XD3888BL Pipeline Wind Speed Sensor
“
Product Information
Specifications
- Brand: XUNCHIP
- Model: XD3888BL
- Wind Speed Range: Customizable
- Wind Speed Accuracy: High precision
- Induction Principle: Not specified
- Interface: RS485, RS232, CAN, 4-20mA, DC0-5V/10V, ZIGBEE, Lora,
WIFI, GPRS - Power: Not specified
- Operating Temperature: Not specified
- Working Humidity: Not specified
Product Usage Instructions
Installation
Thread the pipeline wind speed sensor following the installation
instructions provided in the manual.
Product Selection
The product comes in different models based on output
method:
- XD3888B – RS485
- XD3888M – 4-20mA
- XD3888V5 – DC0-5V
- XD3888V10 – DC0-10V
Product Size
Wire the product as shown in the figure in case of broken wires.
Reference the core color if the product has no leads.
Frequently Asked Questions (FAQ)
How do I read data from the device?
To read data using function code 0x03, you can follow the
example command structure provided in the manual.
How can I configure the device address?
To read or modify the device address, refer to the instructions
on querying or modifying the device address in the manual.
“`
XD3888BL Us er Ma nual
http://www.xunchip.com/
XD3888BL Threaded installation of pipeline wind speed sensor
User Manual
File Version: V24.11.14
XD3888BL using the standard ,easy access to PLCDCS and other instruments or systems for monitoring wind speed state quantities.The internal use of high -precision sensing core and related devices to ensure high reliability and excellent long-term stability,can be customized RS232,RS485,CAN,4-20mA,DC0~5V10V,ZIGBEE,Lora,WIFI,GPRS and other output methods.
Technical Parameters
ShanghaiXUNCHIP Industrial Co., Ltd XUNCHIP Brand Division Page1
XD3888BL Us er Ma nual
Technical parameter Brand Wind speed range Wind speed accuracy Induction principle Interface Power Running temperature Working humidity
http://www.xunchip.com/
Parameter value XUNCHIP 0~30m/s ±3% Thermal film induction RS485/4-20mA/DC0-5V/DC0-10V DC12~24V 1A -30~85 5%RH~90%RH
Product Selection
Product DesignRS485,4-20mA,DC0-5V,DC0-10VMultiple output methods, the products are divided
into the following models depending on the output method.
Product model
output method
XD3888B
RS485
XD3888M
4-20mA
XD3888V5
DC0-5V
XD3888V10
DC0-10V
Product Size
In the case of broken wires, wire the wires as shown in the figure. If the product itself has no leads, the core color is for reference.
How to use?
ShanghaiXUNCHIP Industrial Co., Ltd XUNCHIP Brand Division Page2
XD3888BL Us er Ma nual
http://www.xunchip.com/
Application solution
ShanghaiXUNCHIP Industrial Co., Ltd XUNCHIP Brand Division Page3
XD3888BL Us er Ma nual
http://www.xunchip.com/
ShanghaiXUNCHIP Industrial Co., Ltd XUNCHIP Brand Division Page4
XD3888BL Us er Ma nual
http://www.xunchip.com/
Product List
Communication Protocol
The product uses RS485 MODBUS-RTU standard protocol format, all operation or reply commands are hexadecimal data. The default device address is 1 when the device leaves the factory, and the module or NON-Recorder default baud rate is 9600,8,n,1 ,but data recorder default baud rate is 115200 .
1. Read data (function code 0x03)
Inquiry frame (hexadecimal), sending example: query 1 data of 1# device, the upper computer sends the command: 01 03 00 00 00 01 84 0A .
ShanghaiXUNCHIP Industrial Co., Ltd XUNCHIP Brand Division Page5
Address 01
XD3888BL Us er Ma nual
Function Code 03
Start Address 00 00
http://www.xunchip.com/
Data Length 00 01
Check Code 84 0A
For the correct query frame, the device will respond with data: 01 03 02 00 79 79 A6 , response format:
Address
Function Code
Length
Data 1
Check Code
01
03
02
00 79
79 A6
Data description: The data in the command is hexadecimal, take data 1 as an example, 00 79 is
converted to decimal value as 121, assuming the data magnification is 100, then the real value is
121/100=1.21, Others and so on.
2. Common data address table
Configuration
Register Address Register
Data Type
Value Range
Address
Description
40001
00 00
wind speed
Read Only
0~65535
40101
00 64
Model Code
Read/Write
0~65535
40102
00 65
total number of
read/write
1~20
measuring points
40103
00 66
device address
read/write
1~249
40104
00 67
baud rate
read/write
0~6
40105
00 68
communication
read/write
1~4
mode
40106
00 69
protocol type
read/write
1~10
3 Read and modify device address
(1) Read or query device address
If you don’t know the current device address and there is only one device on the bus, you can query
the device address through the commandFA 03 00 66 00 01 71 9E .
Device Address
Function Code
Start Address
Data Length
Check Code
FA
03
00 66
00 01
71 9E
FA means 250 is the general address, when you don’t know the address, you can use 250 to get the
real device address, 00 66 is the device address register.
For the correct query command, the device will respond, for example, the response data is: 01 03 02
00 01 79 84, and its format parsing is shown in the following table:
Device Address
Function Code
Start Address
Model Code
Check Code
01
03
02
00 01
79 84
In the response data, the first byte 01 represents the real address of the current device.
(2) Change device address
For example, if the current device address is 1 and we want to change it to 02, the command is: 01 06
00 66 00 02 E8 14 .
Device Address
Function Code
Register Address Target Address
Check Code
01
06
00 66
00 02
E8 14
After the change is successful, the device will return the information: 02 06 00 66 00 02 E8 27 , and its
format analysis is shown in the following table:
Device Address
Function Code
Register Address Target Address
Check Code
02
06
00 66
00 02
E8 27
ShanghaiXUNCHIP Industrial Co., Ltd XUNCHIP Brand Division Page6
XD3888BL Us er Ma nual
http://www.xunchip.com/
In the response data, after the modification is successful, the first byte is the new device address.
Generally, after the device address is changed, it will take effect immediately. At this time, the user needs
to change the query command of his software accordingly. .
4 Read and modify baud rate (1) Read baud rate
The default factory baud rate of the device is 9600. If you need to change it, you can change it
according to the following table and the corresponding co mmunication protocol. For example, to read the
baud rate ID of the current device, the command is: 01 03 00 67 00 01 35 D5 , the format is parsed as
follows.
Device Address
Function Code
Start Address
Data Length
Check Code
01
03
00 67
00 01
35 D5
Read the baud rate code of the current device. Baud rate code: 1 is 2400; 2 is 4800; 3 is 9600; 4 is
19200; 5 is 38400; 6 is 115200.
For the correct query command, the device will respond, for example, the response data is: 01 03 02
00 03 F8 45, and its format analysis is shown in the following table:
Device Address
Function Code
Data Length
Baud Rate Code Check Code
01
03
02
00 03
F8 45
According to the baud rate code, 03 is 9600, that is, the baud rate of the current device is 9600.
(2) Change the baud rate
For example, change the baud rate from 9600 to 38400, that is, change the code from 3 to 5, the
command is: 01 06 00 67 00 05 F8 16 .
Device Address
Function Code
Register Address Target Baud Rate Check Code
01
06
00 67
00 05
F8 16
Change the baud rate from 9600 to 38400, that is, change the code from 3 to 5. The new baud rate will
take effect immediately, and the device will lose response at this time, and the baud rate of the device
needs to be checked accordingly Modified.
5 Read and modify correction value (1) Read correction value
When there is an error between the data and the reference standard, we can reduce the display error
by adjusting the correction value. The correction difference can be modified in a rang e of plus or minus
1000, that is, the value range is 0-1000 or 64535 -65535. For example, when the displayed value is too
small by 100, we can correct it by adding 100. The command is: 01 03 00 6B 00 01 F5 D6 . In the
command, 100 is hexadecimal 0x64 ;If you need to reduce it, you can set a negative value, such as -100,
the corresponding hexadecimal value is FF 9C, the calculation method is 100 -65535=65435, and then
converted to hexadecimal, it is 0x FF 9C. Device The correction value starts from 00 6B. We take the first
parameter as an example to illustrate. When there are multiple parameters, the correction value is read
and modified in the same way.
Device Address
Function Code
Start Address
Data Length
Check Code
01
03
00 6B
00 01
F5 D6
For the correct query command, the device will respond, for example, the response data is: 01 03 02
00 64 B9 AF, and its format parsing is shown in the following table:
Device Address
Function Code
Data Length
Correction Value Check Code
01
03
02
00 64
B9 AF
In the response data, the first byte 01 represents the real address of the current device, and 00 6B is
ShanghaiXUNCHIP Industrial Co., Ltd XUNCHIP Brand Division Page7
XD3888BL Us er Ma nual
http://www.xunchip.com/
the first state correction value register. If the device has multiple parameters, other parameters operate in
the same way as this The same, generally temperature and humidity have this parameter, and lighting
generally does not have this parameter.
(2) Change the correction value
For example, if the current state is too small, we want to add 1 to its real value, and add 100 to the
current value. The correction operation command is: 01 06 00 6B 00 64 F9 FD .
Device Address
Function Code
Register Address Target Address
Check Code
01
06
00 6B
00 64
F9 FD
After the operation is successful, the device will return the information: 01 06 00 6B 00 64 F9 FD , after
the successful change, the parameters will take effect immediately.
For example, the range is 0~30m/s, the analog output is 4~20mA curre nt signal, wind speed and
current The calculation relationship is as shown in the formula: C = (A2 -A1) * (X-B1) / (B2-B1) + A1, where
A2 is wind speed range upper limit, A1 is the lower limit of the range, B2 is current output range upper limit,
B1 is the lower limit, X is the currently read wind speed value, and C is the calculated current value. The list
of commonly used values is as follows:
current(mA)
wind speedValue (m/s)
Calculation Process
4
0.0
(30-0)*(4-4)÷(20-4)+0
5
1.9
(30-0)*(5-4)÷(20-4)+0
6
3.8
(30-0)*(6-4)÷(20-4)+0
7
5.6
(30-0)*(7-4)÷(20-4)+0
8
7.5
(30-0)*(8-4)÷(20-4)+0
9
9.4
(30-0)*(9-4)÷(20-4)+0
10
11.3
(30-0)*(10-4)÷(20-4)+0
11
13.1
(30-0)*(11-4)÷(20-4)+0
12
15.0
(30-0)*(12-4)÷(20-4)+0
13
16.9
(30-0)*(13-4)÷(20-4)+0
14
18.8
(30-0)*(14-4)÷(20-4)+0
15
20.6
(30-0)*(15-4)÷(20-4)+0
16
22.5
(30-0)*(16-4)÷(20-4)+0
17
24.4
(30-0)*(17-4)÷(20-4)+0
18
26.3
(30-0)*(18-4)÷(20-4)+0
19
28.1
(30-0)*(19-4)÷(20-4)+0
20
30.0
(30-0)*(20-4)÷(20-4)+0
As shown in the above formula, when measuring 8mA, current current is 11.5m/s
For example, the range is 0~30m/s, the analog output is 0~5V DC0 -5Vvoltage signal, wind speed and
DC0-5Vvoltage The calculation relationship is as shown in the formula: C = (A2 -A1) * (X-B1) / (B2-B1) + A1,
where A2 is wind speed range upper limit, A1 is the lower limit of the range, B2 is DC0-5Vvoltage output
range upper limit, B1 is the lower limit, X is the currently read wind speed value, and C is the calculated
DC0-5Vvoltage value. The list of commonly used values is as follows:
DC0-5Vvoltage(V)
wind speedValue (m/s)
Calculation Process
0
0.0
(30-0)*(0-0)÷(5-0)+0
ShanghaiXUNCHIP Industrial Co., Ltd XUNCHIP Brand Division Page8
XD3888BL Us er Ma nual
http://www.xunchip.com/
1
6.0
(30-0)*(1-0)÷(5-0)+0
2
12.0
(30-0)*(2-0)÷(5-0)+0
3
18.0
(30-0)*(3-0)÷(5-0)+0
4
24.0
(30-0)*(4-0)÷(5-0)+0
5
30.0
(30-0)*(5-0)÷(5-0)+0
As shown in the above formula, when measuring 2.5V, current DC0-5Vvoltage is 15m/s
For example, the range is 0~30m/s, the analog output is 0~10V DC0 -10Vvoltage signal, wind speed
and DC0-10Vvoltage The calculation relationship is as shown in the formula: C = (A2 -A1) * (X-B1) / (B2-B1)
+ A1, where A2 is wind speed range upper limit, A1 is the lower limit of the range, B2 is DC0-10Vvoltage
output range upper limit, B1 is the lower limit, X is the currently read wind speed value, and C is the
calculated DC0-10Vvoltage value. The list of commonly used values is as follows:
DC0-10Vvoltage(V)
wind speedValue (m/s)
Calculation Process
0
0.0
(30-0)*(0-0)÷(10-0)+0
1
3.0
(30-0)*(1-0)÷(10-0)+0
2
6.0
(30-0)*(2-0)÷(10-0)+0
3
9.0
(30-0)*(3-0)÷(10-0)+0
4
12.0
(30-0)*(4-0)÷(10-0)+0
5
15.0
(30-0)*(5-0)÷(10-0)+0
6
18.0
(30-0)*(6-0)÷(10-0)+0
7
21.0
(30-0)*(7-0)÷(10-0)+0
8
24.0
(30-0)*(8-0)÷(10-0)+0
9
27.0
(30-0)*(9-0)÷(10-0)+0
10
30.0
(30-0)*(10-0)÷(10-0)+0
As shown in the above formula, when measuring 5V, current DC0 -10Vvoltage is 15m/s
Disclaimer
This document provides all information about the product, does not grant any license to intellectual
property, does not express or imply, and prohibits any other means of granting any intellectual property
rights, such as the statement of sales terms and conditions of this product, other issues. No liabi lity is
assumed. Furthermore, our company makes no warranties, express or implied, regarding the sale and use
of this product, including the suitability for the specific use of the product, the marketability or the
infringement liability for any patent, copyright or other intellectual property rights, etc. Product
specifications and product descriptions may be modified at any time without notice.
Contact Us
Brand: XUNCHIP
Address: Room 208, Building 8, No. 215, Nandong Road, Ba oshan District, Shanghai, Xinxin Brand
Business Department
Chinese site: http://www.xunchip.com
International site: http://www.xunchip.com
SKYPE: soobuu
E-mail: sale@sonbest.com
Tel: 86-021-51083595 / 66862055 / 66862075 / 66861077
ShanghaiXUNCHIP Industrial Co., Ltd XUNCHIP Brand Division Page9