Raychem Elexant 450c-Modbus Protocol Interface Mapping

Firmware version V2.1.1

The Raychem Elexant 450c-Modbus controller is designed for use with Modbus systems, allowing integration with Distributed Control Systems (DCS) or Building Management Systems (BMS). This manual provides a comprehensive mapping of its Modbus registers, enabling system integrators to monitor, configure, and manage the controller remotely.

1. Introduction

This manual details the Modbus registers of the Raychem Elexant 450c-Modbus. It is intended for system integrators who wish to interface their external devices (e.g., DCS or BMS systems) using the Modbus protocol. The manual includes details on the system's current configuration, available resources, set-up parameters, current conditions, alarm status, log information, and numerous other fixed and variable data points.

1.1 How to Use This Manual

The Elexant 450c-Modbus register can be accessed by DCS or BMS systems. This should only be performed by expert users familiar with the system's semaphore fields, which ensure synchronization between multiple users and prevent conflicting instructions. The Modbus register map provides access to current set-up and real-time measured values. It allows for easy reading of current conditions, data for trending, alarm status, and alarm threshold/setpoint settings without risking system performance.

This document includes the complete Modbus register map. While most Modbus host devices can write to the database, it is strongly recommended that system integrators thoroughly test their systems to ensure proper operation and prevent unintended consequences.

1.2 Modbus Communications

The controller functions as a Modbus slave device, allowing a Modbus master device to read from and write to it. This facilitates remote monitoring, configuration, and alarm viewing. The protocol used is Modbus RTU via RS485.

Variable Description Default Range/options
Address Modbus Station Address used to identify the controller. 1 1 to 247
Baud The data rate at which communications occur on the serial network. 9600 2400, 4800, 9600, 19200
Parity Parity defines the type of parity bit to be used with any of the three serial communications ports. None None, Odd, Even
Stop Bits Defines the number of stop bits used with any of the three serial communications ports. 1 1, 2

The host defaults are:

The standard configuration is: 8 data bits, no parity, and one stop bit.

The dip switches (located below terminals 26 and 27) control resistors:

Pushing the button to the ON position connects the corresponding resistor.

[Diagram showing dip switches labeled 1, 2, 3 with an arrow indicating the ON position]

2. Modbus Register Map

2.1 Alarm Status Coils

Modbus Function Code: 1

Modbus Start Address: 0

Modbus Block Size: 17

Number of Blocks: 1

Description Modbus Address Function Comments
High TS 1 Alarm 0 1 0 = no alarm, 1 = alarm
Low TS 1 Alarm 1 1 0 = no alarm, 1 = alarm
TS 1 Failure 2 1 0 = no alarm, 1 = alarm
High TS 2 3 1 0 = no alarm, 1 = alarm
Low TS 2 4 1 0 = no alarm, 1 = alarm
TS 2 Failure 5 1 0 = no alarm, 1 = alarm
Internal Error 15 1 0 = no internal error, 1 = internal error
Panel Alarm status 16 1 0 = no alarm, 1 = alarm

2.2 Controller Setup Parameters

Modbus Function Code: 1, 5, 15

Modbus Start Address: 145

Modbus Block Size: 9

Number of Blocks: 1

Description Modbus Address Function Comments
TS1 Fail Mode 145 1, 5, 15 0 = Fail off, 1 = Fail on
TS2 Fail Mode 146 1, 5, 15 0 = Fail off, 1 = Fail on
Test Program 147 1, 5, 15 0 = no, 1 = yes, test program is running
Alarm Buzzer 148 1, 5, 15 0 = no, buzzer off; 1 = yes, buzzer on
TS1 high alarm feature off 149 1, 5, 15 0 = alarm active, 1 = alarm deactive
TS1 high alarm feature off 150 1, 5, 15 0 = alarm active, 1 = alarm deactive
TS1 low alarm feature off 151 1, 5, 15 0 = alarm active, 1 = alarm deactive
TS1 low alarm feature off 152 1, 5, 15 0 = alarm active, 1 = alarm deactive
Panel Alarm Control 153 1, 5, 15 0 = alarm deactive, 1 = alarm active

2.3 Controller Status

Modbus Function Code: 2

Modbus Start Address: 3

Modbus Block Size: 3

Number of Blocks: 1

Description Modbus Address Function Comments
Raw Switch Output 1 3 2 0 = HC1 relay off, 1 = HC1 relay on
Keylock Status 4 2 0 = no, 1 = yes, locked
Raw Switch Output 2 5 2 0 = HC2 relay off, 1 = HC2 relay on

2.4 INPUT Parameters

Modbus Function Code: 3, 6, 16

Modbus Start Address: 0

Modbus Block Size: 20

Number of Blocks: 1

Description Modbus Address Function Comments Units Scaling
Control Temperature Setpoint 1 0 3, 6, 16 0°C to 80°C (0°C to 245°C for PT100) °C 10ths
PASC Minimum Pipe Size 1 1 3, 6, 16 10, 15, 20, 25, 32, 40, 50, 60, 70, 80, 100, 125; if invalid value 25 is used DN 1
Switch Control Mode 2 3, 6, 16 4 = Line/Line, 5 = PASC/PASC, 6 = Line/PASC, 7 = PASC/Line, 8 = Line/OFF, 9 = PASC/OFF, 10 = OFF/Line, 11 = OFF/PASC, 12 = OFF/OFF - 1
Deadband 1 3 3, 6, 16 1.0°C to 5°C °C 10ths
PASC Minimum Ambient Temperature 1 4 3, 6, 16 -40°C to 0°C °C 10ths
PASC Minimum Pipe Size 1 5 3, 6, 16 10, 15, 20, 25, 32, 40, 50, 60, 70, 80, 100, 125; if invalid value 25 is used DN 1
PASC Power Adjust 6 3, 6, 16 70, 80, 90, 100, 110, 120, 130, 140 % 1
Sensor Setup 7 3, 6, 16 bit 1 = TS 1 assign for Circuit 1; bit 2 = TS 2 assign for Circuit 1; bit 5 = TS 1 assign for Circuit 2; bit 6 = TS 2 assign for Circuit 2; bit 0,3,4,7 = NA - 1
Language 8 3, 6, 16 0 = No (No select); 1 = Yes (Select); 0 = DANISH, 1 = GERMAN, 2 = DUTCH, 3 = ENGLISH, 4 = FRENCH, 5 = ITALIAN, 6 = SWEDISH, 7 = NORWEGIAN, 8 = FINNISH, 9 = RUSSIAN, 10 = CZECH, 11 = POLISH - 1

* Temperature displayed in 1/10th of °C (example: 10°C = 100)

2.4.1 Country Settings

Description Modbus Address Function Comments Units Scaling
Country 9 3, 6, 16 0 = GERMANY, 1 = AUSTRIA, 2 = SWITZERLAND, 3 = UK, 4 = FRANCE, 5 = ITALY, 6 = POLAND, 7 = CZECH_REPUBLIC, 8 = DENMARK, 9 = BELGIUM, 10 = RUSSIA, 11 = CHINA, 12 = JAPAN, 13 = SWEDEN, 14 = NORWAY, 15 = LITHUANIA, 16 = SLOVAKIA, 17 = NETHERLANDS, 18 = FINLAND, 19 = IRELAND - 1

2.4.2 Cable Type Settings

Description Modbus Address Function Comments Units Scaling
Cable type 1 10 3, 6, 16 0 = 10XL2_ZH, 1 = 15XL2_ZH, 2 = 26XL2_ZH, 3 = 31XL2_ZH, 4 = FS_C10_2X, 5 = OTHER - 1
Cable type 2 11 3, 6, 16 0 = 10XL2_ZH, 1 = 15XL2_ZH, 2 = 26XL2_ZH, 3 = 31XL2_ZH, 4 = FS_C10_2X, 5 = OTHER - 1

2.4.3 Deadband 2

Description Modbus Address Function Comments Units Scaling
Deadband 2 12 3, 6, 16 1.0°C to 5°C °C 10ths

2.4.4 Date and Time Settings

Description Modbus Address Function Comments Units Scaling
Date-Year 13 3, 6, 16 00-99 year 1
Date-Month 14 3, 6, 16 1-12 month 1
Date-Day 15 3, 6, 16 1-31 day 1
Time-Hour 16 3, 6, 16 0-23 hour 1
Time-Minute 17 3, 6, 16 0-59 minute 1

2.4.5 Control Temperature Setpoint 2

Description Modbus Address Function Comments Units Scaling
Control Temperature Setpoint 2 18 3, 6, 16 0°C to 80°C (0°C to 245°C for PT100) °C 10ths

2.4.6 PASC Minimum Ambient Temperature 2

Description Modbus Address Function Comments Units Scaling
PASC Minimum Ambient Temperature 2 19 3, 6, 16 -40°C to 0°C °C 10ths

* Temperature displayed in 1/10th of °C (example: 10°C = 100)

2.5 Temperature Sensor Parameters

Modbus Function Code: 3, 6, 16

Modbus Start Address: 20

Modbus Block Size: 4

Number of Blocks: 1

Description Modbus Address Function Comments Units Scaling
High TS 1 Alarm Setpoint 20 3, 6, 16 2°C - 90°C (2°C to 250°C for PT100) °C 10ths
Low TS 1 Alarm Setpoint 21 3, 6, 16 -40°C - 78°C (-40°C to +245°C for PT100) °C 10ths
High TS 2 Alarm Setpoint 22 3, 6, 16 2°C - 90°C (2°C to 250°C for PT100) °C 10ths
Low TS 2 Alarm Setpoint 23 3, 6, 16 -40°C - 78°C (-40°C to 245°C for PT100) °C 10ths

* Temperature displayed in 1/10th of °C (example: 10°C = 100)

** Can be disabled through section 2.2

2.6 Override

Modbus Function Code: 3, 6, 16

Modbus Start Address: 34

Modbus Block Size: 2

Number of Blocks: 1

Description Modbus Address Function Comments Units Scaling
Remote Override Status 1 34 3, 6, 16 0 = Override not active; 1 = Force on Override active; 2 = Force off Override active - -
Remote Override Status 2 35 3, 6, 16 0 = Override not active; 1 = Force on Override active; 2 = Force off Override active - -

2.7 Controller's Identification Tag

Modbus Function Code: 3, 6, 16

Modbus Start Address: 90

Modbus Block Size: 10

Number of Blocks: 1

Description Modbus Address Function Comments Units Scaling
Controller's Identification Tag 90 to 99 3, 6, 16 Letters (A-Z), numbers (0-9), /.()_-# Two characters per address. String terminators = Null or space. Note: LSByte of 99 is always Null. Input the ascii code for the characters above, for example, input 0x4142 (Hex or 16706 in Dec) for register 90, and 0x3031 (in Hex or 12337 in Dec) for register 91, then the controller ID will be AB01. - -

2.8 Console Parameters

Modbus Function Code: 3, 6, 16

Modbus Start Address: 120

Modbus Block Size: 2

Number of Blocks: 1

Description Modbus Address Function Comments Units Scaling
Keylock Passcode 120 3, 6, 16 1 to 9999: Incorrect passcode input will be ignored, and correct input will be valid for 2 minutes. (used to enter the code to unlock access to register 121) - -
Lock Enable/Disable 121 3, 6, 16 0 = Keylock inactive, 1 = Keylock active - -

2.9 Temperature Sensor Parameters

Modbus Function Code: 3, 6, 16

Modbus Start Address: 147

Modbus Block Size: 1

Number of Blocks: 1

Description Modbus Address Function Comments Units Scaling
Communications Activity Time-out 147 3, 6, 16 Used for load shedding and remote override 0-255 sec 1

2.10 General Controller Information

Modbus Function Code: 4

Modbus Start Address: 0

Modbus Block Size: 4

Number of Blocks: 1

Description Modbus Address Function Comments Units Scaling
Device Type 0 4 Fixed value = 450 - 1
Firmware Version 1 1 4 Firmware Version-Major 0-255 - 1
Firmware Version 2 2 4 Firmware Version-Minor 0-255 - 1
Firmware Version 3 3 4 Firmware Version-Build 0-255 - 1

2.11 Dynamic Output Status

Modbus Function Code: 4

Modbus Start Address: 50

Modbus Block Size: 15

Number of Blocks: 1

Description Modbus Address Function Comments Units Scaling
Control Output Duty Cycle 1 50 4 0 = full off, 100 = full on % 1
Tracing Control Status 51 4 2 digits, the first for circuit 1 and the second for circuit 2 (e.g., 0 means both are normal, 15 means circuit 1 = force off, circuit 2 = force on) - 1
PASC On-Count 1 52 4 0 = normal temperature control; 1 = output override force off; 2 = test program in progress; 5 = output override force on sec 1
PASC Off-Count 1 53 4 - sec 1
PASC Next Switch Count 1 54 4 - sec 1
PASC Percent On 1 55 4 0 = full off, 100 = full on % 1
PASC Output State 1 56 4 0 = Off, 1 = On - 1
PASC Total Time 1 57 4 - sec 1
Control Output Duty Cycle 2 58 4 0 = full off, 100 = full on % 1
PASC On-Count 2 59 4 - sec 1
PASC Off-Count 2 60 4 - sec 1
PASC Next Switch Count 2 61 4 - sec 1
PASC Percent On 2 62 4 0 = full off, 100 = full on % 1
PASC Output State 2 63 4 0 = Off, 1 = On - 1
PASC Total Time 2 64 4 - sec 1

2.12 Analog Readings

Modbus Function Code: 4

Modbus Start Address: 81

Modbus Block Size: 2

Number of Blocks: 1

Description Modbus Address Function Comments Units Scaling
Current TS 1 Temperature 81 4 TS 1 failure = +3000.0°C; TS 1 not used = +3200.0°C °C 10ths
Current TS 2 Temperature 82 4 TS 2 failure = +3000.0°C; TS 2 not used = +3200.0°C °C 10ths

* Temperature displayed in 1/10th of °C (example: 10°C = 100)

2.13 Disclaimer

MODBUS map information is proprietary and confidential. Use of this information is permitted solely to implement a communications link between customer equipment and Raychem controllers. It may not be used for any other purpose, and it is not to be disclosed to 3rd parties without the written consent of Chemelex Thermal LLC.

Models: NGC-UIT3-EX, EU1850-Elexant450cModbus-ML-2504, Elexant 450c-Modbus Protocol Interface Mapping, Elexant 450c-Modbus, Protocol Interface Mapping, Protocol Interface Mapping, Interface Mapping, Mapping

File Info : application/pdf, 18 Pages, 743.19KB

PDF preview unavailable. Download the PDF instead.

RAYCHEM-OM-EU1850-Elexant450cModbus-ML ?srsltid=AfmBOoqBF c8VNmVknXP0YUWFdnvWozdN1JdZdIp9PvI6aBTry4lnuu6

References

Adobe PDF Library 17.0 Adobe InDesign 20.4 (Windows)

Related Documents

Preview Raychem Elexant 450c Installation and Operation Manual
This manual provides detailed installation and operation instructions for the Raychem Elexant 450c and Elexant 450c-Modbus electronic control thermostats, including important safety information, technical specifications, and troubleshooting guidance.
Preview Raychem Elexant 4010i: Single-Point Heat-Tracing Controller Specifications
Comprehensive technical specifications and overview of the Raychem Elexant 4010i, a touch-screen single-point heat-tracing controller designed for freeze protection and process temperature maintenance. Details features, control algorithms, monitoring capabilities, installation, communication, and ordering information.
Preview Raychem Supervisor Heat-Tracing Controller Configuration and Monitoring Software Operations Manual
Comprehensive operations manual for Raychem Supervisor software, detailing configuration, monitoring, system requirements, setup, and advanced features for heat-tracing controllers and systems. Covers NGC-40, Elexant, and other Raychem products.
Preview Raychem Elexant 4010i Installation Instructions
Comprehensive installation guide for the Raychem Elexant 4010i, a touch-screen based, single-point heat-tracing controller for freeze protection and process temperature maintenance. Covers product description, specifications, variants, approvals, connections, and mounting.
Preview Raychem Touch 1500 Configuration Guide
This guide provides detailed instructions for configuring and operating the Raychem NGC-40 system using the Touch 1500 user interface. It covers system overview, basic and advanced settings, and communication protocols for various Raychem modules.
Preview Raychem HTC-915 Universal Heat Tracing Control System User Manual
This document provides detailed information on the Raychem HTC-915 Universal Heat Tracing Control System, including its specifications, installation, operation, and configuration. It covers features such as temperature control, alarm outputs, and communication protocols, along with guidance on using the optional HTC-915-LIM limiter.
Preview Raychem E650C-G: Moisture and Temperature Sensor for Road Heating
Detailed product information for the Raychem E650C-G sensor, a robust and encapsulated moisture and temperature sensor designed for road heating applications. Includes product overview, specifications, installation guidelines, and ordering information.
Preview Raychem Touch 1500 Configuration Guide
This guide provides detailed instructions for configuring and monitoring Raychem NGC-40 systems, including various modules like NGC-40-BRIDGE, HTC, HTC3, and SLIM, as well as compatible thermostats such as Elexant 3500i, NGC20/Elexant 5010i, and Elexant 4010i/4020i, using the Touch 1500 interface for heat tracing applications.