Elexant 450c-Modbus
Modbus Protocol Interface Mapping
ເວີຊັ່ນເຟີມແວ V2.1.1

![]()
1. ແນະນຳ
This manual details the Modbus registers of the Raychem Elexant 450c-Modbus. It is intended to be used by the users’ system integrators who wish to interface with their external device (i.e. DCS or Building management system -BMS- system) to the using the Modbus protocol. The manual includes details of the system’s current configuration, availability resources, set-up parameters, current conditions, alarm status, log info and numerous other fixed and variable data points.
1.1 ວິທີການນໍາໃຊ້ຄູ່ມືນີ້
The Elexant 450c-Modbus register can be accessed by DCS or BMS systems. However, this should only be done by expert users who understand that the system makes use of extensive semaphore fields to assure synchronization between the possibility of multiple users and conflicting instructions. These portions of the Modbus register map provide access to the current set-up and real time values being measured by the system. A snap shot of the current conditions, data for trending, alarm status, the current setting for the alarm thresholds and setpoints can be easily read without any risk to the system performance.
ແຜນທີ່ທະບຽນ Modbus ທັງໝົດແມ່ນລວມຢູ່ໃນເອກະສານນີ້ເພື່ອຄວາມສົມບູນ. ການຂຽນຖານຂໍ້ມູນແມ່ນຢູ່ໃນຄວາມສາມາດຂອງອຸປະກອນເຈົ້າພາບ Modbus ສ່ວນໃຫຍ່. ຢ່າງໃດກໍ່ຕາມ, ພວກເຮົາແນະນໍາຢ່າງແຂງແຮງວ່າຜູ້ລວມລະບົບທີ່ຂຽນໃສ່ຖານຂໍ້ມູນຕ້ອງທົດສອບລະບົບຂອງພວກເຂົາຢ່າງລະອຽດເພື່ອຮັບປະກັນວ່າມັນເຮັດວຽກຢ່າງຖືກຕ້ອງແລະບໍ່ມີຜົນສະທ້ອນທີ່ບໍ່ໄດ້ຕັ້ງໃຈ.
1.2 ການສື່ສານ Modbus
ຕົວຄວບຄຸມເຮັດຫນ້າທີ່ເປັນອຸປະກອນສໍາລອງ Modbus. ອຸປະກອນແມ່ບົດ modbus ສາມາດອ່ານ ແລະຂຽນໃສ່ຕົວຄວບຄຸມໄດ້. ນີ້ເຮັດໃຫ້ຄວາມເປັນໄປໄດ້ໃນການຕິດຕາມ, ຕັ້ງຄ່າແລະ view ໂມງປຸກຈາກໄລຍະໄກ. ໂປໂຕຄອນທີ່ໃຊ້ແມ່ນ Modbus RTU ຜ່ານ RS485.
| ຕົວແປ | ລາຍລະອຽດ | ຄ່າເລີ່ມຕົ້ນ | ຊ່ວງ/ຕົວເລືອກ |
| ທີ່ຢູ່ | ທີ່ຢູ່ສະຖານີ Modbus ໃຊ້ເພື່ອລະບຸຕົວຄວບຄຸມ. | 1 | 1 ຫາ 247 |
| ບັກ | ອັດຕາຂໍ້ມູນທີ່ການສື່ສານເກີດຂຶ້ນໃນເຄືອຂ່າຍ serial. | 9600 | 2400, 4800, 9600, 19200 |
| Parity | Parity ກໍານົດປະເພດຂອງ parity bit ທີ່ຈະນໍາໃຊ້ກັບໃດໆຂອງສາມພອດການສື່ສານ serial. | ບໍ່ມີ | ບໍ່ມີ, ຄີກ, ແມ່ນແຕ່ |
| ຢຸດ Bits | ກໍານົດຈໍານວນຂອງບິດຢຸດທີ່ໃຊ້ກັບໃດໆຂອງສາມພອດການສື່ສານ serial. | 1 | 1,2 |
ຄ່າເລີ່ມຕົ້ນຂອງເຈົ້າພາບແມ່ນ:
- ທີ່ຢູ່ Modbus: 1
- ອັດຕາ Baud: 9600
ການຕັ້ງຄ່າມາດຕະຖານແມ່ນ: 8 bits ຂໍ້ມູນ, ບໍ່ມີ parity ແລະ one stop bits.
ສະຫຼັບການຈຸ່ມ (ຂ້າງລຸ່ມ terminal 26 ແລະ 27):
| ປຸ່ມ | ຕົວຕ້ານທານ |
| 1 – | ດຶງຕົວຕ້ານທານລົງ |
| 2 – | ດຶງຕົວຕ້ານທານ |
| 3 – | ຕົວຕ້ານການສິ້ນສຸດ |
ກົດປຸ່ມເພື່ອເປີດ (ຕາມລູກສອນຊີ້) ຂ້າງຈະເຊື່ອມຕໍ່ຕົວຕ້ານທານທີ່ສອດຄ້ອງກັນໃນ.

2. MODBUS REGISTER MAP
2.1 Alarm Status Coils
ລະຫັດຟັງຊັນ Modbus: 1
ທີ່ຢູ່ເລີ່ມຕົ້ນ Modbus: 0
Modbus Block Size: 17
ຈໍານວນຕັນ: 1
| ລາຍລະອຽດ | ທີ່ຢູ່ Modbus | ຟັງຊັນ | ຄຳເຫັນ |
| High TS 1 Alarm | 0 | 1 | 0 = ບໍ່ມີສັນຍານເຕືອນ, 1 = ປຸກ |
| Low TS 1 Alarm | 1 | 1 | 0 = ບໍ່ມີສັນຍານເຕືອນ, 1 = ປຸກ |
| TS 1 ຄວາມລົ້ມເຫຼວ | 2 | 1 | 0 = ບໍ່ມີສັນຍານເຕືອນ, 1 = ປຸກ |
| High TS 2 | 3 | 1 | 0 = ບໍ່ມີສັນຍານເຕືອນ, 1 = ປຸກ |
| Low TS 2 | 4 | 1 | 0 = ບໍ່ມີສັນຍານເຕືອນ, 1 = ປຸກ |
| TS 2 ຄວາມລົ້ມເຫຼວ | 5 | 1 | 0 = ບໍ່ມີສັນຍານເຕືອນ, 1 = ປຸກ |
| ຄວາມຜິດພາດພາຍໃນ | 15 | 1 | 0 = ບໍ່ມີຂໍ້ຜິດພາດພາຍໃນ, 1 = ຂໍ້ຜິດພາດພາຍໃນ |
| ສະຖານະປຸກກະດານ | 16 | 1 | 0 = ບໍ່ມີສັນຍານເຕືອນ, 1 = ປຸກ |
2.2 Controller Setup Parameters
ລະຫັດຟັງຊັນ Modbus: 1,5,15
ທີ່ຢູ່ເລີ່ມຕົ້ນ Modbus: 145
Modbus Block Size: 9
ຈໍານວນຕັນ: 1
| ລາຍລະອຽດ | ທີ່ຢູ່ Modbus | ຟັງຊັນ | ຄຳເຫັນ |
| TS1 ໂໝດລົ້ມເຫລວ | 145 | 1, 5, 15 | 0 = ລົ້ມເຫລວ, 1 = ລົ້ມເຫລວ |
| TS2 ໂໝດລົ້ມເຫລວ | 146 | 1, 5, 15 | 0 = ລົ້ມເຫລວ, 1 = ລົ້ມເຫລວ |
| ໂຄງການທົດສອບ | 147 | 1, 5, 15 | 0 = ບໍ່, 1 = ແມ່ນແລ້ວ, ໂຄງການທົດສອບກໍາລັງແລ່ນ |
| Buzzer ປຸກ | 148 | 1, 5, 15 | 0 = ບໍ່, buzzer off 1 = ແມ່ນແລ້ວ, buzzer ເປີດ |
| TS1 high alarm feature off | 149 | 1, 5, 15 | 0 = alarm active, 1 = alarm deactive |
| TS1 high alarm feature off | 150 | 1, 5, 15 | 0 = alarm active, 1 = alarm deactive |
| TS1 low alarm feature off | 151 | 1, 5, 15 | 0 = alarm active, 1 = alarm deactive |
| TS1 low alarm feature off | 152 | 1, 5, 15 | 0 = alarm active, 1 = alarm deactive |
| ແຜງຄວບຄຸມການແຈ້ງເຕືອນ | 153 | 1, 5, 15 | 0 = ປຸກ deactive, 1 = ປຸກ active |
2.3 ສະຖານະການຄວບຄຸມ
ລະຫັດຟັງຊັນ Modbus: 2
ທີ່ຢູ່ເລີ່ມຕົ້ນ Modbus: 3
Modbus Block Size: 3
ຈໍານວນຕັນ: 1
| ລາຍລະອຽດ | ທີ່ຢູ່ Modbus | ຟັງຊັນ | ຄຳເຫັນ |
| Raw Switch Output1 | 3 | 2 | 0 = HC1 relay off, 1 = HC1 relay ເປີດ |
| ສະຖານະລັອກ | 4 | 2 | 0 = ບໍ່, 1 = ແມ່ນແລ້ວ, ລັອກ |
| Raw Switch Output2 | 5 | 2 | 0 = HC2 relay off, 1 = HC2 relay ເປີດ |
2.4 INPUT Parameters
ລະຫັດຟັງຊັນ Modbus: 3, 6, 16
ທີ່ຢູ່ເລີ່ມຕົ້ນ Modbus: 0
Modbus Block Size: 20
ຈໍານວນຕັນ: 1
| ລາຍລະອຽດ | ທີ່ຢູ່ Modbus | ຟັງຊັນ | ຄຳເຫັນ | ໜ່ວຍ | ປັບຂະໜາດ |
| Control Temperature Setpoint 1 | 0 | 3, 6, 16 | 0°C to 80°C (0°C to 245°C for PT100) | °C | ວັນທີ 10* |
| PASC Minimum Pipe Size 2 | 1 | 3, 6, 16 | 10, 15, 20, 25, 32, 40, 50, 60, 70, 80, 100, 125 if invalid value 25 is used | DN | 1 |
| ສະຫຼັບໂໝດການຄວບຄຸມ | 2 | 3, 6, 16 | 4 = Line/Line, 5 = PASC/PASC, 6 = Line/PASC, 7 = PASC/Line, 8 = Line/OFF, 9 = PASC/OFF, 10 = OFF/Line, 11 = OFF/PASC, 12 = OFF/OFF |
– | 1 |
| Deadband 1 | 3 | 3, 6, 16 | 1.0°C ຫາ 5°C | °C | ວັນທີ 10* |
| PASC Minimum Ambient Temperature 1 | 4 | 3, 6, 16 | -40°C ເຖິງ 0°C | °C | ວັນທີ 10* |
| PASC Minimum Pipe Size 1 | 5 | 3, 6, 16 | 10, 15, 20, 25, 32, 40, 50, 60, 70, 80, 100, 125 if invalid value 25 is used | DN | 1 |
| PASC Power Adjust | 6 | 3, 6, 16 | 70,80,90,100,110,120,130,140 | % | 1 |
| ຕັ້ງແກັບ | 7 | 3, 6, 16 | bit 1 = TS 1 ກຳນົດສຳລັບວົງຈອນ 1 bit 2 = TS 2 ກຳນົດສຳລັບວົງຈອນ 1 bit 5 = TS 1 ກຳນົດສຳລັບວົງຈອນ 2 bit 6 = TS 2 ກຳນົດສຳລັບວົງຈອນ 2 bit 0,3,4,7 = NA 0 = ບໍ່ (ບໍ່ເລືອກ) 1 = ແມ່ນ (ເລືອກ) |
– | 1 |
| ພາສາ | 8 | 3, 6, 16 | 0 = ດານັງ, 1 = ເຢຍລະມັນ, 2 = ໂຮນລັງ, 3 = ພາສາອັງກິດ, 4 = ຝຣັ່ງ, 5 = ອິຕາລີ, 6 = ສະວີເດັນ, 7 = ນໍເວ, 8 = ຟິນນິສ, 9 = ລັດເຊຍ, 10 = CZECH, 11 = POLISH |
– | 1 |
| ປະເທດ | 9 | 3, 6, 16 | 0 = ເຢຍລະມັນ, 1 = ອອສເຕຣເລຍ, 2 = ສະວິດເຊີແລນ, 3 = ອັງກິດ, 4 = ຝຣັ່ງ, 5 = ອິຕາລີ, 6 = POLAND, 7 = CZECH_REPUBLIC, 8 = DENMARK, 9 = BELGIUM, 10 = ລັດເຊຍ, 11 = ຈີນ, 12 = ຍີ່ປຸ່ນ, 13 = ສະວີເດັນ, 14 = ນໍເວ, 15 = ລິທົວເນຍ, 16 = ສະໂລວາເກຍ, 17 = ເນເທີແລນ, 18 = ຟິນແລນ, 19 = ໄອຣ໌ແລນ |
– | 1 |
| ປະເພດສາຍ 1 | 10 | 3, 6, 16 | 0 = 10XL2_ZH, 1 = 15XL2_ZH, 2 = 26XL2_ZH, 3 = 31XL2_ZH, 4 = FS_C10_2X, 5 = OTHER |
– | 1 |
| ປະເພດສາຍ 2 | 11 | 3, 6, 16 | 0 = 10XL2_ZH, 1 = 15XL2_ZH, 2 = 26XL2_ZH, 3 = 31XL2_ZH, 4 = FS_C10_2X, 5 = OTHER |
– | 1 |
| Deadband 2 | 12 | 3, 6, 16 | 1.0°C ຫາ 5°C | °C | ວັນທີ 10* |
| Date-Year | 13 | 3, 6, 16 | 00–99 | ປີ | 1 |
| Date-Month | 14 | 3, 6, 16 | 1–12 | ເດືອນ | 1 |
| Date-Day | 15 | 3, 6, 16 | 1–31 | ມື້ | 1 |
| Time-Hour | 16 | 3, 6, 16 | 0–23 | ຊົ່ວໂມງ | 1 |
| Time-Minute | 17 | 3, 6, 16 | 0–59 | ນາທີ | 1 |
| Control Temperature Setpoint 2 | 18 | 3, 6, 16 | 0°C to 80°C (0°C to 245°C for PT100) | °C | ວັນທີ 10* |
| PASC Minimum Ambient Temperature 2 | 19 | 3, 6, 16 | -40°C ເຖິງ 0°C | °C | ວັນທີ 10* |
* ອຸນຫະພູມສະແດງໃຫ້ເຫັນໃນ 1/10th ຂອງ°C (example: 10°C = 100)
2.5 Temperature Sensor Parameters
ລະຫັດຟັງຊັນ Modbus: 3, 6, 16
ທີ່ຢູ່ເລີ່ມຕົ້ນ Modbus: 20
Modbus Block Size: 4
ຈໍານວນຕັນ: 1
| ລາຍລະອຽດ | ທີ່ຢູ່ Modbus | ຟັງຊັນ | ຄຳເຫັນ | ໜ່ວຍ | ປັບຂະໜາດ |
| High TS 1 Alarm Setpoint** | 20 | 3, 6, 16 | 2°C – 90°C (2°C to 250°C for PT100) |
°C | ວັນທີ 10* |
| Low TS 1 Alarm Setpoint** | 21 | 3, 6, 16 | -40°C – 78°C (-40°C to +245°C for PT100) |
°C | ວັນທີ 10* |
| High TS 2 Alarm Setpoint** | 22 | 3, 6, 16 | 2°C – 90°C (2°C to 250°C for PT100) |
°C | ວັນທີ 10* |
| Low TS 2 Alarm Setpoint** | 23 | 3, 6, 16 | -40°C – 78°C (-40°C to 245°C for PT100) |
°C | ວັນທີ 10* |
* ອຸນຫະພູມສະແດງໃຫ້ເຫັນໃນ 1/10th ຂອງ°C (example: 10°C = 100)
** Can be disabled through section 2.2
2.6 ລົບລ້າງ
ລະຫັດຟັງຊັນ Modbus: 3, 6, 16
ທີ່ຢູ່ເລີ່ມຕົ້ນ Modbus: 34
Modbus Block Size: 2
ຈໍານວນຕັນ: 1
| ລາຍລະອຽດ | ທີ່ຢູ່ Modbus | ຟັງຊັນ | ຄຳເຫັນ | ໜ່ວຍ | ປັບຂະໜາດ |
| ສະຖານະ Override ໄລຍະໄກ 1 | 34 | 3, 6, 16 | 0 = Override ບໍ່ເຄື່ອນໄຫວ 1 = Force on Override active 2 = Force off Override active |
– | – |
| ສະຖານະ Override ໄລຍະໄກ 2 | 35 | 3, 6, 16 | 0 = Override ບໍ່ເຄື່ອນໄຫວ 1 = Force on Override active 2 = Force off Override active |
– | – |
2.7 Controller’s Identification Tag
ລະຫັດຟັງຊັນ Modbus: 3, 6, 16
ທີ່ຢູ່ເລີ່ມຕົ້ນ Modbus: 90
Modbus Block Size: 10
ຈໍານວນຕັນ: 1
| ລາຍລະອຽດ | ທີ່ຢູ່ Modbus | ຟັງຊັນ | ຄຳເຫັນ | ໜ່ວຍ | ປັບຂະໜາດ |
| ການລະບຸຕົວຄວບຄຸມ Tag | 90 ຫາ 99 | 3, 6, 16 | Letters(A-Z) numbers(0-9), /.()_-# Two characters per address. String terminators = Null or space Note: LSByte of 99 is always Null. ໃສ່ລະຫັດ ascii ສໍາລັບຕົວອັກສອນຂ້າງເທິງ, ຕົວຢ່າງample, input 0x4142 (Hex or 16706 in Dec) for register 90, and 0x3031 (in Hex or 12337 in Dec) for register 91, then the controller ID will be AB01. |
– | – |
2.8 Console Parameters
ລະຫັດຟັງຊັນ Modbus: 3, 6, 16
ທີ່ຢູ່ເລີ່ມຕົ້ນ Modbus: 120
Modbus Block Size: 2
ຈໍານວນຕັນ: 1
| ລາຍລະອຽດ | ທີ່ຢູ່ Modbus | ຟັງຊັນ | ຄຳເຫັນ | ໜ່ວຍ | ປັບຂະໜາດ |
| ລະຫັດລັອກ | 120 | 3, 6, 16 | 1 ຫາ 9999: Incorrect passcode input will be ignored, and correct input will be valid for 2 minutes. (used to enter the code to unlock access to register 121) |
– | – |
| Lock Enable/ Disable | 121 | 3, 6, 16 | 0 = ລັອກບໍ່ເຄື່ອນໄຫວ, 1 = ປຸ່ມລັອກເປີດໃຊ້ງານ |
– | – |
2.9 Temperature Sensor Parameters
ລະຫັດຟັງຊັນ Modbus: 3, 6, 16
ທີ່ຢູ່ເລີ່ມຕົ້ນ Modbus: 147
Modbus Block Size: 1
ຈໍານວນຕັນ: 1
| ລາຍລະອຽດ | ທີ່ຢູ່ Modbus | ຟັງຊັນ | ຄຳເຫັນ | ໜ່ວຍ | ປັບຂະໜາດ |
| Communications Activity Time-out | 147 | 3, 6, 16 | Used for load shedding and remote override 0-255 | ວິ | 1 |
2.10 General Controller Information
ລະຫັດຟັງຊັນ Modbus: 4
ທີ່ຢູ່ເລີ່ມຕົ້ນ Modbus: 0
Modbus Block Size: 4
ຈໍານວນຕັນ: 1
| ລາຍລະອຽດ | ທີ່ຢູ່ Modbus | ຟັງຊັນ | ຄຳເຫັນ | ໜ່ວຍ | ປັບຂະໜາດ |
| ປະເພດອຸປະກອນ | 0 | 4 | ມູນຄ່າຄົງທີ່ = 450 | – | 1 |
| ລຸ້ນ Firmware | 1 | 4 | Firmware Version-Major 0-255 | – | 1 |
| ລຸ້ນ Firmware | 2 | 4 | Firmware Version-Minor 0-255 | – | 1 |
| ລຸ້ນ Firmware | 3 | 4 | Firmware Version-Build 0-255 | – | 1 |
2.11 Dynamic Output Status
ລະຫັດຟັງຊັນ Modbus: 4
ທີ່ຢູ່ເລີ່ມຕົ້ນ Modbus: 50
Modbus Block Size: 15
ຈໍານວນຕັນ: 1
| ລາຍລະອຽດ | ທີ່ຢູ່ Modbus | ຟັງຊັນ | ຄຳເຫັນ | ໜ່ວຍ | ປັບຂະໜາດ |
| ຄວບຄຸມຮອບວຽນການສົ່ງອອກ 1 | 50 | 4 | 0 = full off, 100 = full on | % | 1 |
| ສະຖານະການຄວບຄຸມການຕິດຕາມ | 51 | 4 | 2 ຕົວເລກ, ທໍາອິດສໍາລັບວົງຈອນ 1 ແລະທີສອງສໍາລັບວົງຈອນ 2 (ຕົວຢ່າງample, 0 means both are normal, 15 means circuit 1 = force off, circuit 2 = force on) 0 = ການຄວບຄຸມອຸນຫະພູມປົກກະຕິ 1 = output override force off 2 = test program in progress 5 = ຜົນບັງຄັບໃຊ້ override ສຸດ |
– | 1 |
| PASC On-Count 1 | 52 | 4 | ວິ | 1 | |
| PASC Off-Count 1 | 53 | 4 | ວິ | 1 | |
| PASC Next Switch Count 1 | 54 | 4 | ວິ | 1 | |
| PASC Percent On 1 | 55 | 4 | 0 = full off, 100 = full on | % | 1 |
| PASC Output State 1 | 56 | 4 | 0 = ປິດ, 1 = ເປີດ | – | 1 |
| PASC Total Time 1 | 57 | 4 | ວິ | 1 | |
| ຄວບຄຸມຮອບວຽນການສົ່ງອອກ 2 | 58 | 4 | 0 = full off, 100 = full on | % | 1 |
| PASC On-Count 2 | 59 | 4 | ວິ | 1 | |
| PASC Off-Count 2 | 60 | 4 | ວິ | 1 | |
| PASC Next Switch Count 2 | 61 | 4 | ວິ | 1 | |
| PASC Percent On 2 | 62 | 4 | 0=full off, 100=full on | % | 1 |
| PASC Output State 2 | 63 | 4 | 0 = ປິດ, 1 = ເປີດ | – | 1 |
| PASC Total Time 2 | 64 | 4 | ວິ | 1 |
2.12 Analog Readings
ລະຫັດຟັງຊັນ Modbus: 4
ທີ່ຢູ່ເລີ່ມຕົ້ນ Modbus: 81
Modbus Block Size: 2
ຈໍານວນຕັນ: 1
| ລາຍລະອຽດ | ທີ່ຢູ່ Modbus | ຟັງຊັນ | ຄຳເຫັນ | ໜ່ວຍ | ປັບຂະໜາດ |
| Current TS 1 Temperature | 81 | 4 | TS 1 ຄວາມລົ້ມເຫຼວ = +3000.0°C TS 1 ບໍ່ໄດ້ໃຊ້ = +3200.0°C | °C | ວັນທີ 10* |
| Current TS 2 Temperature | 82 | 4 | TS 2 ຄວາມລົ້ມເຫຼວ = +3000.0°C TS 2 ບໍ່ໄດ້ໃຊ້ = +3200.0°C | °C | ວັນທີ 10* |
* ອຸນຫະພູມສະແດງໃຫ້ເຫັນໃນ 1/10th ຂອງ°C (example: 10°C = 100)
2.13 ການປະຕິເສດຄວາມຮັບຜິດຊອບ
MODBUS map information is proprietary and confidential. Use of this information is permitted solely in order to implement a communications link between customer equipment and Raychem controllers. It may not be used for any other purpose, and it is not to be disclosed to 3rd parties without the written consent of Chemelex Thermal LLC.

ປະເທດແບນຊິກ / Belgique
ໂທ +32 16 21 35 02
ແຟັກ +32 16 21 36 04
SalesBelux@chemelex.com
ບຸນກາຣີ
ໂທ +359 2 973 33 73
SalesEE@chemelex.com
Česká ສາທາລະນະລັດ
ໂທ +420 606 069 618 (ຄອມ)
+420 602 232 969 (Ind)
infoCZ@chemelex.com
ແດນມາກ
ໂທ +45 70 11 04 00
SalesDK@chemelex.com
Deutschland
ໂທ 0800 181 82 05
SalesDE@chemelex.com
ແອສປານາ
ໂທ +34 911 59 30 60
ແຟັກ +34 900 98 32 64
SalesES@chemelex.com
ປະເທດຝຣັ່ງ
ໂທ 0800 90 60 45
SalesFR@chemelex.com
Hrvatska
ໂທ +385 51 225 073 (ຄອມ)
+385 1 605 01 88 (Ind)
SalesEE@chemelex.com
ອີຕາລີ
ໂທ +39 02 577 61 51
ແຟັກ +39 02 577 61 55 28
SalesIT@chemelex.com
Lietuva/Latvija/Eesti
ໂທ +370 698 411 56
SalesEE@chemelex.com
Magyarország
ໂທ +36 1 253 76 17
SalesHU@chemelex.com
ເນເດີແລນ
ໂທ 0800 022 49 78
SalesNL@chemelex.com
Norge
ໂທ +47 66 81 79 90
SalesNO@chemelex.com
Österreich
ໂທ 0800 29 74 10
SalesAT@chemelex.com
Polska
ໂທ +48 22 331 29 50
ແຟັກ +48 22 331 29 51
SalesPL@chemelex.com
Казахстан
ໂທ +7 7112 31 67 03170
SalesKZ@chemelex.com
ເຊີເບຍ ແລະ ມອນເຕເນໂກຣ
ໂທ +386 41 665 634 (ຄອມ)
+381 230 439 519 (Ind)
SalesEE@chemelex.com
Schweiz/Suisse/Svizzera
ໂທ +41 (41) 766 30 80
ແຟັກ +41 (41) 766 30 81
infoCH@chemelex.com
ຊູມິ
ພຸດ 0800 11 67 99
SalesFI@chemelex.com
Sverige
ໂທ +46 31 335 58 00
SalesSE@chemelex.com
ຕວກກີ
ໂທ +90 545 284 09 05
SalesEE@chemelex.com
ອັງກິດ/ໄອແລນ
ໂທ 0800 969 013
SalesUK@chemelex.com
![]()
© 2025 Chemelex. ເຄື່ອງໝາຍ ແລະໂລໂກ້ຂອງ Chemelex ທັງໝົດແມ່ນເປັນເຈົ້າຂອງ ຫຼືອະນຸຍາດໂດຍ Chemelex Europe GmbH ຫຼືສາຂາຂອງມັນ. ເຄື່ອງຫມາຍການຄ້າອື່ນໆທັງຫມົດແມ່ນຊັບສິນຂອງເຈົ້າຂອງຂອງເຂົາເຈົ້າ. Chemelex ສະຫງວນສິດໃນການປ່ຽນແປງສະເພາະໂດຍບໍ່ມີການແຈ້ງໃຫ້ຊາບ.
RAYCHEM-OM-EU1850-Elexant450cModbus-ML-2504
ເອກະສານ / ຊັບພະຍາກອນ
![]() |
Raychem Elexant 450c-Modbus Modbus Protocol Interface Mapping [pdf] ຄູ່ມືຜູ້ໃຊ້ NGC-UIT3-EX, EU1850-Elexant450cModbus-ML-2504, Elexant 450c-Modbus Protocol Interface Mapping, Elexant 450c-Modbus, Protocol Interface Mapping, Protocol Interface Mapping, Interface Mapping, Mapping |