TERACOM TSM400-4-CP MODBUS CO₂ and Pressure Sensor

Version 1.1 / August 2022

Website: www.teracomsystems.com

1. Short Description

The TSM400-4-CP is a multi-parameter sensor supporting the MODBUS RTU protocol over an RS-485 interface. It measures barometric pressure and CO₂ concentration using an advanced non-dispersive infrared (NDIR) sensing element. The CO₂ measurement principle relies on the absorption of infrared light by CO₂ molecules and is temperature-compensated for accuracy. The sensor features self-calibration for CO₂ measurements when exposed to fresh air (approximately 400 ppm CO₂). The barometric pressure sensing element is factory calibrated and requires no lifetime recalibration. The sensor is housed in a slim plastic enclosure designed for installation on standard flush-mounted/cavity wall boxes (Ø68mm) with 61mm installation openings.

2. Features

3. Applications

4. Specifications

Physical Characteristics

Environmental Limits

Power Requirements

CO₂ Measurements

Pressure Measurements

Warranty

5. Pinout

Diagram showing a connector with labels TERM, 1-W, +5+30V, GND, A+, B-.

PinDescriptionUTP wires color
TERMFor termination, connect to B-Blue
1-WNot used
+5+30VPositive power supplyBrown/White Tracer
GNDGround (negative) supplyBrown
A+Line A+ of RS-485Blue/White Tracer
B-Line B- of RS-485Blue

6. Installation

The Two-Wire MODBUS definition, according to modbus.org, states that a MODBUS solution over a serial line should implement a "Two-Wire" electrical interface compliant with the EIA/TIA-485 standard. In this topology, only one driver has the right to transmit at any given time. A third conductor is required to interconnect all devices on the bus, serving as the common ground.

Diagram illustrating an RS-485 bus topology with terminators, master/slave devices, +5V, A+, B-, and GND connections.

Attention: For proper interface operation, terminators (120 ohm resistors) must be installed at both ends of the bus. The TSM400-4-CP device includes a built-in 120-ohm resistor; to terminate the line, the "B-" and "TERM" pins must be shortened. A daisy-chained (linear) topology is recommended for multiple sensors. UTP/FTP cables are mandatory for interconnection.

Images of TERACOM devices: TCW260, TSM400-4-CP, and TSH300 connected via RS-485.

7. Installation Tips

The location and mounting position significantly impact measurement accuracy. Follow these tips for optimal results:

Diagram showing dimensions for mounting the TSM400-4-CP sensor on a wall box. It indicates a 68mm diameter box and 61mm screw spacing, with specific measurements for mounting holes (e.g., 61.6 mm, 11.5 mm, 13.8 mm, 7 mm, 18 mm, R2.75, R1.75).

8. Status Indicator

The device status is indicated by a single LED located inside the enclosure:

9. Factory Default Settings

To restore factory default settings:

  1. Disconnect the sensor from the bus (switch off the power supply).
  2. Press and hold the "config" button.
  3. While holding the button, reconnect the sensor to the bus (switch on the power supply).
  4. The "status" LED will be ON for 3 seconds, then flash for 7 seconds, and finally remain ON after the 10th second.
  5. Release the "config" button. The sensor will restart with factory default settings.

10. Firmware Update

Firmware updates for the sensor can be performed using a TERACOM controller that supports MODBUS RTU or with the MBRTU-Config software. For detailed instructions, consult your dealer.

11. Modbus Address Table

This table lists the Modbus registers for the TSM400-4-CP sensor.

Register NameR/WFCPDU Address (Decimal)Logical Address (Decimal)Offset (Decimal)Data SizeDefaultValid Values
RS-485 addressR/W03/0610400114000116-bit uns. integer11-247
Baud rate*R/W03/0611400124000116-bit uns. integer192002400, 4800, 9600, 19200, 38400, 57600
Parity, data, stop bits *R/W03/0612400134000116-bit uns. integer11=E81, 2=O81, 3=N81
Data orderR/W03/0613400144000116-bit uns. integer11=MSWF (MSW, LSW) 2=LSWF (LSW, MSW)
Sub-family numberR314400154000116-bit uns. integer10xC9
FW versionR315400164000116-bit uns. integer
Vendor URLR316400174000164 bytes UTF-8teracomsystems.com
Float test value (MSWF)R382400834000132-bit float-9.9(0xC11E6666)
Float test value (LSWF)R384400854000132-bit float-9.9(0xC11E6666)
Signed integer test valueR386400874000116-bit sig. integer-999(0xFC19)
Signed integer test value (MSWF)R387400884000132-bit sig. integer-99999(0xFFFE7961)
Signed integer test value (LSWF)R389400904000132-bit sig. integer-99999(0xFFFE7961)
Unsigned integer test valueR391400924000116-bit uns. integer999(0x03E7)
Unsigned integer test value (MSWF)R392400934000132-bit uns. integer99999(0x0001869F)
Unsigned integer test value (LSWF)R394400954000132-bit uns. integer99999(0x0001869F)
CO₂, ppmR3106401074000132-bit float
Pressure, hPaR3108401094000132-bit float
CO₂, ppmR3206402074000132-bit float
Pressure, mmHgR3208402094000132-bit float
CO₂, ppmR3603406044000116-bit uns. integer
Pressure, hPaR3604406054000116-bit uns. integer
CO₂, ppmR3703407044000116-bit uns. integer
Pressure High, mmHg x 100R3704407054000116-bit uns. integer
Pressure Low, mmHg x 100R3705407064000116-bit uns. integer

MSWF - Most significant word first - (bits 31 ... 16), (bits 15 ... 0); LSWF - Least significant word first - (bits 15 ... 0), (bits 31 ... 16); PDU address - Actual address bytes used in a Modbus Protocol Data unit. A "NaN" value is returned for unavailable floating-point values (e.g., in case of measurement error). * The settings will take effect after restarting the device by power-off, power-on.

12. Recycling

♻️ Recycle all applicable material.

Do not dispose of with regular household refuse.

Models: TSM400-4-CP Modbus Co2 and Pressure Sensor, TSM400-4-CP Modbus, TSM400-4-CP, Modbus, Co2 Sensor, Pressure Sensor, Sensor

File Info : application/pdf, 5 Pages, 637.33KB

PDF preview unavailable. Download the PDF instead.

tsm400-4-cp-modbus-co2-and-pressure-sensor-user-manual-r1.1

References

Microsoft Word 2019

Related Documents

Preview TSM400-1-CP: 1-Wire Carbon Dioxide and Pressure Sensor User Manual
User manual for the TERACOM TSM400-1-CP, a 1-Wire sensor measuring carbon dioxide and atmospheric pressure for environmental monitoring and smart ventilation systems. Includes specifications, installation, and features.
Preview TERACOM TD1340 S0 Pulse Counter User Manual | MODBUS RTU Interface
Comprehensive user manual for the TERACOM TD1340 S0 pulse counter. Learn about its features, specifications, MODBUS RTU communication, and applications in industrial monitoring and energy management.