1. INTRODUCTION

This manual details the Modbus registers of the Raychem Elexant 450c-Modbus. It is intended to be used by the users’ system integrators who wish to interface with their external device (i.e. DCS or Building management system -BMS- system) to the using the Modbus protocol. The manual includes details of the system’s current configuration, availability resources, set-up parameters, current conditions, alarm status, log info and numerous other fixed and variable data points.

1.1 How to Use This Manual

The Elexant 450c-Modbus register can be accessed by DCS or BMS systems. However, this should only be done by expert users who understand that the system makes use of extensive semaphore fields to assure synchronization between the possibility of multiple users and conflicting instructions. These portions of the Modbus register map provide access to the current set-up and real time values being measured by the system. A snap shot of the current conditions, data for trending, alarm status, the current setting for the alarm thresholds and setpoints can be easily read without any risk to the system performance.

The entire Modbus register map is included in this document for completeness. Writing to the database is within the capability of most Modbus host devices. However, we strongly recommend that system integrators who write to the database must thoroughly test their system to ensure it is working properly and that there are no unintended consequences.

1.2 Modbus Communications

The controller acts as Modbus slave device. A modbus master device can read and write to the controller. This enables the possibility to monitor, configure and view the alarms remotely. The protocol used is Modbus RTU via RS485.

Variable Description Default Range/options
Address Modbus Station Address used to identify the controller. 1 1 to 247
Baud The data rate at which communications occur on the serial network. 9600 2400, 4800, 9600, 19200
Parity Parity Defines the type of parity bit to be used with any of the three serial communications ports. None None, Odd, Even
Stop Bits Defines the number of stop bits used with any of the three serial communications ports. 1 1,2

The host defaults are:

  • Modbus Address: 1
  • Baud Rate: 9600

The standard configuration is: 8 data bits, no parity and one stop bit.

The dip switches (below terminal 26 and 27):

Button Resistor
1 – Pull down resistor
2 – Pull up resistor
3 – Termination resistor

Push the button to ON (as the arrow indicates) side will connect the corresponding resistor in.

Raychem Elexant 450c-Modbus Modbus Protocol Interface Mapping - 2

2. MODBUS REGISTER MAP

2.1 Alarm Status Coils

Modbus Function Code: 1

Modbus Start Address: 0

Modbus Block Size: 17

Number of Blocks: 1

Description Modbus Address Function Comments
High TS 1 Alarm 0 1 0 = no alarm, 1 = alarm
Low TS 1 Alarm 1 1 0 = no alarm, 1 = alarm
TS 1 Failure 2 1 0 = no alarm, 1 = alarm
High TS 2 3 1 0 = no alarm, 1 = alarm
Low TS 2 4 1 0 = no alarm, 1 = alarm
TS 2 Failure 5 1 0 = no alarm, 1 = alarm
Internal Error 15 1 0 = no internal error, 1 = internal error
Panel Alarm status 16 1 0 = no alarm, 1 = alarm
2.2 Controller Setup Parameters

Modbus Function Code: 1,5,15

Modbus Start Address: 145

Modbus Block Size: 9

Number of Blocks: 1

Description Modbus Address Function Comments
TS1 Fail Mode 145 1, 5, 15 0 = Fail off, 1 = Fail on
TS2 Fail Mode 146 1, 5, 15 0 = Fail off, 1 = Fail on
Test Program 147 1, 5, 15 0 = no, 1 = yes, test program is running
Alarm Buzzer 148 1, 5, 15 0 = no, buzzer off 1 = yes, buzzer on
TS1 high alarm feature off 149 1, 5, 15 0 = alarm active, 1 = alarm deactive
TS1 high alarm feature off 150 1, 5, 15 0 = alarm active, 1 = alarm deactive
TS1 low alarm feature off 151 1, 5, 15 0 = alarm active, 1 = alarm deactive
TS1 low alarm feature off 152 1, 5, 15 0 = alarm active, 1 = alarm deactive
Panel Alarm Control 153 1, 5, 15 0 = alarm deactive, 1 = alarm active
2.3 Controller Status

Modbus Function Code: 2

Modbus Start Address: 3

Modbus Block Size: 3

Number of Blocks: 1

Description Modbus Address Function Comments
Raw Switch Output1 3 2 0 = HC1 relay off, 1 = HC1 relay on
Keylock Status 4 2 0 = no, 1 = yes, locked
Raw Switch Output2 5 2 0 = HC2 relay off, 1 = HC2 relay on
2.4 INPUT Parameters

Modbus Function Code: 3, 6, 16

Modbus Start Address: 0

Modbus Block Size: 20

Number of Blocks: 1

Description Modbus Address Function Comments Units Scaling
Control Temperature Setpoint 1 0 3, 6, 16 0°C to 80°C (0°C to 245°C for PT100) °C 10ths*
PASC Minimum Pipe Size 2 1 3, 6, 16 10, 15, 20, 25, 32, 40, 50, 60, 70, 80, 100, 125 if invalid value 25 is used DN 1
Switch Control Mode 2 3, 6, 16 4 = Line/Line, 5 = PASC/PASC,
6 = Line/PASC, 7 = PASC/Line,
8 = Line/OFF, 9 = PASC/OFF,
10 = OFF/Line, 11 = OFF/PASC,
12 = OFF/OFF
1
Deadband 1 3 3, 6, 16 1.0°C to 5°C °C 10ths*
PASC Minimum Ambient Temperature 1 4 3, 6, 16 -40°C to 0°C °C 10ths*
PASC Minimum Pipe Size 1 5 3, 6, 16 10, 15, 20, 25, 32, 40, 50, 60, 70, 80, 100, 125 if invalid value 25 is used DN 1
PASC Power Adjust 6 3, 6, 16 70,80,90,100,110,120,130,140 % 1
Sensor Setup 7 3, 6, 16 bit 1 = TS 1 assign for Circuit 1
bit 2 = TS 2 assign for Circuit 1
bit 5 = TS 1 assign for Circuit 2
bit 6 = TS 2 assign for Circuit 2
bit 0,3,4,7 = NA
0 = No (No select) 1 = Yes (Select)
1
Language 8 3, 6, 16 0 = DANISH, 1 = GERMAN,
2 = DUTCH, 3 = ENGLISH,
4 = FRENCH, 5 = ITALIAN,
6 = SWEDISH, 7 = NORWEGIAN,
8 = FINNISH, 9 = RUSSIAN,
10 = CZECH, 11 = POLISH
1
Country 9 3, 6, 16 0 = GERMANY, 1 = AUSTRIA,
2 = SWITZERLAND, 3 = UK,
4 = FRANCE, 5 = ITALY,
6 = POLAND, 7 = CZECH_REPUBLIC, 8
= DENMARK, 9 = BELGIUM,
10 = RUSSIA, 11 = CHINA,
12 = JAPAN, 13 = SWEDEN,
14 = NORWAY, 15 = LITHUANIA,
16 = SLOVAKIA, 17 = NETHERLANDS,
18 = FINLAND, 19 = IRELAND
1
Cable type 1 10 3, 6, 16 0 = 10XL2_ZH, 1 = 15XL2_ZH,
2 = 26XL2_ZH, 3 = 31XL2_ZH,
4 = FS_C10_2X, 5 = OTHER
1
Cable type 2 11 3, 6, 16 0 = 10XL2_ZH, 1 = 15XL2_ZH,
2 = 26XL2_ZH, 3 = 31XL2_ZH,
4 = FS_C10_2X, 5 = OTHER
1
Deadband 2 12 3, 6, 16 1.0°C to 5°C °C 10ths*
Date-Year 13 3, 6, 16 00 – 99 year 1
Date-Month 14 3, 6, 16 1 – 12 month 1
Date-Day 15 3, 6, 16 1 – 31 day 1
Time-Hour 16 3, 6, 16 0 – 23 hour 1
Time-Minute 17 3, 6, 16 0 – 59 minute 1
Control Temperature Setpoint 2 18 3, 6, 16 0°C to 80°C (0°C to 245°C for PT100) °C 10ths*
PASC Minimum Ambient Temperature 2 19 3, 6, 16 -40°C to 0°C °C 10ths*

* Temperature displayed in 1/10th of °C (example: 10°C = 100)

2.5 Temperature Sensor Parameters

Modbus Function Code: 3, 6, 16

Modbus Start Address: 20

Modbus Block Size: 4

Number of Blocks: 1

Description Modbus Address Function Comments Units Scaling
High TS 1 Alarm Setpoint** 20 3, 6, 16 2°C – 90°C
(2°C to 250°C for PT100)
°C 10ths*
Low TS 1 Alarm Setpoint** 21 3, 6, 16 -40°C – 78°C
(-40°C to +245°C for PT100)
°C 10ths*
High TS 2 Alarm Setpoint** 22 3, 6, 16 2°C – 90°C
(2°C to 250°C for PT100)
°C 10ths*
Low TS 2 Alarm Setpoint** 23 3, 6, 16 -40°C – 78°C
(-40°C to 245°C for PT100)
°C 10ths*

* Temperature displayed in 1/10th of °C (example: 10°C = 100)
** Can be disabled through section 2.2

2.6 Override

Modbus Function Code: 3, 6, 16

Modbus Start Address: 34

Modbus Block Size: 2

Number of Blocks: 1

Description Modbus Address Function Comments Units Scaling
Remote Override Status 1 34 3, 6, 16 0 = Override not active
1 = Force on Override active
2 = Force off Override active
Remote Override Status 2 35 3, 6, 16 0 = Override not active
1 = Force on Override active
2 = Force off Override active
2.7 Controller’s Identification Tag

Modbus Function Code: 3, 6, 16

Modbus Start Address: 90

Modbus Block Size: 10

Number of Blocks: 1

Description Modbus Address Function Comments Units Scaling
Controller’s Identification Tag 90 to 99 3, 6, 16 Letters(A-Z) numbers(0-9), /.()_-#
Two characters per address.
String terminators = Null or space
Note: LSByte of 99 is always Null.
Input the ascii code for the characters above, for example, input 0x4142 (Hex or 16706 in Dec) for register 90, and 0x3031 (in Hex or 12337 in Dec) for register 91, then the controller ID will be AB01.
2.8 Console Parameters

Modbus Function Code: 3, 6, 16

Modbus Start Address: 120

Modbus Block Size: 2

Number of Blocks: 1

Description Modbus Address Function Comments Units Scaling
Keylock Passcode 120 3, 6, 16 1 to 9999:
Incorrect passcode input will be ignored, and correct input will be valid for 2 minutes. (used to enter the code to unlock access to register 121)
Lock Enable/ Disable 121 3, 6, 16 0 = Keylock inactive,
1 = Keylock active
2.9 Temperature Sensor Parameters

Modbus Function Code: 3, 6, 16

Modbus Start Address: 147

Modbus Block Size: 1

Number of Blocks: 1

Description Modbus Address Function Comments Units Scaling
Communications Activity Time-out 147 3, 6, 16 Used for load shedding and remote override 0-255 sec 1
2.10 General Controller Information

Modbus Function Code: 4

Modbus Start Address: 0

Modbus Block Size: 4

Number of Blocks: 1

Description Modbus Address Function Comments Units Scaling
Device Type 0 4 Fixed value = 450 1
Firmware Version 1 4 Firmware Version-Major 0-255 1
Firmware Version 2 4 Firmware Version-Minor 0-255 1
Firmware Version 3 4 Firmware Version-Build 0-255 1
2.11 Dynamic Output Status

Modbus Function Code: 4

Modbus Start Address: 50

Modbus Block Size: 15

Number of Blocks: 1

Description Modbus Address Function Comments Units Scaling
Control Output Duty Cycle 1 50 4 0 = full off, 100 = full on % 1
Tracing Control Status 51 4 2 digits, the first for circuit 1 and the second for circuit 2 (for example, 0 means both are normal, 15 means circuit 1 = force off, circuit 2 = force on)
0 = normal temperature control
1 = output override force off
2 = test program in progress
5 = output override force on
1
PASC On-Count 1 52 4 sec 1
PASC Off-Count 1 53 4 sec 1
PASC Next Switch Count 1 54 4 sec 1
PASC Percent On 1 55 4 0 = full off, 100 = full on % 1
PASC Output State 1 56 4 0 = Off, 1 = On 1
PASC Total Time 1 57 4 sec 1
Control Output Duty Cycle 2 58 4 0 = full off, 100 = full on % 1
PASC On-Count 2 59 4 sec 1
PASC Off-Count 2 60 4 sec 1
PASC Next Switch Count 2 61 4 sec 1
PASC Percent On 2 62 4 0=full off, 100=full on % 1
PASC Output State 2 63 4 0 = Off, 1 = On 1
PASC Total Time 2 64 4 sec 1
2.12 Analog Readings

Modbus Function Code: 4

Modbus Start Address: 81

Modbus Block Size: 2

Number of Blocks: 1

Description Modbus Address Function Comments Units Scaling
Current TS 1 Temperature 81 4 TS 1 failure = +3000.0°C TS 1 not used = +3200.0°C °C 10ths*
Current TS 2 Temperature  82 4 TS 2 failure = +3000.0°C TS 2 not used = +3200.0°C °C 10ths*

* Temperature displayed in 1/10th of °C (example: 10°C = 100)

2.13 Disclaimer

MODBUS map information is proprietary and confidential. Use of this information is permitted solely in order to implement a communications link between customer equipment and Raychem controllers. It may not be used for any other purpose, and it is not to be disclosed to 3rd parties without the written consent of Chemelex Thermal LLC.

Raychem Elexant 450c-Modbus Modbus Protocol Interface Mapping - 3

België / Belgique
Tel +32 16 21 35 02
Fax +32 16 21 36 04
SalesBelux@chemelex.com

Bulgaria
Tel +359 2 973 33 73
SalesEE@chemelex.com

Česká Republika
Tel +420 606 069 618 (Comm)
+420 602 232 969 (Ind)
infoCZ@chemelex.com

Danmark
Tel +45 70 11 04 00
SalesDK@chemelex.com

Deutschland
Tel 0800 181 82 05
SalesDE@chemelex.com

España
Tel +34 911 59 30 60
Fax +34 900 98 32 64
SalesES@chemelex.com

France
Tél 0800 90 60 45
SalesFR@chemelex.com

Hrvatska
Tel +385 51 225 073 (Comm)
+385 1 605 01 88 (Ind)
SalesEE@chemelex.com

Italia
Tel +39 02 577 61 51
Fax +39 02 577 61 55 28
SalesIT@chemelex.com

Lietuva/Latvija/Eesti
Tel +370 698 411 56
SalesEE@chemelex.com

Magyarország
Tel +36 1 253 76 17
SalesHU@chemelex.com

Nederland
Tel 0800 022 49 78
SalesNL@chemelex.com

Norge
Tel +47 66 81 79 90
SalesNO@chemelex.com

Österreich
Tel 0800 29 74 10
SalesAT@chemelex.com

Polska
Tel +48 22 331 29 50
Fax +48 22 331 29 51
SalesPL@chemelex.com

Казахстан
Tel +7 7112 31 67 03170
SalesKZ@chemelex.com

Serbia and Montenegro
Tel +386 41 665 634 (Comm)
+381 230 439 519 (Ind)
SalesEE@chemelex.com

Schweiz/Suisse/Svizzera
Tel +41 (41) 766 30 80
Fax +41 (41) 766 30 81
infoCH@chemelex.com

Suomi
Puh 0800 11 67 99
SalesFI@chemelex.com

Sverige
Tel +46 31 335 58 00
SalesSE@chemelex.com

Türkiye
Tel +90 545 284 09 05
SalesEE@chemelex.com

UK/Ireland
Tel 0800 969 013
SalesUK@chemelex.com


chemelex logo2 Raychem - logos

 

©2025 Chemelex. All Chemelex marks and logos are owned or licensed by Chemelex Europe GmbH or its affiliates. All other trademarks are the property of their respective owners. Chemelex reserves the right to change specifications without notice.

RAYCHEM-OM-EU1850-Elexant450cModbus-ML-2504

chemelex.com