XUNCHIP XD3888BL Pipeline Wind Speed Sensor User Manual

XD3888BL Pipeline Wind Speed Sensor

Product Information

Specifications

  • Brand: XUNCHIP
  • Model: XD3888BL
  • Wind Speed Range: Customizable
  • Wind Speed Accuracy: High precision
  • Induction Principle: Not specified
  • Interface: RS485, RS232, CAN, 4-20mA, DC0-5V/10V, ZIGBEE, Lora,
    WIFI, GPRS
  • Power: Not specified
  • Operating Temperature: Not specified
  • Working Humidity: Not specified

Product Usage Instructions

Installation

Thread the pipeline wind speed sensor following the installation
instructions provided in the manual.

Product Selection

The product comes in different models based on output
method:

  • XD3888B – RS485
  • XD3888M – 4-20mA
  • XD3888V5 – DC0-5V
  • XD3888V10 – DC0-10V

Product Size

Wire the product as shown in the figure in case of broken wires.
Reference the core color if the product has no leads.

Frequently Asked Questions (FAQ)

How do I read data from the device?

To read data using function code 0x03, you can follow the
example command structure provided in the manual.

How can I configure the device address?

To read or modify the device address, refer to the instructions
on querying or modifying the device address in the manual.

“`

XD3888BL Us er Ma nual

http://www.xunchip.com/

XD3888BL Threaded installation of pipeline wind speed sensor
User Manual
File Version: V24.11.14

XD3888BL using the standard ,easy access to PLCDCS and other instruments or systems for monitoring wind speed state quantities.The internal use of high -precision sensing core and related devices to ensure high reliability and excellent long-term stability,can be customized RS232,RS485,CAN,4-20mA,DC0~5V10V,ZIGBEE,Lora,WIFI,GPRS and other output methods.
Technical Parameters
ShanghaiXUNCHIP Industrial Co., Ltd XUNCHIP Brand Division Page1

XD3888BL Us er Ma nual
Technical parameter Brand Wind speed range Wind speed accuracy Induction principle Interface Power Running temperature Working humidity

http://www.xunchip.com/
Parameter value XUNCHIP 0~30m/s ±3% Thermal film induction RS485/4-20mA/DC0-5V/DC0-10V DC12~24V 1A -30~85 5%RH~90%RH

Product Selection

Product DesignRS485,4-20mA,DC0-5V,DC0-10VMultiple output methods, the products are divided

into the following models depending on the output method.

Product model

output method

XD3888B

RS485

XD3888M

4-20mA

XD3888V5

DC0-5V

XD3888V10

DC0-10V

Product Size

In the case of broken wires, wire the wires as shown in the figure. If the product itself has no leads, the core color is for reference.
How to use?
ShanghaiXUNCHIP Industrial Co., Ltd XUNCHIP Brand Division Page2

XD3888BL Us er Ma nual

http://www.xunchip.com/

Application solution
ShanghaiXUNCHIP Industrial Co., Ltd XUNCHIP Brand Division Page3

XD3888BL Us er Ma nual

http://www.xunchip.com/

ShanghaiXUNCHIP Industrial Co., Ltd XUNCHIP Brand Division Page4

XD3888BL Us er Ma nual

http://www.xunchip.com/

Product List
Communication Protocol
The product uses RS485 MODBUS-RTU standard protocol format, all operation or reply commands are hexadecimal data. The default device address is 1 when the device leaves the factory, and the module or NON-Recorder default baud rate is 9600,8,n,1 ,but data recorder default baud rate is 115200 .
1. Read data (function code 0x03)
Inquiry frame (hexadecimal), sending example: query 1 data of 1# device, the upper computer sends the command: 01 03 00 00 00 01 84 0A .
ShanghaiXUNCHIP Industrial Co., Ltd XUNCHIP Brand Division Page5

Address 01

XD3888BL Us er Ma nual

Function Code 03

Start Address 00 00

http://www.xunchip.com/

Data Length 00 01

Check Code 84 0A

For the correct query frame, the device will respond with data: 01 03 02 00 79 79 A6 , response format:

Address

Function Code

Length

Data 1

Check Code

01

03

02

00 79

79 A6

Data description: The data in the command is hexadecimal, take data 1 as an example, 00 79 is

converted to decimal value as 121, assuming the data magnification is 100, then the real value is

121/100=1.21, Others and so on.

2. Common data address table

Configuration

Register Address Register

Data Type

Value Range

Address

Description

40001

00 00

wind speed

Read Only

0~65535

40101

00 64

Model Code

Read/Write

0~65535

40102

00 65

total number of

read/write

1~20

measuring points

40103

00 66

device address

read/write

1~249

40104

00 67

baud rate

read/write

0~6

40105

00 68

communication

read/write

1~4

mode

40106

00 69

protocol type

read/write

1~10

3 Read and modify device address

(1) Read or query device address

If you don’t know the current device address and there is only one device on the bus, you can query

the device address through the commandFA 03 00 66 00 01 71 9E .

Device Address

Function Code

Start Address

Data Length

Check Code

FA

03

00 66

00 01

71 9E

FA means 250 is the general address, when you don’t know the address, you can use 250 to get the

real device address, 00 66 is the device address register.

For the correct query command, the device will respond, for example, the response data is: 01 03 02

00 01 79 84, and its format parsing is shown in the following table:

Device Address

Function Code

Start Address

Model Code

Check Code

01

03

02

00 01

79 84

In the response data, the first byte 01 represents the real address of the current device.

(2) Change device address

For example, if the current device address is 1 and we want to change it to 02, the command is: 01 06

00 66 00 02 E8 14 .

Device Address

Function Code

Register Address Target Address

Check Code

01

06

00 66

00 02

E8 14

After the change is successful, the device will return the information: 02 06 00 66 00 02 E8 27 , and its

format analysis is shown in the following table:

Device Address

Function Code

Register Address Target Address

Check Code

02

06

00 66

00 02

E8 27

ShanghaiXUNCHIP Industrial Co., Ltd XUNCHIP Brand Division Page6

XD3888BL Us er Ma nual

http://www.xunchip.com/

In the response data, after the modification is successful, the first byte is the new device address.

Generally, after the device address is changed, it will take effect immediately. At this time, the user needs

to change the query command of his software accordingly. .
4 Read and modify baud rate (1) Read baud rate

The default factory baud rate of the device is 9600. If you need to change it, you can change it

according to the following table and the corresponding co mmunication protocol. For example, to read the

baud rate ID of the current device, the command is: 01 03 00 67 00 01 35 D5 , the format is parsed as

follows.

Device Address

Function Code

Start Address

Data Length

Check Code

01

03

00 67

00 01

35 D5

Read the baud rate code of the current device. Baud rate code: 1 is 2400; 2 is 4800; 3 is 9600; 4 is

19200; 5 is 38400; 6 is 115200.

For the correct query command, the device will respond, for example, the response data is: 01 03 02

00 03 F8 45, and its format analysis is shown in the following table:

Device Address

Function Code

Data Length

Baud Rate Code Check Code

01

03

02

00 03

F8 45

According to the baud rate code, 03 is 9600, that is, the baud rate of the current device is 9600.
(2) Change the baud rate

For example, change the baud rate from 9600 to 38400, that is, change the code from 3 to 5, the

command is: 01 06 00 67 00 05 F8 16 .

Device Address

Function Code

Register Address Target Baud Rate Check Code

01

06

00 67

00 05

F8 16

Change the baud rate from 9600 to 38400, that is, change the code from 3 to 5. The new baud rate will

take effect immediately, and the device will lose response at this time, and the baud rate of the device

needs to be checked accordingly Modified.

5 Read and modify correction value (1) Read correction value
When there is an error between the data and the reference standard, we can reduce the display error

by adjusting the correction value. The correction difference can be modified in a rang e of plus or minus

1000, that is, the value range is 0-1000 or 64535 -65535. For example, when the displayed value is too

small by 100, we can correct it by adding 100. The command is: 01 03 00 6B 00 01 F5 D6 . In the

command, 100 is hexadecimal 0x64 ;If you need to reduce it, you can set a negative value, such as -100,

the corresponding hexadecimal value is FF 9C, the calculation method is 100 -65535=65435, and then

converted to hexadecimal, it is 0x FF 9C. Device The correction value starts from 00 6B. We take the first

parameter as an example to illustrate. When there are multiple parameters, the correction value is read

and modified in the same way.

Device Address

Function Code

Start Address

Data Length

Check Code

01

03

00 6B

00 01

F5 D6

For the correct query command, the device will respond, for example, the response data is: 01 03 02

00 64 B9 AF, and its format parsing is shown in the following table:

Device Address

Function Code

Data Length

Correction Value Check Code

01

03

02

00 64

B9 AF

In the response data, the first byte 01 represents the real address of the current device, and 00 6B is
ShanghaiXUNCHIP Industrial Co., Ltd XUNCHIP Brand Division Page7

XD3888BL Us er Ma nual

http://www.xunchip.com/

the first state correction value register. If the device has multiple parameters, other parameters operate in

the same way as this The same, generally temperature and humidity have this parameter, and lighting

generally does not have this parameter.
(2) Change the correction value

For example, if the current state is too small, we want to add 1 to its real value, and add 100 to the

current value. The correction operation command is: 01 06 00 6B 00 64 F9 FD .

Device Address

Function Code

Register Address Target Address

Check Code

01

06

00 6B

00 64

F9 FD

After the operation is successful, the device will return the information: 01 06 00 6B 00 64 F9 FD , after

the successful change, the parameters will take effect immediately.

For example, the range is 0~30m/s, the analog output is 4~20mA curre nt signal, wind speed and

current The calculation relationship is as shown in the formula: C = (A2 -A1) * (X-B1) / (B2-B1) + A1, where

A2 is wind speed range upper limit, A1 is the lower limit of the range, B2 is current output range upper limit,

B1 is the lower limit, X is the currently read wind speed value, and C is the calculated current value. The list

of commonly used values is as follows:

current(mA)

wind speedValue (m/s)

Calculation Process

4

0.0

(30-0)*(4-4)÷(20-4)+0

5

1.9

(30-0)*(5-4)÷(20-4)+0

6

3.8

(30-0)*(6-4)÷(20-4)+0

7

5.6

(30-0)*(7-4)÷(20-4)+0

8

7.5

(30-0)*(8-4)÷(20-4)+0

9

9.4

(30-0)*(9-4)÷(20-4)+0

10

11.3

(30-0)*(10-4)÷(20-4)+0

11

13.1

(30-0)*(11-4)÷(20-4)+0

12

15.0

(30-0)*(12-4)÷(20-4)+0

13

16.9

(30-0)*(13-4)÷(20-4)+0

14

18.8

(30-0)*(14-4)÷(20-4)+0

15

20.6

(30-0)*(15-4)÷(20-4)+0

16

22.5

(30-0)*(16-4)÷(20-4)+0

17

24.4

(30-0)*(17-4)÷(20-4)+0

18

26.3

(30-0)*(18-4)÷(20-4)+0

19

28.1

(30-0)*(19-4)÷(20-4)+0

20

30.0

(30-0)*(20-4)÷(20-4)+0

As shown in the above formula, when measuring 8mA, current current is 11.5m/s

For example, the range is 0~30m/s, the analog output is 0~5V DC0 -5Vvoltage signal, wind speed and

DC0-5Vvoltage The calculation relationship is as shown in the formula: C = (A2 -A1) * (X-B1) / (B2-B1) + A1,

where A2 is wind speed range upper limit, A1 is the lower limit of the range, B2 is DC0-5Vvoltage output

range upper limit, B1 is the lower limit, X is the currently read wind speed value, and C is the calculated

DC0-5Vvoltage value. The list of commonly used values is as follows:

DC0-5Vvoltage(V)

wind speedValue (m/s)

Calculation Process

0

0.0

(30-0)*(0-0)÷(5-0)+0

ShanghaiXUNCHIP Industrial Co., Ltd XUNCHIP Brand Division Page8

XD3888BL Us er Ma nual

http://www.xunchip.com/

1

6.0

(30-0)*(1-0)÷(5-0)+0

2

12.0

(30-0)*(2-0)÷(5-0)+0

3

18.0

(30-0)*(3-0)÷(5-0)+0

4

24.0

(30-0)*(4-0)÷(5-0)+0

5

30.0

(30-0)*(5-0)÷(5-0)+0

As shown in the above formula, when measuring 2.5V, current DC0-5Vvoltage is 15m/s

For example, the range is 0~30m/s, the analog output is 0~10V DC0 -10Vvoltage signal, wind speed

and DC0-10Vvoltage The calculation relationship is as shown in the formula: C = (A2 -A1) * (X-B1) / (B2-B1)

+ A1, where A2 is wind speed range upper limit, A1 is the lower limit of the range, B2 is DC0-10Vvoltage

output range upper limit, B1 is the lower limit, X is the currently read wind speed value, and C is the

calculated DC0-10Vvoltage value. The list of commonly used values is as follows:

DC0-10Vvoltage(V)

wind speedValue (m/s)

Calculation Process

0

0.0

(30-0)*(0-0)÷(10-0)+0

1

3.0

(30-0)*(1-0)÷(10-0)+0

2

6.0

(30-0)*(2-0)÷(10-0)+0

3

9.0

(30-0)*(3-0)÷(10-0)+0

4

12.0

(30-0)*(4-0)÷(10-0)+0

5

15.0

(30-0)*(5-0)÷(10-0)+0

6

18.0

(30-0)*(6-0)÷(10-0)+0

7

21.0

(30-0)*(7-0)÷(10-0)+0

8

24.0

(30-0)*(8-0)÷(10-0)+0

9

27.0

(30-0)*(9-0)÷(10-0)+0

10

30.0

(30-0)*(10-0)÷(10-0)+0

As shown in the above formula, when measuring 5V, current DC0 -10Vvoltage is 15m/s

Disclaimer

This document provides all information about the product, does not grant any license to intellectual

property, does not express or imply, and prohibits any other means of granting any intellectual property

rights, such as the statement of sales terms and conditions of this product, other issues. No liabi lity is

assumed. Furthermore, our company makes no warranties, express or implied, regarding the sale and use

of this product, including the suitability for the specific use of the product, the marketability or the

infringement liability for any patent, copyright or other intellectual property rights, etc. Product

specifications and product descriptions may be modified at any time without notice.

Contact Us

Brand: XUNCHIP

Address: Room 208, Building 8, No. 215, Nandong Road, Ba oshan District, Shanghai, Xinxin Brand

Business Department

Chinese site: http://www.xunchip.com

International site: http://www.xunchip.com

SKYPE: soobuu

E-mail: sale@sonbest.com

Tel: 86-021-51083595 / 66862055 / 66862075 / 66861077

ShanghaiXUNCHIP Industrial Co., Ltd XUNCHIP Brand Division Page9