SINOTIMER STVP-932

SINOTIMER STVP-932 Three-Phase Digital Display Self-Resetting Adjustable Intelligent Multi-Function Over-Voltage Protector

Model: STVP-932 | Brand: SINOTIMER

1. Introduction

The SINOTIMER STVP-932 is an advanced three-phase intelligent voltage protector designed to provide comprehensive protection for electrical equipment against various power supply anomalies. This device features a digital display for real-time voltage monitoring and offers adjustable parameters for over-voltage, under-voltage, voltage unbalance, phase sequence, zero line break, and phase failure protection. Its self-resetting capability ensures continuous operation and enhanced system reliability.

2. Safety Information

  • Installation and maintenance should only be performed by qualified electricians.
  • Ensure the main power supply is disconnected before any installation, wiring, or maintenance work.
  • Verify that the voltage and current ratings of the protector match your application requirements.
  • Do not operate the device if it shows signs of damage.
  • Always follow local electrical codes and regulations.

3. Product Overview

3.1 Features

  • Over-voltage protection
  • Under-voltage protection
  • Voltage display (separate ABC phase volt measurement)
  • Three-phase voltage unbalance protection
  • Phase sequence protection (reverse phase protection)
  • Zero line break protection
  • Phase failure protection
  • Adjustable over-voltage protection value
  • Adjustable over-voltage recovery value
  • Adjustable over-voltage protection action time
  • Adjustable under-voltage protection value
  • Adjustable under-voltage recovery value
  • Adjustable under-voltage protection action time
  • Adjustable 3-phase voltage unbalance protection value
  • Adjustable 3-phase voltage unbalance protection action time
  • Adjustable delay time after power-on
  • Adjustable fault recovery delay time
  • Reset mode selection
  • Fault inquiry function
  • Factory data reset function

3.2 Components

The STVP-932 features a clear digital display, control buttons for setting parameters, and robust terminals for secure wiring.

Front view of the SINOTIMER STVP-932 voltage protector
Figure 1: Front view of the STVP-932 showing digital display and control buttons.
Close-up of the STVP-932 digital display showing individual phase voltages
Figure 2: Digital display indicating voltage readings for phases A, B, and C.

4. Specifications

ParameterValue
Model NumberSTVP-932
Power Supply3*230V / 400V AC 50/60Hz
Max. Loading Power50A, 63A, or 80A (model dependent)
Over-voltage Protection Range221V~300V-OFF (Adjustable, Default: 280V)
Over-voltage Recovery Range220V~299V (Default: 250V)
Over-voltage Action Time0.1~10 seconds (Adjustable, Default: 0.2s)
Under-voltage Protection Range150V~219V-OFF (Adjustable, Default: 160V)
Dimensions (L x W x H)72 x 65 x 80mm
MaterialABS + Electronic Components
ColorWhite
Dimensional drawing of the STVP-932 voltage protector
Figure 3: Dimensions of the STVP-932 device.

5. Setup and Installation

The STVP-932 is designed for DIN rail mounting within an electrical enclosure. Ensure proper ventilation and clearance around the device.

5.1 Mounting

Attach the protector to a standard 35mm DIN rail by snapping the clips on the back of the device onto the rail. Ensure it is securely fastened.

Side view of the STVP-932 showing DIN rail mounting clips
Figure 4: Side view illustrating the DIN rail mounting mechanism.

5.2 Wiring Diagram

Follow the wiring diagram carefully to connect the STVP-932 to your three-phase electrical system. The device has 'IN' terminals for incoming power (L1, L2, L3, N) and 'OUT' terminals for protected outgoing power (L1, L2, L3, N).

Wiring diagram for SINOTIMER STVP-932 showing connections to power switch and air circuit breaker
Figure 5: Wiring diagram for the STVP-932, showing connections to a power switch and an air circuit breaker. Ensure correct phase (L1, L2, L3) and neutral (N) connections for both input and output.

Connection Steps:

  1. Connect the incoming three-phase power supply (L1, L2, L3, N) to the 'IN' terminals of the STVP-932.
  2. Connect the 'OUT' terminals (L1, L2, L3, N) of the STVP-932 to the load or downstream circuit protection devices (e.g., air circuit breaker).
  3. Ensure all connections are tight and secure to prevent loose contacts and overheating.

6. Operating Instructions

6.1 Digital Display

The digital display shows real-time voltage readings for each phase (A, B, C). In normal operation, it cycles through these readings or displays the current status.

6.2 Setting Parameters

Use the 'SET' button to enter the parameter setting mode. The 'Up' and 'Down' arrow buttons are used to navigate through parameters and adjust their values. Press 'SET' again to confirm a setting and move to the next parameter, or to exit the setting mode.

Adjustable parameters include:

  • Over-voltage protection value (Uvo)
  • Over-voltage recovery value
  • Over-voltage protection action time
  • Under-voltage protection value (Uve)
  • Under-voltage recovery value
  • Under-voltage protection action time
  • Three-phase voltage unbalance protection value
  • Three-phase voltage unbalance protection action time
  • Delay time after power-on
  • Fault recovery delay time

6.3 Reset Mode Selection

The device supports different reset modes. Consult the English manual included in the package for detailed instructions on selecting the appropriate reset mode for your application.

6.4 Fault Inquiry and Factory Reset

The device allows for fault inquiry to review past protection events. A factory data reset option is also available to restore all parameters to their default settings.

7. Troubleshooting

This section provides guidance on common issues you might encounter with the STVP-932.

ProblemPossible CauseSolution
Device trips frequentlyVoltage fluctuations (over/under voltage), phase unbalance, incorrect settings.Check power supply stability. Adjust protection thresholds (Uvo, Uve) and action times. Verify load balance across phases.
No display/No powerNo input power, incorrect wiring, internal fault.Ensure main power is on. Check input wiring (L1, L2, L3, N). If wiring is correct and power is present, contact support.
Device does not resetContinuous fault condition, incorrect reset mode setting.Ensure the fault condition has cleared. Check the configured reset mode and recovery delay time.
Incorrect voltage readingsLoose connections, sensor issue.Verify all wiring connections are secure. If the issue persists, contact support.

8. Maintenance

  • Regularly inspect the device for any physical damage or signs of overheating.
  • Keep the device clean and free from dust and debris. Use a dry, soft cloth for cleaning.
  • Periodically check all wiring connections to ensure they remain tight and secure.
  • Do not attempt to open or repair the device yourself, as this may void any warranty and pose a safety risk.

9. User Tips

Based on common usage and feedback, here are some tips for optimizing your experience with the STVP-932:

  • Initial Setup: When first installing, set the protection values slightly wider than your expected normal operating range to avoid nuisance tripping, then fine-tune as needed.
  • Monitoring: Regularly check the digital display to understand the typical voltage behavior of your system, which can help in setting optimal protection parameters.
  • Recovery Delay: Utilize the fault recovery delay time setting to prevent rapid on/off cycling of equipment during intermittent power issues, protecting sensitive loads.

10. Warranty and Support

For warranty information, technical support, or service inquiries, please contact your original point of purchase or the SINOTIMER customer service department. Keep your purchase receipt and product model number handy for faster assistance.

Related Documents - STVP-932

PreviewSVP-916 Intelligent Over-Voltage Limit Current Protector Instruction Manual
Instruction manual for the SINOTIMER SVP-916 intelligent over-voltage, under-voltage, and over-current protector for single-phase AC 230V systems. Details features, parameters, and setting methods for electrical equipment protection.
PreviewSINOTIMER WiFi Smart Switch Instruction Manual
Comprehensive instruction manual for the SINOTIMER WiFi Smart Switch, detailing network setup via the Graffiti Smart APP, device unbinding and reset procedures, indicator light status, electricity consumption display, and configuration of overvoltage, undervoltage, and overcurrent protection settings.
PreviewSINOTIMER SVP719 User Manual: Voltage Protector, Energy Meter, and Power Consumption Monitor
Comprehensive user manual for the SINOTIMER SVP719, detailing its features as an adjustable over/under voltage protector, surge protector, over-current limit relay, and a Watt/kWh energy meter for monitoring power consumption.
PreviewSINOTIMER DDS6619 Series Guide Rail Metering Switch Instruction Manual
Instruction manual for SINOTIMER DDS6619 series guide rail type metering switches. Details technical specifications, wiring, app control via Smart Life/Tuya, operating instructions, and safety precautions for smart energy monitoring.
PreviewSINOTIMER TM-610 Digital Time Switch for DIN Rail - User Manual and Specifications
Detailed specifications, wiring diagrams, and operating instructions for the SINOTIMER TM-610 digital time switch, designed for DIN rail mounting.
PreviewSINOTIMER TM929: Guía del Temporizador Analógico Diario de 24 Horas
Explore el temporizador analógico diario SINOTIMER TM929 de 24 horas. Este manual proporciona información detallada sobre sus características, especificaciones técnicas y diagramas de cableado para una fácil instalación y operación.