TERACOM TSM400-4-CP Modbus CO2 and Pressure Sensor User Manual
TERACOM TSM400-4-CP Modbus CO2 and Pressure Sensor

Short description

TSM400-4-CP is a multi-parameter sensor that supports MODBUS RTU protocol over the RS-485 interface. The sensor measures barometric pressure and CO2 concentration.  MODBUS device integrates an advanced non-dispersive infrared sensing element (NDIR) for CO2 measurements. The measurement principle is based on the absorption of infra-red (IR) light with specific wavelengths by CO2 molecules. The CO2sensing element is realized with built-in humidity and temperature for better accuracy. Self-calibration is available for carbon dioxide measurements. It is done if the sensor is left in fresh (around 400 ppm CO2 concentration) air.

The basic sensing element for barometric pressure is factory calibrated and it does not require any lifetime recalibration.

MODBUS CO2 and pressure sensor TSH400-4-CP is housed in a slim plastic enclosure. The bottom part of the enclosure is suitable for installation on standard flush mounted/cavity wall boxes ø68mm, with installation openings on 61 mm.

Features

  • LED indicator for status of communication;
  • Long-term stability based on digital signal processing;
  • Self-calibration on fresh air for CO2 measurements;
  • RS-485 interface carrying up to 32 nodes;
  • Changeable bitrate and other communication parameters;
  • Firmware update via the interface.

Applications

  • Indoor air quality (IAQ);
  • CO2 storage facilities leakage control;
  • Smart ventilation systems;
  • Restaurants and breweries CO2 level monitoring.

Specifications

  • Physical characteristics
    Dimensions: 81 x 81 x 30 mm
    Weight: 66 g
  • Environmental limits
    Operating temperature range: -20 to 60°C
    Operating relative humidity range: 5 to 95% (non-condensing)
    Storage temperature range: -20 to 60°C
    Storage relative humidity range: 5 to 95% (non-condensing)
    Ingress protection: IP20
  • Power requirements
    Operating voltage range (including -15/+20% according to IEC 62368-1): 4.5 to 26 VDC
    Current consumption: 25 mA@5VDC (Peak: 150 mA@5VDC)
  • CO2 measurements
    Range: 400 to 5000 ppm
    Accuracy: ± (40 ppm + 5 %)
    Resolution: 1 ppm
  • Pressure measurements
    Range: 10 to 1200 hPa
    Accuracy (min): ±1.5 (25°C, 750 hPa)
    Accuracy (max): ±2.5 (-20°C to + 85°C, 300 to 1100 hPa)
    Resolution: 1 hPa
  • Warranty
    Warranty period: 3 years

Pinout

Pinout Pin Description UTP wires color
1-W Not used
+5÷30V Positive power supply Brown/White Tracer
GND Ground (negative) supply Brown
A+ Line A+ of RS-485 Blue/White Tracer
B- Line B- of RS-485 Blue
TERM For termination, connect to B-  

Installation

Two-Wire MODBUS definition according to modbus.org:
“A MODBUS solution over a serial line should implement a “Two-Wire” electrical interface in accordance with EIA/TIA-485 standard. On such a “Two-Wire” topology, at any time one driver only has the right to transmit. In fact, a third conductor must also interconnect all the devices of the bus – the common.”
Installation

Attention:
For proper operation of the interface, terminators (120 ohms resistors) must be installed at both ends of the bus. The device has a built-in 120-ohm resistor and to terminate the line, “B-“ and “TERM” must be shortened.
A daisy-chained (linear) topology for multiple sensors should be used. UTP/FTP cables are mandatory for interconnection.
Installation

Installation tips

The location and the mounting position of sensors have a direct effect on the accuracy of monitoring humidity and temperature. The tips below will ensure good measuring results:

  • Sensor shall be installed about 1.2-1.4 m above the floor;
  • To avoid solar radiation, the sensor should not be installed next to windows or directly in the sunlight;
  • Sensors shall be installed in a place with sufficient air circulation.

TSM400-4-CP sensor is intended for installation on a cavity wall box with 68mm diameter and 61 mm screw spacing.
Installation tips

Status indicator

The status of the device is shown by a single LED, located inside the box:

  • If the LED blinks for a period of 1 second, the sensor works properly;
  • If the LED blinks for a period of 3 seconds, there isn‘t communication with the controller;
  • If the LED doesn‘t blink, there isn‘t a power supply.

Factory default settings

Disconnect the sensor from the bus (switch off the power supply).
Press and hold the “config” button. Don’t release the button, connecting the sensor to the bus (switch on the power supply).
The “status” LED will be ON for 3 seconds and after this will flash for 7 seconds. After the 10-th second the LED will be ON.

Release the button. The sensor will restart with factory default settings.

Firmware update

The firmware of the sensor can be updated with a Teracom controller which supports MODBUS RTU or MBRTU-Config software. For more details, ask your dealer.

Modbus address table

Register name R/W FC PDU Address (Decimal) Logical Address (Decimal) Offset (Decimal) Data size Default Valid values
RS-485 address R/W 03/06 10 40011 40001 16-bit uns. integer 1 1-247
Baud rate* R/W 03/06 11 40012 40001 16-bit uns. integer 19200 2400, 4800, 9600, 19200, 38400, 57600
Parity, data, stop bits * R/W 03/06 12 40013 40001 16-bit uns. integer 1 1=E81, 2=O81, 3=N81
Data order R/W 03/06 13 40014 40001 16-bit uns. integer 1 1=MSWF (MSW, LSW)
2=LSWF (LSW, MSW)
Sub-family number R 3 14 40015 40001 16-bit uns. integer 1 0xC9
FW version R 3 15 40016 40001 16-bit uns. integer
Vendor URL R 3 16 40017 40001 64 bytes UTF-8 teracomsystems.com
Float test value (MSWF) R 3 82 40083 40001 32-bit float   -9.9(0xC11E6666)
Float test value (LSWF) R 3 84 40085 40001 32-bit float   -9.9(0xC11E6666)
Signed integer test value R 3 86 40087 40001 16-bit sig. integer   -999(0xFC19)
Signed integer test value (MSWF) R 3 87 40088 40001 32-bit sig. integer   -99999(0xFFFE7961)
Signed integer test value (LSWF) R 3 89 40090 40001 32-bit sig. integer -99999(0xFFFE7961)
Unsigned integer test value R 3 91 40092 40001 16-bit uns. integer   999(0x03E7)
Unsigned integer test value (MSWF) R 3 92 40093 40001 32-bit uns. integer   99999(0x0001869F)
Unsigned integer test value (LSWF) R 3 94 40095 40001 32-bit uns. integer   99999(0x0001869F)
             
CO2, ppm R 3 106 40107 40001 32-bit float
Pressure, hPa R 3 108 40109 40001 32-bit float
             
CO2, ppm R 3 206 40207 40001 32-bit float
Pressure, mmHg R 3 208 40209 40001 32-bit float
             
CO2, ppm R 3 603 40604 40001 16-bit uns. integer
Pressure, hPa R 3 604 40605 40001 16-bit uns. integer
 
CO2, ppm R 3 703 40704 40001 16-bit uns. integer
Pressure High, mmHg x 100 R 3 704 40705 40001 16-bit uns. integer
Pressure Low, mmHg x 100 R 3 705 40706 40001 16-bit uns. integer  

MSWF – Most significant word first – (bits 31 … 16), (bits 15 … 0); LSWF – Least significant word first – (bits 15 … 0), (bits 31 … 16);
PDU address – Actual address bytes used in a Modbus Protocol Data unit
A “NaN” value is returned for unavailable floating-point values (e.g., in case of measurement error)

  • The settings will take effect after restarting the device by power-off, power on.

Recycling

Recycle icon Recycle all applicable material.
Disposal icon Do not dispose of with regular household refuse.

Logo

Documents / Resources

TERACOM TSM400-4-CP Modbus CO2 and Pressure Sensor [pdf] User Manual
TSM400-4-CP, Modbus CO2 and Pressure Sensor, TSM400-4-CP Modbus CO2 and Pressure Sensor