ໂລໂກ້ Raychem

Elexant 450c-Modbus

Modbus Protocol Interface Mapping

ເວີຊັ່ນເຟີມແວ V2.1.1

Raychem Elexant 450c-Modbus Modbus Protocol Interface Mapping - 1

ໂລໂກ້ chemelex 1

1. ແນະນຳ

This manual details the Modbus registers of the Raychem Elexant 450c-Modbus. It is intended to be used by the users’ system integrators who wish to interface with their external device (i.e. DCS or Building management system -BMS- system) to the using the Modbus protocol. The manual includes details of the system’s current configuration, availability resources, set-up parameters, current conditions, alarm status, log info and numerous other fixed and variable data points.

1.1 ວິທີການນໍາໃຊ້ຄູ່ມືນີ້

The Elexant 450c-Modbus register can be accessed by DCS or BMS systems. However, this should only be done by expert users who understand that the system makes use of extensive semaphore fields to assure synchronization between the possibility of multiple users and conflicting instructions. These portions of the Modbus register map provide access to the current set-up and real time values being measured by the system. A snap shot of the current conditions, data for trending, alarm status, the current setting for the alarm thresholds and setpoints can be easily read without any risk to the system performance.

ແຜນທີ່ທະບຽນ Modbus ທັງໝົດແມ່ນລວມຢູ່ໃນເອກະສານນີ້ເພື່ອຄວາມສົມບູນ. ການຂຽນຖານຂໍ້ມູນແມ່ນຢູ່ໃນຄວາມສາມາດຂອງອຸປະກອນເຈົ້າພາບ Modbus ສ່ວນໃຫຍ່. ຢ່າງໃດກໍ່ຕາມ, ພວກເຮົາແນະນໍາຢ່າງແຂງແຮງວ່າຜູ້ລວມລະບົບທີ່ຂຽນໃສ່ຖານຂໍ້ມູນຕ້ອງທົດສອບລະບົບຂອງພວກເຂົາຢ່າງລະອຽດເພື່ອຮັບປະກັນວ່າມັນເຮັດວຽກຢ່າງຖືກຕ້ອງແລະບໍ່ມີຜົນສະທ້ອນທີ່ບໍ່ໄດ້ຕັ້ງໃຈ.

1.2 ການສື່ສານ Modbus

ຕົວຄວບຄຸມເຮັດຫນ້າທີ່ເປັນອຸປະກອນສໍາລອງ Modbus. ອຸປະກອນແມ່ບົດ modbus ສາມາດອ່ານ ແລະຂຽນໃສ່ຕົວຄວບຄຸມໄດ້. ນີ້ເຮັດໃຫ້ຄວາມເປັນໄປໄດ້ໃນການຕິດຕາມ, ຕັ້ງຄ່າແລະ view ໂມງປຸກຈາກໄລຍະໄກ. ໂປໂຕຄອນທີ່ໃຊ້ແມ່ນ Modbus RTU ຜ່ານ RS485.

ຕົວແປ ລາຍລະອຽດ ຄ່າເລີ່ມຕົ້ນ ຊ່ວງ/ຕົວເລືອກ
ທີ່ຢູ່ ທີ່ຢູ່ສະຖານີ Modbus ໃຊ້ເພື່ອລະບຸຕົວຄວບຄຸມ. 1 1 ຫາ 247
ບັກ ອັດຕາຂໍ້ມູນທີ່ການສື່ສານເກີດຂຶ້ນໃນເຄືອຂ່າຍ serial. 9600 2400, 4800, 9600, 19200
Parity Parity ກໍານົດປະເພດຂອງ parity bit ທີ່ຈະນໍາໃຊ້ກັບໃດໆຂອງສາມພອດການສື່ສານ serial. ບໍ່ມີ ບໍ່ມີ, ຄີກ, ແມ່ນແຕ່
ຢຸດ Bits ກໍານົດຈໍານວນຂອງບິດຢຸດທີ່ໃຊ້ກັບໃດໆຂອງສາມພອດການສື່ສານ serial. 1 1,2

ຄ່າເລີ່ມຕົ້ນຂອງເຈົ້າພາບແມ່ນ:

  • ທີ່ຢູ່ Modbus: 1
  • ອັດຕາ Baud: 9600

ການ​ຕັ້ງ​ຄ່າ​ມາດ​ຕະ​ຖານ​ແມ່ນ​: 8 bits ຂໍ້​ມູນ​, ບໍ່​ມີ parity ແລະ one stop bits​.

ສະຫຼັບການຈຸ່ມ (ຂ້າງລຸ່ມ terminal 26 ແລະ 27):

ປຸ່ມ ຕົວຕ້ານທານ
1 – ດຶງຕົວຕ້ານທານລົງ
2 – ດຶງຕົວຕ້ານທານ
3 – ຕົວຕ້ານການສິ້ນສຸດ

ກົດປຸ່ມເພື່ອເປີດ (ຕາມລູກສອນຊີ້) ຂ້າງຈະເຊື່ອມຕໍ່ຕົວຕ້ານທານທີ່ສອດຄ້ອງກັນໃນ.

Raychem Elexant 450c-Modbus Modbus Protocol Interface Mapping - 2

2. MODBUS REGISTER MAP

2.1 Alarm Status Coils

ລະຫັດຟັງຊັນ Modbus: 1

ທີ່ຢູ່ເລີ່ມຕົ້ນ Modbus: 0

Modbus Block Size: 17

ຈໍານວນຕັນ: 1

ລາຍລະອຽດ ທີ່ຢູ່ Modbus ຟັງຊັນ ຄຳເຫັນ
High TS 1 Alarm 0 1 0 = ບໍ່ມີສັນຍານເຕືອນ, 1 = ປຸກ
Low TS 1 Alarm 1 1 0 = ບໍ່ມີສັນຍານເຕືອນ, 1 = ປຸກ
TS 1 ຄວາມລົ້ມເຫຼວ 2 1 0 = ບໍ່ມີສັນຍານເຕືອນ, 1 = ປຸກ
High TS 2 3 1 0 = ບໍ່ມີສັນຍານເຕືອນ, 1 = ປຸກ
Low TS 2 4 1 0 = ບໍ່ມີສັນຍານເຕືອນ, 1 = ປຸກ
TS 2 ຄວາມລົ້ມເຫຼວ 5 1 0 = ບໍ່ມີສັນຍານເຕືອນ, 1 = ປຸກ
ຄວາມຜິດພາດພາຍໃນ 15 1 0 = ບໍ່ມີຂໍ້ຜິດພາດພາຍໃນ, 1 = ຂໍ້ຜິດພາດພາຍໃນ
ສະຖານະປຸກກະດານ 16 1 0 = ບໍ່ມີສັນຍານເຕືອນ, 1 = ປຸກ
2.2 Controller Setup Parameters

ລະຫັດຟັງຊັນ Modbus: 1,5,15

ທີ່ຢູ່ເລີ່ມຕົ້ນ Modbus: 145

Modbus Block Size: 9

ຈໍານວນຕັນ: 1

ລາຍລະອຽດ ທີ່ຢູ່ Modbus ຟັງຊັນ ຄຳເຫັນ
TS1 ໂໝດລົ້ມເຫລວ 145 1, 5, 15 0 = ລົ້ມເຫລວ, 1 = ລົ້ມເຫລວ
TS2 ໂໝດລົ້ມເຫລວ 146 1, 5, 15 0 = ລົ້ມເຫລວ, 1 = ລົ້ມເຫລວ
ໂຄງການທົດສອບ 147 1, 5, 15 0 = ບໍ່, 1 = ແມ່ນແລ້ວ, ໂຄງການທົດສອບກໍາລັງແລ່ນ
Buzzer ປຸກ 148 1, 5, 15 0 = ບໍ່, buzzer off 1 = ແມ່ນແລ້ວ, buzzer ເປີດ
TS1 high alarm feature off 149 1, 5, 15 0 = alarm active, 1 = alarm deactive
TS1 high alarm feature off 150 1, 5, 15 0 = alarm active, 1 = alarm deactive
TS1 low alarm feature off 151 1, 5, 15 0 = alarm active, 1 = alarm deactive
TS1 low alarm feature off 152 1, 5, 15 0 = alarm active, 1 = alarm deactive
ແຜງຄວບຄຸມການແຈ້ງເຕືອນ 153 1, 5, 15 0 = ປຸກ deactive, 1 = ປຸກ active
2.3 ສະຖານະການຄວບຄຸມ

ລະຫັດຟັງຊັນ Modbus: 2

ທີ່ຢູ່ເລີ່ມຕົ້ນ Modbus: 3

Modbus Block Size: 3

ຈໍານວນຕັນ: 1

ລາຍລະອຽດ ທີ່ຢູ່ Modbus ຟັງຊັນ ຄຳເຫັນ
Raw Switch Output1 3 2 0 = HC1 relay off, 1 = HC1 relay ເປີດ
ສະຖານະລັອກ 4 2 0 = ບໍ່, 1 = ແມ່ນແລ້ວ, ລັອກ
Raw Switch Output2 5 2 0 = HC2 relay off, 1 = HC2 relay ເປີດ
2.4 INPUT Parameters

ລະຫັດຟັງຊັນ Modbus: 3, 6, 16

ທີ່ຢູ່ເລີ່ມຕົ້ນ Modbus: 0

Modbus Block Size: 20

ຈໍານວນຕັນ: 1

ລາຍລະອຽດ ທີ່ຢູ່ Modbus ຟັງຊັນ ຄຳເຫັນ ໜ່ວຍ ປັບຂະໜາດ
Control Temperature Setpoint 1 0 3, 6, 16 0°C to 80°C (0°C to 245°C for PT100) °C ວັນທີ 10*
PASC Minimum Pipe Size 2 1 3, 6, 16 10, 15, 20, 25, 32, 40, 50, 60, 70, 80, 100, 125 if invalid value 25 is used DN 1
ສະຫຼັບໂໝດການຄວບຄຸມ 2 3, 6, 16 4 = Line/Line, 5 = PASC/PASC,
6 = Line/PASC, 7 = PASC/Line,
8 = Line/OFF, 9 = PASC/OFF,
10 = OFF/Line, 11 = OFF/PASC,
12 = OFF/OFF
1
Deadband 1 3 3, 6, 16 1.0°C ຫາ 5°C °C ວັນທີ 10*
PASC Minimum Ambient Temperature 1 4 3, 6, 16 -40°C ເຖິງ 0°C °C ວັນທີ 10*
PASC Minimum Pipe Size 1 5 3, 6, 16 10, 15, 20, 25, 32, 40, 50, 60, 70, 80, 100, 125 if invalid value 25 is used DN 1
PASC Power Adjust 6 3, 6, 16 70,80,90,100,110,120,130,140 % 1
ຕັ້ງແກັບ 7 3, 6, 16 bit 1 = TS 1 ກຳນົດສຳລັບວົງຈອນ 1
bit 2 = TS 2 ກຳນົດສຳລັບວົງຈອນ 1
bit 5 = TS 1 ກຳນົດສຳລັບວົງຈອນ 2
bit 6 = TS 2 ກຳນົດສຳລັບວົງຈອນ 2
bit 0,3,4,7 = NA
0 = ບໍ່ (ບໍ່ເລືອກ) 1 = ແມ່ນ (ເລືອກ)
1
ພາສາ 8 3, 6, 16 0 = ດານັງ, 1 = ເຢຍລະມັນ,
2 = ໂຮນລັງ, 3 = ພາສາອັງກິດ,
4 = ຝຣັ່ງ, 5 = ອິຕາລີ,
6 = ສະວີເດັນ, 7 = ນໍເວ,
8 = ຟິນນິສ, 9 = ລັດເຊຍ,
10 = CZECH, 11 = POLISH
1
ປະເທດ 9 3, 6, 16 0 = ເຢຍລະມັນ, 1 = ອອສເຕຣເລຍ,
2 = ສະວິດເຊີແລນ, 3 = ອັງກິດ,
4 = ຝຣັ່ງ, 5 = ອິຕາລີ,
6 = POLAND, 7 = CZECH_REPUBLIC, 8
= DENMARK, 9 = BELGIUM,
10 = ລັດເຊຍ, 11 = ຈີນ,
12 = ຍີ່ປຸ່ນ, 13 = ສະວີເດັນ,
14 = ນໍເວ, 15 = ລິທົວເນຍ,
16 = ສະໂລວາເກຍ, 17 = ເນເທີແລນ,
18 = ຟິນແລນ, 19 = ໄອຣ໌ແລນ
1
ປະເພດສາຍ 1 10 3, 6, 16 0 = 10XL2_ZH, 1 = 15XL2_ZH,
2 = 26XL2_ZH, 3 = 31XL2_ZH,
4 = FS_C10_2X, 5 = OTHER
1
ປະເພດສາຍ 2 11 3, 6, 16 0 = 10XL2_ZH, 1 = 15XL2_ZH,
2 = 26XL2_ZH, 3 = 31XL2_ZH,
4 = FS_C10_2X, 5 = OTHER
1
Deadband 2 12 3, 6, 16 1.0°C ຫາ 5°C °C ວັນທີ 10*
Date-Year 13 3, 6, 16 00–99 ປີ 1
Date-Month 14 3, 6, 16 1–12 ເດືອນ 1
Date-Day 15 3, 6, 16 1–31 ມື້ 1
Time-Hour 16 3, 6, 16 0–23 ຊົ່ວໂມງ 1
Time-Minute 17 3, 6, 16 0–59 ນາທີ 1
Control Temperature Setpoint 2 18 3, 6, 16 0°C to 80°C (0°C to 245°C for PT100) °C ວັນທີ 10*
PASC Minimum Ambient Temperature 2 19 3, 6, 16 -40°C ເຖິງ 0°C °C ວັນທີ 10*

* ອຸນ​ຫະ​ພູມ​ສະ​ແດງ​ໃຫ້​ເຫັນ​ໃນ 1/10th ຂອງ°C (example: 10°C = 100)

2.5 Temperature Sensor Parameters

ລະຫັດຟັງຊັນ Modbus: 3, 6, 16

ທີ່ຢູ່ເລີ່ມຕົ້ນ Modbus: 20

Modbus Block Size: 4

ຈໍານວນຕັນ: 1

ລາຍລະອຽດ ທີ່ຢູ່ Modbus ຟັງຊັນ ຄຳເຫັນ ໜ່ວຍ ປັບຂະໜາດ
High TS 1 Alarm Setpoint** 20 3, 6, 16 2°C – 90°C
(2°C to 250°C for PT100)
°C ວັນທີ 10*
Low TS 1 Alarm Setpoint** 21 3, 6, 16 -40°C – 78°C
(-40°C to +245°C for PT100)
°C ວັນທີ 10*
High TS 2 Alarm Setpoint** 22 3, 6, 16 2°C – 90°C
(2°C to 250°C for PT100)
°C ວັນທີ 10*
Low TS 2 Alarm Setpoint** 23 3, 6, 16 -40°C – 78°C
(-40°C to 245°C for PT100)
°C ວັນທີ 10*

* ອຸນ​ຫະ​ພູມ​ສະ​ແດງ​ໃຫ້​ເຫັນ​ໃນ 1/10th ຂອງ°C (example: 10°C = 100)
** Can be disabled through section 2.2

2.6 ລົບລ້າງ

ລະຫັດຟັງຊັນ Modbus: 3, 6, 16

ທີ່ຢູ່ເລີ່ມຕົ້ນ Modbus: 34

Modbus Block Size: 2

ຈໍານວນຕັນ: 1

ລາຍລະອຽດ ທີ່ຢູ່ Modbus ຟັງຊັນ ຄຳເຫັນ ໜ່ວຍ ປັບຂະໜາດ
ສະຖານະ Override ໄລຍະໄກ 1 34 3, 6, 16 0 = Override ບໍ່ເຄື່ອນໄຫວ
1 = Force on Override active
2 = Force off Override active
ສະຖານະ Override ໄລຍະໄກ 2 35 3, 6, 16 0 = Override ບໍ່ເຄື່ອນໄຫວ
1 = Force on Override active
2 = Force off Override active
2.7 Controller’s Identification Tag

ລະຫັດຟັງຊັນ Modbus: 3, 6, 16

ທີ່ຢູ່ເລີ່ມຕົ້ນ Modbus: 90

Modbus Block Size: 10

ຈໍານວນຕັນ: 1

ລາຍລະອຽດ ທີ່ຢູ່ Modbus ຟັງຊັນ ຄຳເຫັນ ໜ່ວຍ ປັບຂະໜາດ
ການລະບຸຕົວຄວບຄຸມ Tag 90 ຫາ 99 3, 6, 16 Letters(A-Z) numbers(0-9), /.()_-#
Two characters per address.
String terminators = Null or space
Note: LSByte of 99 is always Null.
ໃສ່ລະຫັດ ascii ສໍາລັບຕົວອັກສອນຂ້າງເທິງ, ຕົວຢ່າງample, input 0x4142 (Hex or 16706 in Dec) for register 90, and 0x3031 (in Hex or 12337 in Dec) for register 91, then the controller ID will be AB01.
2.8 Console Parameters

ລະຫັດຟັງຊັນ Modbus: 3, 6, 16

ທີ່ຢູ່ເລີ່ມຕົ້ນ Modbus: 120

Modbus Block Size: 2

ຈໍານວນຕັນ: 1

ລາຍລະອຽດ ທີ່ຢູ່ Modbus ຟັງຊັນ ຄຳເຫັນ ໜ່ວຍ ປັບຂະໜາດ
ລະຫັດລັອກ 120 3, 6, 16 1 ຫາ 9999:
Incorrect passcode input will be ignored, and correct input will be valid for 2 minutes. (used to enter the code to unlock access to register 121)
Lock Enable/ Disable 121 3, 6, 16 0 = ລັອກບໍ່ເຄື່ອນໄຫວ,
1 = ປຸ່ມລັອກເປີດໃຊ້ງານ
2.9 Temperature Sensor Parameters

ລະຫັດຟັງຊັນ Modbus: 3, 6, 16

ທີ່ຢູ່ເລີ່ມຕົ້ນ Modbus: 147

Modbus Block Size: 1

ຈໍານວນຕັນ: 1

ລາຍລະອຽດ ທີ່ຢູ່ Modbus ຟັງຊັນ ຄຳເຫັນ ໜ່ວຍ ປັບຂະໜາດ
Communications Activity Time-out 147 3, 6, 16 Used for load shedding and remote override 0-255 ວິ 1
2.10 General Controller Information

ລະຫັດຟັງຊັນ Modbus: 4

ທີ່ຢູ່ເລີ່ມຕົ້ນ Modbus: 0

Modbus Block Size: 4

ຈໍານວນຕັນ: 1

ລາຍລະອຽດ ທີ່ຢູ່ Modbus ຟັງຊັນ ຄຳເຫັນ ໜ່ວຍ ປັບຂະໜາດ
ປະເພດອຸປະກອນ 0 4 ມູນຄ່າຄົງທີ່ = 450 1
ລຸ້ນ Firmware 1 4 Firmware Version-Major 0-255 1
ລຸ້ນ Firmware 2 4 Firmware Version-Minor 0-255 1
ລຸ້ນ Firmware 3 4 Firmware Version-Build 0-255 1
2.11 Dynamic Output Status

ລະຫັດຟັງຊັນ Modbus: 4

ທີ່ຢູ່ເລີ່ມຕົ້ນ Modbus: 50

Modbus Block Size: 15

ຈໍານວນຕັນ: 1

ລາຍລະອຽດ ທີ່ຢູ່ Modbus ຟັງຊັນ ຄຳເຫັນ ໜ່ວຍ ປັບຂະໜາດ
ຄວບ​ຄຸມ​ຮອບ​ວຽນ​ການ​ສົ່ງ​ອອກ 1 50 4 0 = full off, 100 = full on % 1
ສະຖານະການຄວບຄຸມການຕິດຕາມ 51 4 2 ຕົວເລກ, ທໍາອິດສໍາລັບວົງຈອນ 1 ແລະທີສອງສໍາລັບວົງຈອນ 2 (ຕົວຢ່າງample, 0 means both are normal, 15 means circuit 1 = force off, circuit 2 = force on)
0 = ການຄວບຄຸມອຸນຫະພູມປົກກະຕິ
1 = output override force off
2 = test program in progress
5 = ຜົນບັງຄັບໃຊ້ override ສຸດ
1
PASC On-Count 1 52 4 ວິ 1
PASC Off-Count 1 53 4 ວິ 1
PASC Next Switch Count 1 54 4 ວິ 1
PASC Percent On 1 55 4 0 = full off, 100 = full on % 1
PASC Output State 1 56 4 0 = ປິດ, 1 = ເປີດ 1
PASC Total Time 1 57 4 ວິ 1
ຄວບ​ຄຸມ​ຮອບ​ວຽນ​ການ​ສົ່ງ​ອອກ 2 58 4 0 = full off, 100 = full on % 1
PASC On-Count 2 59 4 ວິ 1
PASC Off-Count 2 60 4 ວິ 1
PASC Next Switch Count 2 61 4 ວິ 1
PASC Percent On 2 62 4 0=full off, 100=full on % 1
PASC Output State 2 63 4 0 = ປິດ, 1 = ເປີດ 1
PASC Total Time 2 64 4 ວິ 1
2.12 Analog Readings

ລະຫັດຟັງຊັນ Modbus: 4

ທີ່ຢູ່ເລີ່ມຕົ້ນ Modbus: 81

Modbus Block Size: 2

ຈໍານວນຕັນ: 1

ລາຍລະອຽດ ທີ່ຢູ່ Modbus ຟັງຊັນ ຄຳເຫັນ ໜ່ວຍ ປັບຂະໜາດ
Current TS 1 Temperature 81 4 TS 1 ຄວາມລົ້ມເຫຼວ = +3000.0°C TS 1 ບໍ່ໄດ້ໃຊ້ = +3200.0°C °C ວັນທີ 10*
Current TS 2 Temperature  82 4 TS 2 ຄວາມລົ້ມເຫຼວ = +3000.0°C TS 2 ບໍ່ໄດ້ໃຊ້ = +3200.0°C °C ວັນທີ 10*

* ອຸນ​ຫະ​ພູມ​ສະ​ແດງ​ໃຫ້​ເຫັນ​ໃນ 1/10th ຂອງ°C (example: 10°C = 100)

2.13 ການປະຕິເສດຄວາມຮັບຜິດຊອບ

MODBUS map information is proprietary and confidential. Use of this information is permitted solely in order to implement a communications link between customer equipment and Raychem controllers. It may not be used for any other purpose, and it is not to be disclosed to 3rd parties without the written consent of Chemelex Thermal LLC.

Raychem Elexant 450c-Modbus Modbus Protocol Interface Mapping - 3

ປະເທດແບນຊິກ / Belgique
ໂທ +32 16 21 35 02
ແຟັກ +32 16 21 36 04
SalesBelux@chemelex.com

ບຸນກາຣີ
ໂທ +359 2 973 33 73
SalesEE@chemelex.com

Česká ສາທາລະນະລັດ
ໂທ +420 606 069 618 (ຄອມ)
+420 602 232 969 (Ind)
infoCZ@chemelex.com

ແດນມາກ
ໂທ +45 70 11 04 00
SalesDK@chemelex.com

Deutschland
ໂທ 0800 181 82 05
SalesDE@chemelex.com

ແອສປານາ
ໂທ +34 911 59 30 60
ແຟັກ +34 900 98 32 64
SalesES@chemelex.com

ປະເທດຝຣັ່ງ
ໂທ 0800 90 60 45
SalesFR@chemelex.com

Hrvatska
ໂທ +385 51 225 073 (ຄອມ)
+385 1 605 01 88 (Ind)
SalesEE@chemelex.com

ອີຕາລີ
ໂທ +39 02 577 61 51
ແຟັກ +39 02 577 61 55 28
SalesIT@chemelex.com

Lietuva/Latvija/Eesti
ໂທ +370 698 411 56
SalesEE@chemelex.com

Magyarország
ໂທ +36 1 253 76 17
SalesHU@chemelex.com

ເນເດີແລນ
ໂທ 0800 022 49 78
SalesNL@chemelex.com

Norge
ໂທ +47 66 81 79 90
SalesNO@chemelex.com

Österreich
ໂທ 0800 29 74 10
SalesAT@chemelex.com

Polska
ໂທ +48 22 331 29 50
ແຟັກ +48 22 331 29 51
SalesPL@chemelex.com

Казахстан
ໂທ +7 7112 31 67 03170
SalesKZ@chemelex.com

ເຊີເບຍ ແລະ ມອນເຕເນໂກຣ
ໂທ +386 41 665 634 (ຄອມ)
+381 230 439 519 (Ind)
SalesEE@chemelex.com

Schweiz/Suisse/Svizzera
ໂທ +41 (41) 766 30 80
ແຟັກ +41 (41) 766 30 81
infoCH@chemelex.com

ຊູມິ
ພຸດ 0800 11 67 99
SalesFI@chemelex.com

Sverige
ໂທ +46 31 335 58 00
SalesSE@chemelex.com

ຕວກກີ
ໂທ +90 545 284 09 05
SalesEE@chemelex.com

ອັງກິດ/ໄອແລນ
ໂທ 0800 969 013
SalesUK@chemelex.com


ໂລໂກ້ chemelex 2 Raychem - logos

 

© 2025 Chemelex. ເຄື່ອງໝາຍ ແລະໂລໂກ້ຂອງ Chemelex ທັງໝົດແມ່ນເປັນເຈົ້າຂອງ ຫຼືອະນຸຍາດໂດຍ Chemelex Europe GmbH ຫຼືສາຂາຂອງມັນ. ເຄື່ອງຫມາຍການຄ້າອື່ນໆທັງຫມົດແມ່ນຊັບສິນຂອງເຈົ້າຂອງຂອງເຂົາເຈົ້າ. Chemelex ສະຫງວນສິດໃນການປ່ຽນແປງສະເພາະໂດຍບໍ່ມີການແຈ້ງໃຫ້ຊາບ.

RAYCHEM-OM-EU1850-Elexant450cModbus-ML-2504

chemelex.com

ເອກະສານ / ຊັບພະຍາກອນ

Raychem Elexant 450c-Modbus Modbus Protocol Interface Mapping [pdf] ຄູ່ມືຜູ້ໃຊ້
NGC-UIT3-EX, EU1850-Elexant450cModbus-ML-2504, Elexant 450c-Modbus Protocol Interface Mapping, Elexant 450c-Modbus, Protocol Interface Mapping, Protocol Interface Mapping, Interface Mapping, Mapping