, current conditions, alarm status, log info and numerous other fixed and variable data points.

1.1 Giunsa Paggamit Kini nga Manwal

The Elexant 450c-Modbus register can be accessed by DCS or BMS systems. However, this should only be done by expert users who understand that the system makes use of extensive semaphore fields to assure synchronization between the possibility of multiple users and conflicting instructions. These portions of the Modbus register map provide access to the current set-up and real time values being measured by the system. A snap shot of the current conditions, data for trending, alarm status, the current setting for the alarm thresholds and setpoints can be easily read without any risk to the system performance.

Ang tibuok Modbus register map gilakip niini nga dokumento para sa pagkakompleto. Ang pagsulat sa database naa sa kapabilidad sa kadaghanan sa mga aparato sa host sa Modbus. Bisan pa, kusganon namon nga girekomenda nga ang mga integrator sa sistema nga nagsulat sa database kinahanglan nga hingpit nga sulayan ang ilang sistema aron masiguro nga kini nagtrabaho sa husto ug nga wala’y wala damha nga mga sangputanan.

1.2 Mga Komunikasyon sa Modbus

Ang controller naglihok isip Modbus ulipon device. Ang modbus master device makabasa ug makasulat sa controller. Gitugotan niini ang posibilidad sa pagmonitor, pag-configure ug view ang mga alarma sa layo. Ang protocol nga gigamit mao ang Modbus RTU pinaagi sa RS485.

Variable Deskripsyon Default Range/mga kapilian
Address Modbus Station Address nga gigamit sa pag-ila sa controller. 1 1 hangtod 247
Baud Ang data rate diin ang mga komunikasyon mahitabo sa serial network. 9600 2400, 4800, 9600, 19200
Pagkaparehas Parity Naghubit sa matang sa parity bit nga gamiton sa bisan hain sa tulo ka serial communications ports. Wala Wala, Katingad-an, Bisan
Hunong ang mga Bits Naghubit sa gidaghanon sa mga stop bit nga gigamit sa bisan asa sa tulo ka serial communications ports. 1 1,2

Ang mga default sa host mao ang:

  • Adres sa Modbus: 1
  • Rate sa Baud: 9600

Ang standard nga configuration mao ang: 8 data bits, walay parity ug one stop bit.

Ang dip switch (ubos sa terminal 26 ug 27):

Butang Resistor
1 – Ibira paubos ang resistor
2 – Ipataas ang resistor
3 – Resistor sa pagtapos

Iduso ang buton sa ON (sama sa gipakita sa pana) nga kilid magkonektar sa katugbang nga resistor sa.

Raychem Elexant 450c-Modbus Modbus Protocol Interface Mapping - 2

2. MODBUS REGISTER MAP

2.1 Alarm Status Coils

Modbus Function Code: 1

Adres sa Pagsugod sa Modbus: 0

Gidak-on sa Modbus Block: 17

Gidaghanon sa mga Bloke: 1

Deskripsyon Adres sa Modbus Kalihokan Mga komento
High TS 1 Alarm 0 1 0 = walay alarma, 1 = alarma
Low TS 1 Alarm 1 1 0 = walay alarma, 1 = alarma
TS 1 Kapakyasan 2 1 0 = walay alarma, 1 = alarma
High TS 2 3 1 0 = walay alarma, 1 = alarma
Low TS 2 4 1 0 = walay alarma, 1 = alarma
TS 2 Kapakyasan 5 1 0 = walay alarma, 1 = alarma
Internal nga Sayop 15 1 0 = walay internal nga sayop, 1 = internal nga sayop
Status sa Alarm sa Panel 16 1 0 = walay alarma, 1 = alarma
2.2 Controller Setup Parameters

Modbus Function Code: 1,5,15

Adres sa Pagsugod sa Modbus: 145

Gidak-on sa Modbus Block: 9

Gidaghanon sa mga Bloke: 1

Deskripsyon Adres sa Modbus Kalihokan Mga komento
TS1 Fail Mode 145 1, 5, 15 0 = Napakyas, 1 = Napakyas sa
TS2 Fail Mode 146 1, 5, 15 0 = Napakyas, 1 = Napakyas sa
Programa sa Pagsulay 147 1, 5, 15 0 = dili, 1 = oo, ang programa sa pagsulay nagdagan
Alarm Buzzer 148 1, 5, 15 0 = dili, buzzer off 1 = oo, buzzer on
TS1 high alarm feature off 149 1, 5, 15 0 = alarm active, 1 = alarm deactive
TS1 high alarm feature off 150 1, 5, 15 0 = alarm active, 1 = alarm deactive
TS1 low alarm feature off 151 1, 5, 15 0 = alarm active, 1 = alarm deactive
TS1 low alarm feature off 152 1, 5, 15 0 = alarm active, 1 = alarm deactive
Pagkontrol sa Alarm sa Panel 153 1, 5, 15 0 = alarma deaktibo, 1 = alarma aktibo
2.3 Kahimtang sa Controller

Modbus Function Code: 2

Adres sa Pagsugod sa Modbus: 3

Gidak-on sa Modbus Block: 3

Gidaghanon sa mga Bloke: 1

Deskripsyon Adres sa Modbus Kalihokan Mga komento
Hilaw nga Switch Output1 3 2 0 = HC1 relay off, 1 = HC1 relay on
Kahimtang sa Keylock 4 2 0 = dili, 1 = oo, gi-lock
Hilaw nga Switch Output2 5 2 0 = HC2 relay off, 1 = HC2 relay on
2.4 INPUT Parameters

Modbus Function Code: 3, 6, 16

Adres sa Pagsugod sa Modbus: 0

Gidak-on sa Modbus Block: 20

Gidaghanon sa mga Bloke: 1

Deskripsyon Adres sa Modbus Kalihokan Mga komento Mga yunit Pag-scale
Control Temperature Setpoint 1 0 3, 6, 16 0°C to 80°C (0°C to 245°C for PT100) °C ika-10*
PASC Minimum Pipe Size 2 1 3, 6, 16 10, 15, 20, 25, 32, 40, 50, 60, 70, 80, 100, 125 if invalid value 25 is used DN 1
Switch Control Mode 2 3, 6, 16 4 = Line/Line, 5 = PASC/PASC,
6 = Line/PASC, 7 = PASC/Line,
8 = Line/OFF, 9 = PASC/OFF,
10 = OFF/Line, 11 = OFF/PASC,
12 = OFF/OFF
1
Deadband 1 3 3, 6, 16 1.0°C hangtod sa 5°C °C ika-10*
PASC Minimum Ambient Temperature 1 4 3, 6, 16 -40°C hangtod 0°C °C ika-10*
PASC Minimum Pipe Size 1 5 3, 6, 16 10, 15, 20, 25, 32, 40, 50, 60, 70, 80, 100, 125 if invalid value 25 is used DN 1
PASC Power Adjust 6 3, 6, 16 70,80,90,100,110,120,130,140 % 1
Pag-setup sa Sensor 7 3, 6, 16 bit 1 = TS 1 assign alang sa Circuit 1
bit 2 = TS 2 assign alang sa Circuit 1
bit 5 = TS 1 assign alang sa Circuit 2
bit 6 = TS 2 assign alang sa Circuit 2
gamay 0,3,4,7 = NA
0 = Dili (Dili pilion) 1 = Oo (Pilia)
1
Pinulongan 8 3, 6, 16 0 = DANISH, 1 = GERMAN,
2 = DUTCH, 3 = ENGLISH,
4 = FRENCH, 5 = ITALIAN,
6 = SWEDISH, 7 = NORWEGIAN,
8 = FINNISH, 9 = RUSSIAN,
10 = CZECH, 11 = POLISH
1
Nasud 9 3, 6, 16 0 = GERMANY, 1 = AUSTRIA,
2 = SWITZERLAND, 3 = UK,
4 = FRANCE, 5 = ITALY,
6 = POLAND, 7 = CZECH_REPUBLIC, 8
= DENMARK, 9 = BELGIUM,
10 = RUSSIA, 11 = CHINA,
12 = JAPAN, 13 = SWEDEN,
14 = NORWAY, 15 = LITHUANIA,
16 = SLOVAKIA, 17 = NETHERLANDS,
18 = FINLAND, 19 = IRELAND
1
Uri sa kable 1 10 3, 6, 16 0 = 10XL2_ZH, 1 = 15XL2_ZH,
2 = 26XL2_ZH, 3 = 31XL2_ZH,
4 = FS_C10_2X, 5 = OTHER
1
Uri sa kable 2 11 3, 6, 16 0 = 10XL2_ZH, 1 = 15XL2_ZH,
2 = 26XL2_ZH, 3 = 31XL2_ZH,
4 = FS_C10_2X, 5 = OTHER
1
Deadband 2 12 3, 6, 16 1.0°C hangtod sa 5°C °C ika-10*
Date-Year 13 3, 6, 16 00 – 99 tuig 1
Date-Month 14 3, 6, 16 1 – 12 bulan 1
Date-Day 15 3, 6, 16 1 – 31 adlaw 1
Time-Hour 16 3, 6, 16 0 – 23 oras 1
Time-Minute 17 3, 6, 16 0 – 59 minuto 1
Control Temperature Setpoint 2 18 3, 6, 16 0°C to 80°C (0°C to 245°C for PT100) °C ika-10*
PASC Minimum Ambient Temperature 2 19 3, 6, 16 -40°C hangtod 0°C °C ika-10*

* Temperatura nga gipakita sa 1/10th sa °C (exampug: 10°C = 100)

2.5 Temperature Sensor Parameters

Modbus Function Code: 3, 6, 16

Adres sa Pagsugod sa Modbus: 20

Gidak-on sa Modbus Block: 4

Gidaghanon sa mga Bloke: 1

Deskripsyon Adres sa Modbus Kalihokan Mga komento Mga yunit Pag-scale
High TS 1 Alarm Setpoint** 20 3, 6, 16 2°C – 90°C
(2°C to 250°C for PT100)
°C ika-10*
Low TS 1 Alarm Setpoint** 21 3, 6, 16 -40°C – 78°C
(-40°C to +245°C for PT100)
°C ika-10*
High TS 2 Alarm Setpoint** 22 3, 6, 16 2°C – 90°C
(2°C to 250°C for PT100)
°C ika-10*
Low TS 2 Alarm Setpoint** 23 3, 6, 16 -40°C – 78°C
(-40°C to 245°C for PT100)
°C ika-10*

* Temperatura nga gipakita sa 1/10th sa °C (exampug: 10°C = 100)
** Can be disabled through section 2.2

2.6 I-override

Modbus Function Code: 3, 6, 16

Adres sa Pagsugod sa Modbus: 34

Gidak-on sa Modbus Block: 2

Gidaghanon sa mga Bloke: 1

Deskripsyon Adres sa Modbus Kalihokan Mga komento Mga yunit Pag-scale
Hilit nga Override Status 1 34 3, 6, 16 0 = Dili aktibo ang override
1 = Aktibo ang Force on Override
2 = Puwersa nga off Override aktibo
Hilit nga Override Status 2 35 3, 6, 16 0 = Dili aktibo ang override
1 = Aktibo ang Force on Override
2 = Puwersa nga off Override aktibo
2.7 Controller’s Identification Tag

Modbus Function Code: 3, 6, 16

Adres sa Pagsugod sa Modbus: 90

Gidak-on sa Modbus Block: 10

Gidaghanon sa mga Bloke: 1

Deskripsyon Adres sa Modbus Kalihokan Mga komento Mga yunit Pag-scale
Pag-ila sa Controller Tag 90 hangtod 99 3, 6, 16 Letters(A-Z) numbers(0-9), /.()_-#
Two characters per address.
String terminators = Null or space
Note: LSByte of 99 is always Null.
Isulod ang ascii code alang sa mga karakter sa ibabaw, alang sa example, input 0x4142 (Hex or 16706 in Dec) for register 90, and 0x3031 (in Hex or 12337 in Dec) for register 91, then the controller ID will be AB01.
2.8 Console Parameters

Modbus Function Code: 3, 6, 16

Adres sa Pagsugod sa Modbus: 120

Gidak-on sa Modbus Block: 2

Gidaghanon sa mga Bloke: 1

Deskripsyon Adres sa Modbus Kalihokan Mga komento Mga yunit Pag-scale
Keylock Passcode 120 3, 6, 16 1 hangtod 9999:
Incorrect passcode input will be ignored, and correct input will be valid for 2 minutes. (used to enter the code to unlock access to register 121)
Lock Enable/ Disable 121 3, 6, 16 0 = Keylock dili aktibo,
1 = Aktibo ang keylock
2.9 Temperature Sensor Parameters

Modbus Function Code: 3, 6, 16

Adres sa Pagsugod sa Modbus: 147

Gidak-on sa Modbus Block: 1

Gidaghanon sa mga Bloke: 1

Deskripsyon Adres sa Modbus Kalihokan Mga komento Mga yunit Pag-scale
Communications Activity Time-out 147 3, 6, 16 Used for load shedding and remote override 0-255 sec 1
2.10 General Controller Information

Modbus Function Code: 4

Adres sa Pagsugod sa Modbus: 0

Gidak-on sa Modbus Block: 4

Gidaghanon sa mga Bloke: 1

Deskripsyon Adres sa Modbus Kalihokan Mga komento Mga yunit Pag-scale
Type sa Device 0 4 Gitakdang bili = 450 1
Bersyon sa Firmware 1 4 Firmware Version-Major 0-255 1
Bersyon sa Firmware 2 4 Firmware Version-Minor 0-255 1
Bersyon sa Firmware 3 4 Firmware Version-Build 0-255 1
2.11 Dynamic Output Status

Modbus Function Code: 4

Adres sa Pagsugod sa Modbus: 50

Gidak-on sa Modbus Block: 15

Gidaghanon sa mga Bloke: 1

Deskripsyon Adres sa Modbus Kalihokan Mga komento Mga yunit Pag-scale
Control Output Duty Cycle 1 50 4 0 = full off, 100 = full on % 1
Pagsubay sa Kahimtang sa Pagkontrol 51 4 2 digit, ang una para sa circuit 1 ug ang ikaduha para sa circuit 2 (alang sa example, 0 means both are normal, 15 means circuit 1 = force off, circuit 2 = force on)
0 = normal nga pagkontrol sa temperatura
1 = output override force off
2 = test program in progress
5 = output override pwersa sa
1
PASC On-Count 1 52 4 sec 1
PASC Off-Count 1 53 4 sec 1
PASC Next Switch Count 1 54 4 sec 1
PASC Percent On 1 55 4 0 = full off, 100 = full on % 1
PASC Output State 1 56 4 0 = Off, 1 = On 1
PASC Total Time 1 57 4 sec 1
Control Output Duty Cycle 2 58 4 0 = full off, 100 = full on % 1
PASC On-Count 2 59 4 sec 1
PASC Off-Count 2 60 4 sec 1
PASC Next Switch Count 2 61 4 sec 1
PASC Percent On 2 62 4 0=full off, 100=full on % 1
PASC Output State 2 63 4 0 = Off, 1 = On 1
PASC Total Time 2 64 4 sec 1
2.12 Analog Readings

Modbus Function Code: 4

Adres sa Pagsugod sa Modbus: 81

Gidak-on sa Modbus Block: 2

Gidaghanon sa mga Bloke: 1

Deskripsyon Adres sa Modbus Kalihokan Mga komento Mga yunit Pag-scale
Current TS 1 Temperature 81 4 TS 1 kapakyasan = +3000.0°C TS 1 wala gigamit = +3200.0°C °C ika-10*
Current TS 2 Temperature  82 4 TS 2 kapakyasan = +3000.0°C TS 2 wala gigamit = +3200.0°C °C ika-10*

* Temperatura nga gipakita sa 1/10th sa °C (exampug: 10°C = 100)

2.13 Disclaimer

MODBUS map information is proprietary and confidential. Use of this information is permitted solely in order to implement a communications link between customer equipment and Raychem controllers. It may not be used for any other purpose, and it is not to be disclosed to 3rd parties without the written consent of Chemelex Thermal LLC.

Raychem Elexant 450c-Modbus Modbus Protocol Interface Mapping - 3

Belgium / Belgium
Tel +32 16 21 35 02
Fax +32 16 21 36 04
SalesBelux@chemelex.com

Bulgaria
Tel +359 2 973 33 73
SalesEE@chemelex.com

Česká Republika
Tel +420 606 069 618 (Comm)
+420 602 232 969 (Ind)
infoCZ@chemelex.com

Danmark
Tel +45 70 11 04 00
SalesDK@chemelex.com

Deutschland
Tel 0800 181 82 05
SalesDE@chemelex.com

España
Tel +34 911 59 30 60
Fax +34 900 98 32 64
SalesES@chemelex.com

France
Tél 0800 90 60 45
SalesFR@chemelex.com

Hrvatska
Tel +385 51 225 073 (Comm)
+385 1 605 01 88 (Ind)
SalesEE@chemelex.com

Italy
Tel +39 02 577 61 51
Fax +39 02 577 61 55 28
SalesIT@chemelex.com

Lietuva/Latvija/Eesti
Tel +370 698 411 56
SalesEE@chemelex.com

Magyarország
Tel +36 1 253 76 17
SalesHU@chemelex.com

Nederland
Tel 0800 022 49 78
SalesNL@chemelex.com

Norge
Tel +47 66 81 79 90
SalesNO@chemelex.com

Österreich
Tel 0800 29 74 10
SalesAT@chemelex.com

Polska
Tel +48 22 331 29 50
Fax +48 22 331 29 51
SalesPL@chemelex.com

Казахстан
Tel +7 7112 31 67 03170
SalesKZ@chemelex.com

Serbia ug Montenegro
Tel +386 41 665 634 (Comm)
+381 230 439 519 (Ind)
SalesEE@chemelex.com

Schweiz/Suisse/Svizzera
Tel +41 (41) 766 30 80
Fax +41 (41) 766 30 81
infoCH@chemelex.com

Suomi
Puh 0800 11 67 99
SalesFI@chemelex.com

Sverige
Tel +46 31 335 58 00
SalesSE@chemelex.com

Türkiye
Tel +90 545 284 09 05
SalesEE@chemelex.com

UK / Ireland
Tel 0800 969 013
SalesUK@chemelex.com


chemelex logo2 Raychem - logos

 

©2025 Chemelex. Ang tanan nga mga marka ug logo sa Chemelex gipanag-iya o lisensyado sa Chemelex Europe GmbH o sa mga kaubanan niini. Ang tanan nga ubang mga marka sa pamatigayon gipanag-iya sa ilang tag-iya. Ang Chemelex adunay katungod sa pag-usab sa mga detalye nga walay pahibalo.

RAYCHEM-OM-EU1850-Elexant450cModbus-ML-2504

chemelex.com