Elexant 450c-Modbus
Modbus Protocol Interface Mapping
Firmware version V2.1.1

![]()
1. INTRODUCTION
This manual details the Modbus registers of the Raychem Elexant 450c-Modbus. It is intended to be used by the users’ system integrators who wish to interface with their external device (i.e. DCS or Building management system -BMS- system) to the using the Modbus protocol. The manual includes details of the system’s current configuration, availability resources, set-up parameters, current conditions, alarm status, log info and numerous other fixed and variable data points.
1.1 How to Use This Manual
The Elexant 450c-Modbus register can be accessed by DCS or BMS systems. However, this should only be done by expert users who understand that the system makes use of extensive semaphore fields to assure synchronization between the possibility of multiple users and conflicting instructions. These portions of the Modbus register map provide access to the current set-up and real time values being measured by the system. A snap shot of the current conditions, data for trending, alarm status, the current setting for the alarm thresholds and setpoints can be easily read without any risk to the system performance.
The entire Modbus register map is included in this document for completeness. Writing to the database is within the capability of most Modbus host devices. However, we strongly recommend that system integrators who write to the database must thoroughly test their system to ensure it is working properly and that there are no unintended consequences.
1.2 Modbus Communications
The controller acts as Modbus slave device. A modbus master device can read and write to the controller. This enables the possibility to monitor, configure and view the alarms remotely. The protocol used is Modbus RTU via RS485.
| Variable | Description | Default | Range/options |
| Address | Modbus Station Address used to identify the controller. | 1 | 1 to 247 |
| Baud | The data rate at which communications occur on the serial network. | 9600 | 2400, 4800, 9600, 19200 |
| Parity | Parity Defines the type of parity bit to be used with any of the three serial communications ports. | None | None, Odd, Even |
| Stop Bits | Defines the number of stop bits used with any of the three serial communications ports. | 1 | 1,2 |
The host defaults are:
- Modbus Address: 1
- Baud Rate: 9600
The standard configuration is: 8 data bits, no parity and one stop bit.
The dip switches (below terminal 26 and 27):
| Button | Resistor |
| 1 – | Pull down resistor |
| 2 – | Pull up resistor |
| 3 – | Termination resistor |
Push the button to ON (as the arrow indicates) side will connect the corresponding resistor in.

2. MODBUS REGISTER MAP
2.1 Alarm Status Coils
Modbus Function Code: 1
Modbus Start Address: 0
Modbus Block Size: 17
Number of Blocks: 1
| Description | Modbus Address | Function | Comments |
| High TS 1 Alarm | 0 | 1 | 0 = no alarm, 1 = alarm |
| Low TS 1 Alarm | 1 | 1 | 0 = no alarm, 1 = alarm |
| TS 1 Failure | 2 | 1 | 0 = no alarm, 1 = alarm |
| High TS 2 | 3 | 1 | 0 = no alarm, 1 = alarm |
| Low TS 2 | 4 | 1 | 0 = no alarm, 1 = alarm |
| TS 2 Failure | 5 | 1 | 0 = no alarm, 1 = alarm |
| Internal Error | 15 | 1 | 0 = no internal error, 1 = internal error |
| Panel Alarm status | 16 | 1 | 0 = no alarm, 1 = alarm |
2.2 Controller Setup Parameters
Modbus Function Code: 1,5,15
Modbus Start Address: 145
Modbus Block Size: 9
Number of Blocks: 1
| Description | Modbus Address | Function | Comments |
| TS1 Fail Mode | 145 | 1, 5, 15 | 0 = Fail off, 1 = Fail on |
| TS2 Fail Mode | 146 | 1, 5, 15 | 0 = Fail off, 1 = Fail on |
| Test Program | 147 | 1, 5, 15 | 0 = no, 1 = yes, test program is running |
| Alarm Buzzer | 148 | 1, 5, 15 | 0 = no, buzzer off 1 = yes, buzzer on |
| TS1 high alarm feature off | 149 | 1, 5, 15 | 0 = alarm active, 1 = alarm deactive |
| TS1 high alarm feature off | 150 | 1, 5, 15 | 0 = alarm active, 1 = alarm deactive |
| TS1 low alarm feature off | 151 | 1, 5, 15 | 0 = alarm active, 1 = alarm deactive |
| TS1 low alarm feature off | 152 | 1, 5, 15 | 0 = alarm active, 1 = alarm deactive |
| Panel Alarm Control | 153 | 1, 5, 15 | 0 = alarm deactive, 1 = alarm active |
2.3 Controller Status
Modbus Function Code: 2
Modbus Start Address: 3
Modbus Block Size: 3
Number of Blocks: 1
| Description | Modbus Address | Function | Comments |
| Raw Switch Output1 | 3 | 2 | 0 = HC1 relay off, 1 = HC1 relay on |
| Keylock Status | 4 | 2 | 0 = no, 1 = yes, locked |
| Raw Switch Output2 | 5 | 2 | 0 = HC2 relay off, 1 = HC2 relay on |
2.4 INPUT Parameters
Modbus Function Code: 3, 6, 16
Modbus Start Address: 0
Modbus Block Size: 20
Number of Blocks: 1
| Description | Modbus Address | Function | Comments | Units | Scaling |
| Control Temperature Setpoint 1 | 0 | 3, 6, 16 | 0°C to 80°C (0°C to 245°C for PT100) | °C | 10ths* |
| PASC Minimum Pipe Size 2 | 1 | 3, 6, 16 | 10, 15, 20, 25, 32, 40, 50, 60, 70, 80, 100, 125 if invalid value 25 is used | DN | 1 |
| Switch Control Mode | 2 | 3, 6, 16 | 4 = Line/Line, 5 = PASC/PASC, 6 = Line/PASC, 7 = PASC/Line, 8 = Line/OFF, 9 = PASC/OFF, 10 = OFF/Line, 11 = OFF/PASC, 12 = OFF/OFF |
– | 1 |
| Deadband 1 | 3 | 3, 6, 16 | 1.0°C to 5°C | °C | 10ths* |
| PASC Minimum Ambient Temperature 1 | 4 | 3, 6, 16 | -40°C to 0°C | °C | 10ths* |
| PASC Minimum Pipe Size 1 | 5 | 3, 6, 16 | 10, 15, 20, 25, 32, 40, 50, 60, 70, 80, 100, 125 if invalid value 25 is used | DN | 1 |
| PASC Power Adjust | 6 | 3, 6, 16 | 70,80,90,100,110,120,130,140 | % | 1 |
| Sensor Setup | 7 | 3, 6, 16 | bit 1 = TS 1 assign for Circuit 1 bit 2 = TS 2 assign for Circuit 1 bit 5 = TS 1 assign for Circuit 2 bit 6 = TS 2 assign for Circuit 2 bit 0,3,4,7 = NA 0 = No (No select) 1 = Yes (Select) |
– | 1 |
| Language | 8 | 3, 6, 16 | 0 = DANISH, 1 = GERMAN, 2 = DUTCH, 3 = ENGLISH, 4 = FRENCH, 5 = ITALIAN, 6 = SWEDISH, 7 = NORWEGIAN, 8 = FINNISH, 9 = RUSSIAN, 10 = CZECH, 11 = POLISH |
– | 1 |
| Country | 9 | 3, 6, 16 | 0 = GERMANY, 1 = AUSTRIA, 2 = SWITZERLAND, 3 = UK, 4 = FRANCE, 5 = ITALY, 6 = POLAND, 7 = CZECH_REPUBLIC, 8 = DENMARK, 9 = BELGIUM, 10 = RUSSIA, 11 = CHINA, 12 = JAPAN, 13 = SWEDEN, 14 = NORWAY, 15 = LITHUANIA, 16 = SLOVAKIA, 17 = NETHERLANDS, 18 = FINLAND, 19 = IRELAND |
– | 1 |
| Cable type 1 | 10 | 3, 6, 16 | 0 = 10XL2_ZH, 1 = 15XL2_ZH, 2 = 26XL2_ZH, 3 = 31XL2_ZH, 4 = FS_C10_2X, 5 = OTHER |
– | 1 |
| Cable type 2 | 11 | 3, 6, 16 | 0 = 10XL2_ZH, 1 = 15XL2_ZH, 2 = 26XL2_ZH, 3 = 31XL2_ZH, 4 = FS_C10_2X, 5 = OTHER |
– | 1 |
| Deadband 2 | 12 | 3, 6, 16 | 1.0°C to 5°C | °C | 10ths* |
| Date-Year | 13 | 3, 6, 16 | 00 – 99 | year | 1 |
| Date-Month | 14 | 3, 6, 16 | 1 – 12 | month | 1 |
| Date-Day | 15 | 3, 6, 16 | 1 – 31 | day | 1 |
| Time-Hour | 16 | 3, 6, 16 | 0 – 23 | hour | 1 |
| Time-Minute | 17 | 3, 6, 16 | 0 – 59 | minute | 1 |
| Control Temperature Setpoint 2 | 18 | 3, 6, 16 | 0°C to 80°C (0°C to 245°C for PT100) | °C | 10ths* |
| PASC Minimum Ambient Temperature 2 | 19 | 3, 6, 16 | -40°C to 0°C | °C | 10ths* |
* Temperature displayed in 1/10th of °C (example: 10°C = 100)
2.5 Temperature Sensor Parameters
Modbus Function Code: 3, 6, 16
Modbus Start Address: 20
Modbus Block Size: 4
Number of Blocks: 1
| Description | Modbus Address | Function | Comments | Units | Scaling |
| High TS 1 Alarm Setpoint** | 20 | 3, 6, 16 | 2°C – 90°C (2°C to 250°C for PT100) |
°C | 10ths* |
| Low TS 1 Alarm Setpoint** | 21 | 3, 6, 16 | -40°C – 78°C (-40°C to +245°C for PT100) |
°C | 10ths* |
| High TS 2 Alarm Setpoint** | 22 | 3, 6, 16 | 2°C – 90°C (2°C to 250°C for PT100) |
°C | 10ths* |
| Low TS 2 Alarm Setpoint** | 23 | 3, 6, 16 | -40°C – 78°C (-40°C to 245°C for PT100) |
°C | 10ths* |
* Temperature displayed in 1/10th of °C (example: 10°C = 100)
** Can be disabled through section 2.2
2.6 Override
Modbus Function Code: 3, 6, 16
Modbus Start Address: 34
Modbus Block Size: 2
Number of Blocks: 1
| Description | Modbus Address | Function | Comments | Units | Scaling |
| Remote Override Status 1 | 34 | 3, 6, 16 | 0 = Override not active 1 = Force on Override active 2 = Force off Override active |
– | – |
| Remote Override Status 2 | 35 | 3, 6, 16 | 0 = Override not active 1 = Force on Override active 2 = Force off Override active |
– | – |
2.7 Controller’s Identification Tag
Modbus Function Code: 3, 6, 16
Modbus Start Address: 90
Modbus Block Size: 10
Number of Blocks: 1
| Description | Modbus Address | Function | Comments | Units | Scaling |
| Controller’s Identification Tag | 90 to 99 | 3, 6, 16 | Letters(A-Z) numbers(0-9), /.()_-# Two characters per address. String terminators = Null or space Note: LSByte of 99 is always Null. Input the ascii code for the characters above, for example, input 0x4142 (Hex or 16706 in Dec) for register 90, and 0x3031 (in Hex or 12337 in Dec) for register 91, then the controller ID will be AB01. |
– | – |
2.8 Console Parameters
Modbus Function Code: 3, 6, 16
Modbus Start Address: 120
Modbus Block Size: 2
Number of Blocks: 1
| Description | Modbus Address | Function | Comments | Units | Scaling |
| Keylock Passcode | 120 | 3, 6, 16 | 1 to 9999: Incorrect passcode input will be ignored, and correct input will be valid for 2 minutes. (used to enter the code to unlock access to register 121) |
– | – |
| Lock Enable/ Disable | 121 | 3, 6, 16 | 0 = Keylock inactive, 1 = Keylock active |
– | – |
2.9 Temperature Sensor Parameters
Modbus Function Code: 3, 6, 16
Modbus Start Address: 147
Modbus Block Size: 1
Number of Blocks: 1
| Description | Modbus Address | Function | Comments | Units | Scaling |
| Communications Activity Time-out | 147 | 3, 6, 16 | Used for load shedding and remote override 0-255 | sec | 1 |
2.10 General Controller Information
Modbus Function Code: 4
Modbus Start Address: 0
Modbus Block Size: 4
Number of Blocks: 1
| Description | Modbus Address | Function | Comments | Units | Scaling |
| Device Type | 0 | 4 | Fixed value = 450 | – | 1 |
| Firmware Version | 1 | 4 | Firmware Version-Major 0-255 | – | 1 |
| Firmware Version | 2 | 4 | Firmware Version-Minor 0-255 | – | 1 |
| Firmware Version | 3 | 4 | Firmware Version-Build 0-255 | – | 1 |
2.11 Dynamic Output Status
Modbus Function Code: 4
Modbus Start Address: 50
Modbus Block Size: 15
Number of Blocks: 1
| Description | Modbus Address | Function | Comments | Units | Scaling |
| Control Output Duty Cycle 1 | 50 | 4 | 0 = full off, 100 = full on | % | 1 |
| Tracing Control Status | 51 | 4 | 2 digits, the first for circuit 1 and the second for circuit 2 (for example, 0 means both are normal, 15 means circuit 1 = force off, circuit 2 = force on) 0 = normal temperature control 1 = output override force off 2 = test program in progress 5 = output override force on |
– | 1 |
| PASC On-Count 1 | 52 | 4 | sec | 1 | |
| PASC Off-Count 1 | 53 | 4 | sec | 1 | |
| PASC Next Switch Count 1 | 54 | 4 | sec | 1 | |
| PASC Percent On 1 | 55 | 4 | 0 = full off, 100 = full on | % | 1 |
| PASC Output State 1 | 56 | 4 | 0 = Off, 1 = On | – | 1 |
| PASC Total Time 1 | 57 | 4 | sec | 1 | |
| Control Output Duty Cycle 2 | 58 | 4 | 0 = full off, 100 = full on | % | 1 |
| PASC On-Count 2 | 59 | 4 | sec | 1 | |
| PASC Off-Count 2 | 60 | 4 | sec | 1 | |
| PASC Next Switch Count 2 | 61 | 4 | sec | 1 | |
| PASC Percent On 2 | 62 | 4 | 0=full off, 100=full on | % | 1 |
| PASC Output State 2 | 63 | 4 | 0 = Off, 1 = On | – | 1 |
| PASC Total Time 2 | 64 | 4 | sec | 1 |
2.12 Analog Readings
Modbus Function Code: 4
Modbus Start Address: 81
Modbus Block Size: 2
Number of Blocks: 1
| Description | Modbus Address | Function | Comments | Units | Scaling |
| Current TS 1 Temperature | 81 | 4 | TS 1 failure = +3000.0°C TS 1 not used = +3200.0°C | °C | 10ths* |
| Current TS 2 Temperature | 82 | 4 | TS 2 failure = +3000.0°C TS 2 not used = +3200.0°C | °C | 10ths* |
* Temperature displayed in 1/10th of °C (example: 10°C = 100)
2.13 Disclaimer
MODBUS map information is proprietary and confidential. Use of this information is permitted solely in order to implement a communications link between customer equipment and Raychem controllers. It may not be used for any other purpose, and it is not to be disclosed to 3rd parties without the written consent of Chemelex Thermal LLC.

België / Belgique
Tel +32 16 21 35 02
Fax +32 16 21 36 04
SalesBelux@chemelex.com
Bulgaria
Tel +359 2 973 33 73
SalesEE@chemelex.com
Česká Republika
Tel +420 606 069 618 (Comm)
+420 602 232 969 (Ind)
infoCZ@chemelex.com
Danmark
Tel +45 70 11 04 00
SalesDK@chemelex.com
Deutschland
Tel 0800 181 82 05
SalesDE@chemelex.com
España
Tel +34 911 59 30 60
Fax +34 900 98 32 64
SalesES@chemelex.com
France
Tél 0800 90 60 45
SalesFR@chemelex.com
Hrvatska
Tel +385 51 225 073 (Comm)
+385 1 605 01 88 (Ind)
SalesEE@chemelex.com
Italia
Tel +39 02 577 61 51
Fax +39 02 577 61 55 28
SalesIT@chemelex.com
Lietuva/Latvija/Eesti
Tel +370 698 411 56
SalesEE@chemelex.com
Magyarország
Tel +36 1 253 76 17
SalesHU@chemelex.com
Nederland
Tel 0800 022 49 78
SalesNL@chemelex.com
Norge
Tel +47 66 81 79 90
SalesNO@chemelex.com
Österreich
Tel 0800 29 74 10
SalesAT@chemelex.com
Polska
Tel +48 22 331 29 50
Fax +48 22 331 29 51
SalesPL@chemelex.com
Казахстан
Tel +7 7112 31 67 03170
SalesKZ@chemelex.com
Serbia and Montenegro
Tel +386 41 665 634 (Comm)
+381 230 439 519 (Ind)
SalesEE@chemelex.com
Schweiz/Suisse/Svizzera
Tel +41 (41) 766 30 80
Fax +41 (41) 766 30 81
infoCH@chemelex.com
Suomi
Puh 0800 11 67 99
SalesFI@chemelex.com
Sverige
Tel +46 31 335 58 00
SalesSE@chemelex.com
Türkiye
Tel +90 545 284 09 05
SalesEE@chemelex.com
UK/Ireland
Tel 0800 969 013
SalesUK@chemelex.com
![]()
©2025 Chemelex. All Chemelex marks and logos are owned or licensed by Chemelex Europe GmbH or its affiliates. All other trademarks are the property of their respective owners. Chemelex reserves the right to change specifications without notice.
RAYCHEM-OM-EU1850-Elexant450cModbus-ML-2504