Elexant 450c-Modbus Modbus Protocol Interface Mapping
“
Specifications
- Product: Raychem Elexant 450c-Modbus
- Model: NGC-UIT3-EX
- Interface: Modbus Protocol
- Firmware Version: V2.1.1
Product Usage Instructions
1. Introduction
This product manual details the Modbus registers of the Raychem
Elexant 450c-Modbus. It is intended for system integrators who wish
to interface with external devices using the Modbus protocol. The
manual includes details on configuration, resources, setup
parameters, current conditions, alarm status, log information, and
various data points.
1.1 How to Use This Manual
The entire Modbus register map is provided in this document.
System integrators writing to the database should thoroughly test
their system to ensure proper functionality and avoid unintended
consequences.
1.2 Modbus Communications
The controller acts as a Modbus slave device, allowing a Modbus
master device to read and write to it. This enables remote
monitoring, configuration, and alarm viewing using Modbus RTU via
RS485.
2. Modbus Register Map
2.1 Alarm Status Coils
- Modbus Function Code: 1
- Modbus Start Address: 0
- Modbus Block Size: 17
- Number of Blocks: 1
Details of various alarm status coils are provided in the Modbus
register map.
2.2 Controller Setup Parameters
- Modbus Function Code: 1,5,15
- Modbus Start Address: 145
- Modbus Block Size: 9
- Number of Blocks: 1
This section details the setup parameters of the controller for
Modbus communication.
FAQ
Q: What is the default Modbus Station Address?
A: The default Modbus Station Address used to identify the
controller is 1.
Q: What is the recommended baud rate for Modbus
communication?
A: The recommended baud rate is 9600 with no parity and one stop
bit.
Q: How can I connect the corresponding resistor using the dip
switches?
A: Push the button to the ON side to connect the corresponding
resistor.
“`
NGC-UIT3-EX SEleexcaonnt d45lin0ce-Modbus
Modbus Protocol Interface Mapping
Firmware version V2.1.1
RAYCHEM-OM-EU1850-Elexant450cModbus-ML-2504
TABLE OF CONTENTS
1. INTRODUCTION…………………………………………………………………………………………………………………………………………………..3 1.1 How to Use This Manual…………………………………………………………………………………………………………………………..3 1.2 Modbus Communications ………………………………………………………………………………………………………………………..3
2. MODBUS REGISTER MAP …………………………………………………………………………………………………………………………………….4 2.1 Alarm Status Coils ………………………………………………………………………………………………………………………………….4 2.2 Controller Setup Parameters ……………………………………………………………………………………………………………………4 2.3 Controller Status ……………………………………………………………………………………………………………………………………5 2.4 INPUT Parameters …………………………………………………………………………………………………………………………………5 2.5 Temperature Sensor Parameters ……………………………………………………………………………………………………………..6 2.6 Override ……………………………………………………………………………………………………………………………………………….7 2.7 Controller’s Identification Tag ………………………………………………………………………………………………………………….7 2.8 Console Parameters ……………………………………………………………………………………………………………………………….7 2.9 Temperature Sensor Parameters ………………………………………………………………………………………………………………8 2.10 General Controller Information …………………………………………………………………………………………………………………8 2.11 Dynamic Output Status ……………………………………………………………………………………………………………………………8 2.12 Analog Readings …………………………………………………………………………………………………………………………………..9 2.13 Disclaimer……………………………………………………………………………………………………………………………………………..9
INHALT
1. EINFÜHRUNG……………………………………………………………………………………………………………………………………………………. 10 1.1 Verwendung dieser Anleitung ………………………………………………………………………………………………………………… 10 1.2 Modbus-Kommunikation……………………………………………………………………………………………………………………….. 10
2. MODBUS-REGISTERÜBERSICHT ………………………………………………………………………………………………………………………….11 2.1 Status Alarmausgang…………………………………………………………………………………………………………………………….11 2.2 Steuergerät-Einstellungsparameter ………………………………………………………………………………………………………… 11 2.3 Steuergerätestatus ………………………………………………………………………………………………………………………………12 2.4 INPUT-Parameter………………………………………………………………………………………………………………………………….12 2.5 Temperatursensor-Parameter ………………………………………………………………………………………………………………… 13 2.6 Überschreiben ……………………………………………………………………………………………………………………………………..14 2.7 Steuergerät Identifikationsnummer…………………………………………………………………………………………………………. 14 2.8 Konsolenparameter ………………………………………………………………………………………………………………………………14 2.9 Temperatursensor-Parameter ……………………………………………………………………………………………………………….. 15 2.10 Allgemeine Informationen zum Steuergerät …………………………………………………………………………………………….. 15 2.11 Status der dynamischen Ausgabe ………………………………………………………………………………………………………….. 15 2.12 Analoge Anzeigen …………………………………………………………………………………………………………………………………16 2.13 Haftungsausschluss ……………………………………………………………………………………………………………………………..16
RAYCHEM-OM-EU1850-Elexant450cModbus-ML-2504
chemelex.com | 2
1. INTRODUCTION
This manual details the Modbus registers of the Raychem Elexant 450c-Modbus. It is intended to be used by the users’ system integrators who wish to interface with their external device (i.e. DCS or Building management system -BMS- system) to the using the Modbus protocol. The manual includes details of the system’s current configuration, availability resources, set-up parameters, current conditions, alarm status, log info and numerous other fixed and variable data points.
1.1 How to Use This Manual
The Elexant 450c-Modbus register can be accessed by DCS or BMS systems. However, this should only be done by expert users who understand that the system makes use of extensive semaphore fields to assure synchronization between the possibility of multiple users and conflicting instructions. These portions of the Modbus register map provide access to the current set-up and real time values being measured by the system. A snap shot of the current conditions, data for trending, alarm status, the current setting for the alarm thresholds and setpoints can be easily read without any risk to the system performance.
The entire Modbus register map is included in this document for completeness. Writing to the database is within the capability of most Modbus host devices. However, we strongly recommend that system integrators who write to the database must thoroughly test their system to ensure it is working properly and that there are no unintended consequences.
1.2 Modbus Communications
The controller acts as Modbus slave device. A modbus master device can read and write to the controller. This enables the possibility to monitor, configure and view the alarms remotely. The protocol used is Modbus RTU via RS485.
Variable Description
Default
Address Modbus Station Address used to identify the controller. 1
Baud Parity Stop Bits
The data rate at which communications occur on the serial network.
Parity Defines the type of parity bit to be used with any of the three serial communications ports.
Defines the number of stop bits used with any of the three serial communications ports.
9600 None 1
The host defaults are:
· Modbus Address: 1
· Baud Rate: 9600
The standard configuration is: 8 data bits, no parity and one stop bit.
Range/options 1 to 247 2400, 4800, 9600, 19200 None, Odd, Even
1,2
The dip switches (below terminal 26 and 27):
Button Resistor
1 –
Pull down resistor
2 –
Pull up resistor
3 –
Termination resistor
Push the button to ON (as the arrow indicates) side will connect the corresponding resistor in.
ON
12 3
RAYCHEM-OM-EU1850-Elexant450cModbus-ML-2504
chemelex.com | 3
2. MODBUS REGISTER MAP 2.1 Alarm Status Coils Modbus Function Code: 1 Modbus Start Address: 0 Modbus Block Size: 17 Number of Blocks: 1
Description
Modbus Address
High TS 1 Alarm 0
Low TS 1 Alarm
1
TS 1 Failure
2
High TS 2
3
Low TS 2
4
TS 2 Failure
5
Internal Error
15
Panel Alarm status 16
Function 1 1 1 1 1 1 1 1
2.2 Controller Setup Parameters Modbus Function Code: 1,5,15 Modbus Start Address: 145 Modbus Block Size: 9 Number of Blocks: 1
Description
Modbus Address
TS1 Fail Mode
145
TS2 Fail Mode
146
Test Program
147
Alarm Buzzer
148
TS1 high alarm feature off
149
TS1 high alarm feature off
150
TS1 low alarm feature off
151
TS1 low alarm feature off
152
Panel Alarm Control 153
Function 1, 5, 15 1, 5, 15 1, 5, 15 1, 5, 15 1, 5, 15 1, 5, 15 1, 5, 15 1, 5, 15 1, 5, 15
Comments 0 = no alarm, 1 = alarm 0 = no alarm, 1 = alarm 0 = no alarm, 1 = alarm 0 = no alarm, 1 = alarm 0 = no alarm, 1 = alarm 0 = no alarm, 1 = alarm 0 = no internal error, 1 = internal error 0 = no alarm, 1 = alarm
Comments 0 = Fail off, 1 = Fail on 0 = Fail off, 1 = Fail on 0 = no, 1 = yes, test program is running 0 = no, buzzer off 1 = yes, buzzer on 0 = alarm active, 1 = alarm deactive 0 = alarm active, 1 = alarm deactive 0 = alarm active, 1 = alarm deactive 0 = alarm active, 1 = alarm deactive 0 = alarm deactive, 1 = alarm active
RAYCHEM-OM-EU1850-Elexant450cModbus-ML-2504
chemelex.com | 4
2.3 Controller Status Modbus Function Code: 2 Modbus Start Address: 3 Modbus Block Size: 3 Number of Blocks: 1
Description
Modbus Address
Raw Switch Output1 3
Keylock Status
4
Raw Switch Output2 5
Function 2 2 2
Comments 0 = HC1 relay off, 1 = HC1 relay on 0 = no, 1 = yes, locked 0 = HC2 relay off, 1 = HC2 relay on
2.4 INPUT Parameters Modbus Function Code: 3, 6, 16 Modbus Start Address: 0 Modbus Block Size: 20 Number of Blocks: 1
Description
Control Temperature Setpoint 1 PASC Minimum Pipe Size 2
Modbus Address 0
1
Switch Control Mode
2
Deadband 1
3
PASC Minimum
Ambient
4
Temperature 1
PASC Minimum Pipe Size 1
5
PASC Power Adjust 6
Sensor Setup
7
Language
8
Function Comments
Units
3, 6, 16 3, 6, 16 3, 6, 16 3, 6, 16 3, 6, 16 3, 6, 16 3, 6, 16
3, 6, 16
3, 6, 16
0°C to 80°C (0°C to 245°C for PT100) °C
10,15,20,25,32,40,50,60,70,80,100, 125 if invalid value 25 is used
DN
4 = Line/Line, 5 = PASC/PASC,
6 = Line/PASC, 7 = PASC/Line,
8 = Line/OFF, 9 = PASC/OFF,
10 = OFF/Line, 11 = OFF/PASC,
12 = OFF/OFF
1.0°C to 5°C
°C
40°C to 0°C
°C
10,15,20,25,32,40,50,60,70,80,100, 125 if invalid value 25 is used
DN
70,80,90,100,110,120,130,140
%
bit 1 = TS 1 assign for Circuit 1
bit 2 = TS 2 assign for Circuit 1
bit 5 = TS 1 assign for Circuit 2 bit 6 = TS 2 assign for Circuit 2
bit 0,3,4,7 = NA
0 = No (No select) 1 = Yes (Select)
0 = DANISH, 1 = GERMAN,
2 = DUTCH, 3 = ENGLISH,
4 = FRENCH, 5 = ITALIAN, 6 = SWEDISH, 7 = NORWEGIAN,
8 = FINNISH, 9 = RUSSIAN,
10 = CZECH, 11 = POLISH
* Temperature displayed in 1/10th of °C (example: 10°C = 100)
Scaling 10ths* 1 1 10ths* 10ths* 1 1
1
1
RAYCHEM-OM-EU1850-Elexant450cModbus-ML-2504
chemelex.com | 5
Description
Country
Cable type 1 Cable type 2 Deadband 2
Modbus Address
9
10 11 12
Function
3, 6, 16
3, 6, 16 3, 6, 16 3, 6, 16
Comments
Units
0 = GERMANY, 1 = AUSTRIA,
2 = SWITZERLAND, 3 = UK,
4 = FRANCE, 5 = ITALY,
6 = POLAND, 7 = CZECH_REPUBLIC, 8
= DENMARK, 9 = BELGIUM, 10 = RUSSIA, 11 = CHINA,
12 = JAPAN, 13 = SWEDEN,
14 = NORWAY, 15 = LITHUANIA,
16 = SLOVAKIA, 17 = NETHERLANDS,
18 = FINLAND, 19 = IRELAND
0 = 10XL2_ZH, 1 = 15XL2_ZH,
2 = 26XL2_ZH, 3 = 31XL2_ZH,
4 = FS_C10_2X, 5 = OTHER
0 = 10XL2_ZH, 1 = 15XL2_ZH,
2 = 26XL2_ZH, 3 = 31XL2_ZH,
4 = FS_C10_2X, 5 = OTHER
1.0°C to 5°C
°C
Date-Year
13
3, 6, 16
00 99
year
Date-Month
14
3, 6, 16
1 12
month
Date-Day
15
3, 6, 16
1 31
day
Time-Hour
16
3, 6, 16
0 23
hour
Time-Minute
17
3, 6, 16
0 59
minute
Control
Temperature
18
Setpoint 2
PASC Minimum
Ambient
19
Temperature 2
3, 6, 16
0°C to 80°C (0°C to 245°C for PT100) °C
3, 6, 16
40°C to 0°C
°C
* Temperature displayed in 1/10th of °C (example: 10°C = 100)
Scaling
1
1 1 10ths* 1 1 1 1 1 10ths* 10ths*
2.5 Temperature Sensor Parameters Modbus Function Code: 3, 6, 16 Modbus Start Address: 20 Modbus Block Size: 4 Number of Blocks: 1
Description
Modbus Address
Function Comments
High TS 1 Alarm Setpoint**
20
Low TS 1 Alarm Setpoint**
21
High TS 2 Alarm Setpoint**
22
Low TS 2 Alarm Setpoint**
23
3, 6, 16 3, 6, 16 3, 6, 16 3, 6, 16
2°C 90°C (2°C to 250°C for PT100)
40°C 78°C (40°C to +245°C for PT100)
2°C 90°C (2°C to 250°C for PT100)
40°C 78°C (40°C to 245°C for PT100)
* Temperature displayed in 1/10th of °C (example: 10°C = 100) ** Can be disabled through section 2.2
Units °C °C °C °C
Scaling 10ths* 10ths* 10ths* 10ths*
RAYCHEM-OM-EU1850-Elexant450cModbus-ML-2504
chemelex.com | 6
2.6 Override Modbus Function Code: 3, 6, 16 Modbus Start Address: 34 Modbus Block Size: 2 Number of Blocks: 1
Description
Remote Override Status 1
Remote Override Status 2
Modbus Address 34
35
Function 3, 6, 16 3, 6, 16
Comments
0 = Override not active 1 = Force on Override active 2 = Force off Override active 0 = Override not active 1 = Force on Override active 2 = Force off Override active
Units
2.7 Controller’s Identification Tag Modbus Function Code: 3, 6, 16 Modbus Start Address: 90 Modbus Block Size: 10 Number of Blocks: 1
Description
Modbus Address
Controller’s Identification Tag
90 to 99
Function 3, 6, 16
Comments
Units
Letters(A-Z) numbers(0-9), /.()_-# Two characters per address. String terminators = Null or space Note: LSByte of 99 is always Null.
Input the ascii code for the characters above, for example, input 0x4142 (Hex or 16706 in Dec) for register 90, and 0x3031 (in Hex or 12337 in Dec) for register 91, then the controller ID will be AB01.
2.8 Console Parameters Modbus Function Code: 3, 6, 16 Modbus Start Address: 120 Modbus Block Size: 2 Number of Blocks: 1
Description
Modbus Address
Keylock Passcode 120
Lock Enable/ Disable
121
Function 3, 6, 16 3, 6, 16
Comments
Units
1 to 9999:
Incorrect passcode input will be
ignored, and correct input will be valid for 2 minutes. (used to enter the code
to unlock access to
register 121)
0 = Keylock inactive, 1 = Keylock active
Scaling
Scaling
Scaling
RAYCHEM-OM-EU1850-Elexant450cModbus-ML-2504
chemelex.com | 7
2.9 Temperature Sensor Parameters Modbus Function Code: 3, 6, 16 Modbus Start Address: 147 Modbus Block Size: 1 Number of Blocks: 1
Description
Communications Activity Time-out
Modbus Address
147
Function 3, 6, 16
Comments
Used for load shedding and remote override 0255
Units sec
2.10 General Controller Information Modbus Function Code: 4 Modbus Start Address: 0 Modbus Block Size: 4 Number of Blocks: 1
Description Device Type
Modbus Address
0
Firmware Version 1
Firmware Version 2
Firmware Version 3
Function Comments
4
Fixed value = 450
4
Firmware Version-Major 0-255
4
Firmware Version-Minor 0-255
4
Firmware Version-Build 0-255
Units
Scaling 1
Scaling 1 1 1 1
2.11 Dynamic Output Status Modbus Function Code: 4 Modbus Start Address: 50 Modbus Block Size: 15 Number of Blocks: 1
Description
Control Output Duty Cycle 1
Modbus Address
50
Tracing Control Status
51
PASC On-Count 1 52
PASC Off-Count 1 53
PASC Next Switch Count 1
54
PASC Percent On 1 55
PASC Output State 1
56
Function Comments
Units
4
0 = full off, 100 = full on
%
2 digits, the first for circuit 1 and the second for circuit 2 (for example, 0
means both are normal, 15 means
circuit 1 = force off, circuit 2 = force
4
on)
0 = normal temperature control
1 = output override force off
2 = test program in progress
5 = output override force on
4
sec
4
sec
4
sec
4
0 = full off, 100 = full on
%
4
0 = Off, 1 = On
Scaling 1
1
1 1 1 1 1
RAYCHEM-OM-EU1850-Elexant450cModbus-ML-2504
chemelex.com | 8
Description
Modbus Address
PASC Total Time 1 57
Control Output Duty Cycle 2
58
PASC On-Count 2 59
PASC Off-Count 2 60
PASC Next Switch Count 2
61
PASC Percent On 2 62
PASC Output State 2
63
PASC Total Time 2 64
Function Comments
4
4
0 = full off, 100 = full on
4 4
4
4
0=full off, 100=full on
4
0 = Off, 1 = On
4
Units sec % sec sec sec % sec
Scaling 1 1 1 1 1 1 1 1
2.12 Analog Readings Modbus Function Code: 4 Modbus Start Address: 81 Modbus Block Size: 2 Number of Blocks: 1
Description
Current TS 1 Temperature Current TS 2 Temperature
Modbus Address 81
82
Function 4 4
Comments
TS 1 failure = +3000.0°C TS 1 not used = +3200.0°C TS 2 failure = +3000.0°C TS 2 not used = +3200.0°C
* Temperature displayed in 1/10th of °C (example: 10°C = 100)
Units °C °C
Scaling 10ths* 10ths*
2.13 Disclaimer
MODBUS map information is proprietary and confidential. Use of this information is permitted solely in order to implement a communications link between customer equipment and Raychem controllers. It may not be used for any other purpose, and it is not to be disclosed to 3rd parties without the written consent of Chemelex Thermal LLC.
RAYCHEM-OM-EU1850-Elexant450cModbus-ML-2504
chemelex.com | 9
1. EINFÜHRUNG
Diese Anleitung beschreibt die Modbus-Register des Raychem Elexant 450c-Modbus. Sie ist für Systemintegratoren bestimmt, die ein externes Gerät (d. h. Leit- oder Gebäudeautomationssystem) über das Modbus-Protokoll verknüpfen möchten. Die Anleitung beschreibt den Modbus-Zugriff auf Angaben zur aktuellen Konfiguration des Systems, zur Verfügbarkeit, zu eingestellten Parametern, zu aktuellen Bedingungen, zum Alarmstatus, zu Protokollinformationen und zu zahlreichen anderen festen oder variablen Datenpunkten.
1.1 Verwendung dieser Anleitung
Leit- oder Gebäudeautomationssysteme können über Modbus auf das Elexant 450c-Modbus-Register zugreifen. Dies wird jedoch nur erfahrenen Anwendern empfohlen, da das System in großem Umfang Datenstrukturfelder verwendet, um auch bei mehreren Anwendern und gegensätzlichen Anweisungen die Prozesssynchronisation zu gewährleisten. Diese Teile der Modbus-Register-Map ermöglichen den Zugriff auf die aktuelle Konfiguration und auf Echtzeitwerte, die vom System gemessen werden. Eine Zusammenfassung der aktuellen Bedingungen, Trenddaten, Alarmstatus, aktuelle Alarmschwellenwerte und Sollwerte lassen sich dadurch ohne Beeinträchtigung der Systemleistung leicht ablesen.
Aus Gründen der Vollständigkeit ist in diesem Dokument die vollständige Register-Map aufgeführt. Die meisten Modbus-Hostgeräte sind in der Lage, in die Datenbank zu schreiben. Wir empfehlen jedoch dringend, dass Systemintegratoren, die in die Datenbank schreiben, ihr System eingehend testen, um sicherzustellen, dass es ordnungsgemäß funktioniert und nicht beabsichtigte Auswirkungen ausgeschlossen sind.
1.2 Modbus-Kommunikation
Das Steuergerät agiert als Host-Client-Gerät. Ein Modbus-Host-Gerät kann auf das Steuergerät schreiben und vom Steuergerät lesen. Dadurch ist es möglich, Alarme fern zu überwachen, zu konfigurieren und anzuzeigen. Das verwendete Protokoll ist Modbus RTU über RS485.
Variabel Adresse Baud Parität
Stoppbits
Beschreibung
Die zur Identifizierung des Steuergeräts verwendete Modbus-Stationsadresse.
Die Datenrate, mit der die Kommunikation über das serielle Netzwerk erfolgt.
Die Parität definiert die Art des Paritätsbits, das mit einer der drei seriellen Kommunikationsschnittstellen verwendet wird.
Die Stoppbits definieren die Art der Stoppbits, die mit einer der drei seriellen Kommunikationsschnittstellen verwendet werden.
Standard 1 9600 Keine
1
Standardeinstellungen des Hosts:
· Modbus-Adresse: 1
· Baud Rate: 9600
Die Standardkonfiguration lautet: 8 Datenbits, keine Parität und ein Stoppbit.
Die Dip-Schalter (unterhalb Klemme 26 und 27):
Tastenwiderstand
1 – Widerstand reduzieren
2 – Widerstand erhöhen 3 – Endwiderstand
ON
Drücken Sie die Taste auf ON (wie der Pfeil anzeigt), wird der entsprechenden Widerstand verbunden.
Bereich/Optionen 1 bis 247 2400, 4800, 9600, 19200 Keine, gerade, ungerade 1,2
12 3
RAYCHEM-OM-EU1850-Elexant450cModbus-ML-2504
chemelex.com | 10
2. MODBUS-REGISTERÜBERSICHT 2.1 Status Alarmausgang Modbus-Funktionscode: 1 Modbus-Startadresse: 0 Modbus-Blockgröße: 17 Anzahl von Blöcken: 1
Beschreibung
Modbus-Adresse
TS 1 Alarm hoch 0
TS 1 Alarm niedrig 1
TS 1 Fehlschlag
2
TS 2 Alarm hoch 3
TS 2 Alarm niedrig 4
TS 2 Fehlschlag 5
Interner Fehler
15
Schaltschrank Sammelstörung 16 Status
Funktion 1 1 1 1 1 1 1
1
2.2 Steuergerät-Einstellungsparameter Modbus-Funktionscode: 1, 5, 15 Modbus-Startadresse: 145 Modbus-Blockgröße: 9 Anzahl von Blöcken: 1
Beschreibung TS1 Fehlermodus TS2 Fehlermodus
Modbus-Adresse 145 146
Funktion 1, 5, 15 1, 5, 15
Testprogramm
147
1, 5, 15
Alarmsummer
148
TS1 Alarm hoch Funktion aus
149
TS1 Alarm hoch Funktion aus
150
TS1 Alarm niedrig Funktion aus
151
TS1 Alarm niedrig Funktion aus
152
Schaltschrank Sammelstörung
153
1, 5, 15 1, 5, 15 1, 5, 15 1, 5, 15 1, 5, 15 1, 5, 15
Anmerkungen 0 = kein Alarm, 1 = Alarm 0 = kein Alarm, 1 = Alarm 0 = kein Alarm, 1 = Alarm 0 = kein Alarm, 1 = Alarm 0 = kein Alarm, 1 = Alarm 0 = kein Alarm, 1 = Alarm 0 = kein interner Fehler, 1 = interner Fehler 0 = kein Alarm, 1 = Alarm
Anmerkungen 0 = Fehler aus, 1 = Fehler ein 0 = Fehler aus, 1 = Fehler ein 0 = nein, 1 = ja, Testprogramm wird ausgeführt 0 = nein, Summer aus, 1 = ja, Summer ein 0 = Alarm aktiviert, 1 = Alarm deaktiviert 0 = Alarm aktiviert, 1 = Alarm deaktiviert 0 = Alarm aktiviert, 1 = Alarm deaktiviert 0 = Alarm aktiviert, 1 = Alarm deaktiviert 0 = Alarm deaktiviert, 1 = Alarm aktiviert
RAYCHEM-OM-EU1850-Elexant450cModbus-ML-2504
chemelex.com | 11
2.3 Steuergerätestatus Modbus-Funktionscode: 2 Modbus-Startadresse: 3 Modbus-Blockgröße: 3 Anzahl von Blöcken: 1
Beschreibung
Raw-Schalter Ausgang1
Tastensperre-Status
Raw-Schalter Ausgang2
Modbus-Adresse 3 4 5
Funktion 2 2 2
Anmerkungen 0 = HC1-Relais aus, 1 = HC1-Relais ein 0 = nein, 1 = ja, gesperrt 0 = HC2-Relais aus, 1 = HC2-Relais ein
2.4 INPUT-Parameter Modbus-Funktionscode: 3, 6, 16 Modbus-Startadresse: 0 Modbus-Blockgröße: 20 Anzahl von Blöcken: 1
Beschreibung
ModbusAdresse
Funktion
Anmerkungen
Einheiten Skalierung
Temperatursollwert 1 0
PASC Mindestrohrweite 2
1
Regelmodus
2
3, 6, 16 3, 6, 16
3, 6, 16
0 °C bis 80 °C (0 °C bis 245 °C für PT100)
°C
10, 15, 20, 25, 32, 40, 50, 60, 70, 80,
100, 125; wenn ungültig, wird der
DN
Wert 25 verwendet
4 = Leitung/Leitung, 5 = PASC/PASC,
6 = Leitung/PASC, 7 = PASC/Leitung,
8 = Leitung/AUS, 9 = PASC/AUS,
10 = AUS/Leitung, 11 = AUS/PASC,
12 = AUS/AUS
Zehntel* 1
1
Totband 1
3
PASC Mindestumgebungstemperatur 1
4
PASC Mindestrohrweite 1
5
PASCLeistungsanpassung
6
Sensoreinrichtung 7
Sprache
8
3, 6, 16 1,0 °C bis 5 °C
°C
3, 6, 16 3, 6, 16 3, 6, 16 3, 6, 16
3, 6, 16
40 °C bis 0 °C
°C
10, 15, 20, 25, 32, 40, 50, 60, 70, 80,
100, 125; wenn ungültig, wird der
DN
Wert 25 verwendet
70, 80, 90, 100, 110, 120, 130, 140
%
Bit 1 = TS 1 zuweisen für Kreis 1
Bit 2 = TS 2 zuweisen für Kreis 1
Bit 5 = TS 1 zuweisen für Kreis 2
Bit 6 = TS 2 zuweisen für Kreis 2
Bit 0,3,4,7 = NV
0 = Nein (keine Auswahl) 1 = Ja
(Auswahl)
0 = DÄNISCH, 1 = DEUTSCH, 2 = NIEDERLÄNDISCH, 3 = ENGLISCH, 4 = FRANZÖSISCH, 5 = ITALIENISCH, 6 = SCHWEDISCH, 7 = NORWEGISCH, 8 = FINNISCH, 9 = RUSSISCH, 10 = TSCHECHISCH, 11 = POLNISCH
Zehntel* Zehntel* 1 1
1
1
* Temperatur wird in Zehnteln eines °C angezeigt (Beispiel: 10 °C = 100) RAYCHEM-OM-EU1850-Elexant450cModbus-ML-2504
chemelex.com | 12
Beschreibung
Land
Kabeltyp 1 Kabeltyp 2 Totband 2 Datum-Jahr
ModbusAdresse
Funktion
Anmerkungen
Einheiten Skalierung
0 = DEUTSCHLAND, 1 =
ÖSTERREICH,
2 = SCHWEIZ, 3 =
GROSSBRITANNIEN,
4 = FRANKREICH, 5 = ITALIEN,
6 = POLEN, 7 = TSCHECHISCHE
9
3, 6, 16 REPUBLIK,
1
8 = DÄNEMARK, 9 = BELGIEN,
10 = RUSSLAND, 11 = CHINA,
12 = JAPAN, 13 = SCHWEDEN,
14 = NORWEGEN, 15 = LITAUEN;
16 = SLOVAKIEN, 17 = NIEDERLANDE,
18 = FINNLAND, 19 = IRLAND
0 = 10XL2_ZH, 1 = 15XL2_ZH,
10
3, 6, 16 2 = 26XL2_ZH, 3 = 31XL2_ZH,
1
4 = FS_C10_2X, 5 = SONSTIGE
0 = 10XL2_ZH, 1 = 15XL2_ZH,
11
3, 6, 16 2 = 26XL2_ZH, 3 = 31XL2_ZH,
1
4 = FS_C10_2X, 5 = SONSTIGE
12
3, 6, 16 1,0 °C bis 5 °C
°C
Zehntel*
13
3, 6, 16 0099
Jahr
1
Datum-Monat
14
3, 6, 16 112
Monat 1
Datum-Tag
15
3, 6, 16 131
Tag
1
Uhrzeit-Stunde
16
3, 6, 16 023
Stunde 1
Uhrzeit-Minute
17
3, 6, 16 059
Temperatursollwert 2 18
PASC Mindestumgebungstemperatur 2
19
3, 6, 16 3, 6, 16
0 °C bis 80 °C (0 °C bis 245 °C für PT100)
40 °C bis 0 °C
* Temperatur wird in Zehnteln eines °C angezeigt (Beispiel: 10 °C = 100)
Minute °C °C
1 Zehntel* Zehntel*
2.5 Temperatursensor-Parameter Modbus-Funktionscode: 3, 6, 16 Modbus-Startadresse: 20 Modbus-Blockgröße: 4 Anzahl von Blöcken: 1
Beschreibung
ModbusAdresse
Funktion
Anmerkungen
TS 1 Alarm hoch Sollwert**
20
TS 1 Alarm niedrig Sollwert**
21
TS 2 Alarm hoch Sollwert**
22
TS 2 Alarm niedrig Sollwert**
23
3, 6, 16 3, 6, 16 3, 6, 16 3, 6, 16
2 °C bis 90 °C (2 °C bis 250 °C für PT100)
40 °C bis 78 °C (40 °C bis +245 °C für PT100)
2 °C bis 90 °C (2 °C bis 250 °C für PT100)
40 °C bis 78 °C (40 °C bis 245 °C für PT100)
* Temperatur wird in Zehnteln eines °C angezeigt (Beispiel: 10 °C = 100) ** Kann über Abschnitt 2.2 deaktiviert werden
Einheiten Skalierung
°C
Zehntel*
°C
Zehntel*
°C
Zehntel*
°C
Zehntel*
RAYCHEM-OM-EU1850-Elexant450cModbus-ML-2504
chemelex.com | 13
2.6 Überschreiben
Modbus-Funktionscode: 3, 6, 16 Modbus-Startadresse: 34 Modbus-Blockgröße: 2 Anzahl von Blöcken: 1
Beschreibung
Remote Übersteuerung Status 1
Remote Übersteuerung Status 2
ModbusAdresse
Funktion
Anmerkungen
Einheiten Skalierung
0 = Übersteuerung nicht aktiv
1 = Übersteuerung aktiv Einschalten
34
3, 6, 16 erzwingen
2 = Übersteuerung aktiv Ausschalten erzwingen
0 = Übersteuerung nicht aktiv
1 = Übersteuerung aktiv Einschalten
35
3, 6, 16 erzwingen
2 = Übersteuerung aktiv Ausschalten erzwingen
2.7 Steuergerät Identifikationsnummer
Modbus-Funktionscode: 3, 6, 16 Modbus-Startadresse: 90 Modbus-Blockgröße: 10 Anzahl von Blöcken: 1
Beschreibung
Identifizierungsnummer des Steuergeräts
ModbusAdresse
Funktion
Anmerkungen
Einheiten Skalierung
Buchstaben (AZ) Zahlen (09), /.()_-#
Zwei Zeichen pro Adresse.
Abschlusszeichen = Null oder Leerschritt
Hinweis: LSByte von 99 ist immer Null.
90 bis 99 3, 6, 16 Den ASCII-Code für die obigen
Zeichen eingeben, z. B. 0x4142 (Hex
oder 16706 in Dez) für Register 90
und 0x3031 (in Hex oder 12337 in
Dez) für Register 91 eingeben. Die
Steuergerätekennung wird dann AB01
sein.
2.8 Konsolenparameter
Modbus-Funktionscode: 3, 6, 16 Modbus-Startadresse: 120 Modbus-Blockgröße: 2 Anzahl von Blöcken: 1
Beschreibung
Passcode für Tastensperre
Sperre aktivieren/ deaktivieren
ModbusAdresse
Funktion
Anmerkungen
Einheiten Skalierung
1 bis 9999
Ein falsch eingegebener Passcode wird
120
3, 6, 16
ignoriert, und eine korrekte Eingabe ist für zwei Minuten gültig. (dient zur
Eingabe des Codes zur Freigabe den
Zugriffs auf das Register 121)
121
3, 6, 16
0 = Tastensperre inaktiv, 1 = Tastensperre aktiv,
RAYCHEM-OM-EU1850-Elexant450cModbus-ML-2504
chemelex.com | 14
2.9 Temperatursensor-Parameter
Modbus-Funktionscode: 3, 6, 16 Modbus-Startadresse: 147 Modbus-Blockgröße: 1 Anzahl von Blöcken: 1
Beschreibung
ModbusAdresse
Timeout für Kommunikationsaktivität
147
Funktion Anmerkungen
3, 6, 16
Dient für Lastabwürfe und remote Übersteuerung 0255
Einheiten Skalierung
s
1
2.10 Allgemeine Informationen zum Steuergerät Modbus-Funktionscode: 4 Modbus-Startadresse: 0 Modbus-Blockgröße: 4 Anzahl von Blöcken: 1
Beschreibung Gerätetyp
ModbusAdresse
Funktion Anmerkungen
0
4
Fixed value = 450
Firmware Version 1
4
Firmware Version-Major 0-255
Firmware Version 2
4
Firmware Version-Minor 0-255
Firmware Version 3
4
Firmware Version-Build 0-255
Einheiten Skalierung
1
1
1
1
2.11 Status der dynamischen Ausgabe Modbus-Funktionscode: 4 Modbus-Startadresse: 50 Modbus-Blockgröße: 15 Anzahl von Blöcken: 1
Beschreibung Steuerungsausgabe Betriebszyklus 1
Status der Verfolgungssteuerung
PASC Ein-Zähler 1
ModbusAdresse
Funktion
Anmerkungen
Einheiten Skalierung
50
4
0 = vollständig aus, 100 = vollständig ein
%
1
2 Ziffern, die erste für Kreis 1 und die zweite für Kreis 2 (z. B. bedeutet 0 beide sind normal, 15 bedeutet Kreis 1 = Abschaltung erzwungen, Kreis 2 = Einschaltung erzwungen)
51
4
0 = Normale Temperaturregelung
1
1 = Ausgabe Übersteuerung
Ausschalten erzwungen
2 = Testprogramm wird ausgeführt
5 = Ausgabe Übersteuerung Einschalten erzwungen
52
4
s
1
PASC Aus-Zähler 1 53
4
s
1
PASC Nächster Schalter Zähler 1
54
4
s
1
PASC Prozent Ein 1 55
4
0 = vollständig aus, 100 = vollständig ein
%
1
PASC Ausgang Status 1
56
4
0 = Aus, 1 = Ein
1
RAYCHEM-OM-EU1850-Elexant450cModbus-ML-2504
chemelex.com | 15
Beschreibung
ModbusAdresse
Funktion
Anmerkungen
Einheiten Skalierung
PASC Gesamt Zeit 1 57
4
s
1
Steuerungsausgabe Betriebszyklus 2
58
4
0 = vollständig aus, 100 = vollständig ein
%
1
PASC Ein-Zähler 2 59
4
s
1
PASC Aus-Zähler 2 60
4
s
1
PASC Nächster Schalter Zähler 2
61
4
s
1
PASC Prozent Ein 2 62
4
0 = vollständig aus, 100 = vollständig ein
%
1
PASC Ausgang Status 2
63
4
0 = Aus, 1 = Ein
1
PASC Gesamt Zeit 2 64
4
s
1
2.12 Analoge Anzeigen Modbus-Funktionscode: 4 Modbus-Startadresse: 81 Modbus-Blockgröße: 2 Anzahl von Blöcken: 1
Beschreibung
Aktuelle TS 1 Temperatur Aktuelle TS 2 Temperatur
ModbusAdresse 81
82
Funktion Anmerkungen
4
TS 1 Fehlschlag = +3000,0 °C TS 1 nicht verwendet = +3200,0 °C
TS 2 Fehlschlag = +3000,0 °C
4
TS 2 nicht verwendet = +3200,0 °C
* Temperatur wird in Zehnteln eines °C angezeigt (Beispiel: 10 °C = 100)
Einheiten Skalierung
°C
Zehntel*
°C
Zehntel*
2.13 Haftungsausschluss
Die MODBUS-Zuordnungsinformationen sind urheberrechtlich geschützt und vertraulich. Die Verwendung dieser Informationen ist ausschließlich für die Umsetzung einer Kommunikationsverbindung zwischen Kundengeräten und Raychem-Steuergeräten zulässig. Sie dürfen nicht für andere Zwecke verwendet werden und ohne die schriftliche Zustimmung von Chemelex Thermal LLC nicht an Dritte weitergegeben werden.
RAYCHEM-OM-EU1850-Elexant450cModbus-ML-2504
chemelex.com | 16
RAYCHEM-OM-EU1850-Elexant450cModbus-ML-2504
chemelex.com | 17
België / Belgique Tel +32 16 21 35 02 Fax +32 16 21 36 04 SalesBelux@chemelex.com
Bulgaria Tel +359 2 973 33 73 SalesEE@chemelex.com
Ceská Republika Tel +420 606 069 618 (Comm)
+420 602 232 969 (Ind) infoCZ@chemelex.com
Danmark Tel +45 70 11 04 00 SalesDK@chemelex.com
Deutschland Tel 0800 181 82 05 SalesDE@chemelex.com
España Tel +34 911 59 30 60 Fax +34 900 98 32 64 SalesES@chemelex.com
France Tél 0800 90 60 45 SalesFR@chemelex.com
Hrvatska Tel +385 51 225 073 (Comm)
+385 1 605 01 88 (Ind) SalesEE@chemelex.com
Italia Tel +39 02 577 61 51 Fax +39 02 577 61 55 28 SalesIT@chemelex.com
Lietuva/Latvija/Eesti Tel +370 698 411 56 SalesEE@chemelex.com
Magyarország Tel +36 1 253 76 17 SalesHU@chemelex.com
Nederland Tel 0800 022 49 78 SalesNL@chemelex.com
Norge Tel +47 66 81 79 90 SalesNO@chemelex.com
Österreich Tel 0800 29 74 10 SalesAT@chemelex.com
Polska Tel +48 22 331 29 50 Fax +48 22 331 29 51 SalesPL@chemelex.com
Tel +7 7112 31 67 03170 SalesKZ@chemelex.com
Serbia and Montenegro Tel +386 41 665 634 (Comm)
+381 230 439 519 (Ind) SalesEE@chemelex.com
Schweiz/Suisse/Svizzera Tel +41 (41) 766 30 80 Fax +41 (41) 766 30 81 infoCH@chemelex.com
Suomi Puh 0800 11 67 99 SalesFI@chemelex.com
Sverige Tel +46 31 335 58 00 SalesSE@chemelex.com
Türkiye Tel +90 545 284 09 05 SalesEE@chemelex.com
UK/Ireland Tel 0800 969 013 SalesUK@chemelex.com
©2025 Chemelex. All Chemelex marks and logos are owned or licensed by Chemelex Europe GmbH or its affiliates. All other trademarks are the property of their respective owners. Chemelex reserves the right to change specifications without notice. RAYCHEM-OM-EU1850-Elexant450cModbus-ML-2504
chemelex.com