E Plus E Sigma 05 Modular Sensor Platform
Litlhaloso
- Lebitso la Sehlahiswa: Sigma 05 – Sensor Hub / Modular Sensor Platform
- Sehokelo: RS485
- Tsamaiso: Modbus RTU
- Maximum Number of Probes: 3
- Phepelo Voltage Range: 15 - 30 V DC
Litaelo tsa Tšebeliso ea Sehlahisoa
Plug-and-Play Operation / Setup
Sigma 05 is designed to work with E+E plug-and-play probes. By default, the automatic discovery function is enabled.
Latela mehato ena ho seta:
- Power off Sigma 05 before connecting or disconnecting probes.
- Sigma 05 will automatically recognize and configure the connected probes according to the predefined table.
- The assignment of measurands and output scaling is done automatically based on the connected probes.
Manual Operation / Setup
- Connect Sigma 05 to a personal computer running the PCS10 Product Configuration Software.
- Disable the automatic discovery function in the software.
- Assign measurands to outputs and configure output scaling as needed.
Moqtage Supply and Outputs
- Ensure correct installation and wiring to prevent overheating.
- Follow the wiring diagram provided for your product version.
- Phepelo voltage range is between 15 – 30 V DC.
Setupo sa Modbus
The factory settings for Modbus communication are as follows.
- Sekhahla sa Baud: 9 600
- Lintlha tsa data: 8
- Bonngoe: Leha ho le joalo
- Emisa likotoana: 1
- Aterese ea Modbus: Not set for Sigma 05
Kamohelo
The Sigma 05 has DNV maritime type approval. Refer to the User Manual for detailed information.
LIEKETSENG
LEMOHA KA KOPO
Fumana tokomane ena le lintlha tse ling tsa sehlahisoa ho rona website at www.epluse.com/sigma05.
Lintlha tse akaretsang
- Sigma 05 is a host device (Modbus master) for up to three E+E sensing probes/measurement devices with RS485 interface and Modbus RTU protocol.
- This Quick Guide focuses on the Sigma 05 functionality with E+E plug-and-play probes. Please make sure to review the Sigma 05 user manual at www.epluse.com/sigma05 for manual setup and other Sigma 05 features.
Plug and Play Operation Setup
- With enabled automatic discovery function (default setting), Sigma 05 automatically recognizes E+E plug-and-play probes and their combinations according to the table below, see “Probe Combinations and Automatic Discovery”.
- Furthermore, the assignment of the measurands to the outputs and display, as well as the scaling of the outputs is performed automatically according to the table.
- This setup can be changed subsequently by the user as required, see “Manual Operation / Setup” below.
LEMOHA KA KOPO
The Sigma 05 must be powered off while connecting or disconnecting probes
Manual Operation Setup
- For manual setup, connect Sigma 05 to a personal computer running PCS10 Product Configuration Software, free download from www.epluse.com/pcs10.
- Disable the automatic discovery function and proceed with assigning measurands to the outputs and display as well as with the output scaling. See the user manual at www.epluse.com/sigma05.
Pin number Function
1 | Phepelo voltage*) |
2 | RS485 B (D-) |
3 | GND |
4 | RS485 A (D+) |
- Phepelo voltage at the probe connector is always equal to the supply voltage applied to Sigma 05. <
- Bohlokoa: Choose the Sigma 05 supply voltage (in the range 15 – 30 V DC) to match the probe supply requirements.
Moqtage Supply and Outputs
- TLHOKOMELO Ho kenngoa ka mokhoa o fosahetseng, likhoele kapa phepelo ea motlakase ho ka baka mocheso o feteletseng mme ka hona likotsi tsa motho kapa tšenyo ea thepa.
- Bakeng sa ho kenya mohala o nepahetseng oa sesebelisoa, ka linako tsohle sheba setšoantšo sa wiring se hlahisitsoeng bakeng sa mofuta oa sehlahisoa se sebelisitsoeng.
- Moetsi a ke ke a jara boikarabello bakeng sa likotsi tsa botho kapa ts'enyehelo ea thepa ka lebaka la ts'ebetso e fosahetseng, ho kenya, ho kenya mohala, phepelo ea motlakase le tlhokomelo ea sesebelisoa.
Setupo sa Modbus
Litlhophiso tsa feme | Lintlha tse ka khethoang ke basebelisi (ka PCS10) | |
Sekhahla sa Baud | 9 600 | 9 600, 19 200, 38 400, 57 600, 76 800, 115 200 |
Lintlha tsa data | 8 | 8 |
Parity | Leha ho le joalo | Ha ho le e 'ngoe, e makatsang, esita le |
Emisa likotoana | 1 | 1, 2 |
Aterese ea Modbus | Sigma 05 has no Modbus address |
- Litlhophiso tse khothaletsoang bakeng sa lisebelisoa tse ngata marang-rang a Modbus RTU ke 9600, 8, Even, 1.
- The Sigma 05 represents 1 unit load in a Modbus network.
Kamohelo
DNV (Det Norske Veritas) maritime type approval.
- For the scope of approval, please refer to the User Manual, chapter 9.4 DNV Type Approval.
Probe Combinations and Automatic Discovery
Analogue Output 1 | Analogue Output 2 | Display line 1 | Display line 2 | Display line 3 | |||||||||
Lipatlisiso | Yuniti | Scale SI | Scale US | Yuniti | Scale SI | Scale US | SI | US | SI | US | SI | US | |
1 EE072 | RH | 0…100 % | 0…100 % | T | -40…80 °C | -40…176 °F | RH[%] | RH[%] | T[°C] | T[°F] | |||
2 EE074 | T | -40…80 °C | -40…176 °F | T[°C] | T[°F] | ||||||||
3 EE872-M13 | CO2 | Range of probe | Range of probe | RH | 0…100 % | 0…100 % | CO2[ppm] | CO2[ppm] | RH[%] | RH[%] | T[°C] | T[°F] | |
4 EE872-M10 | CO2 | Range of probe | Range of probe | CO2[ppm] | CO2[ppm] | ||||||||
5 EE671 | v | Range of probe | Range of probe | v[m/s] | v[ft/min] | ||||||||
6 EE680 | vn | Range of probe | Range of probe | T | 0… 50 ° C | 32…122 °F | vn[m/s] | vn[ft/min] | T[°C] | T[°F] | |||
7 HA010406 | RH | 0…100 % | 0…100 % | T | -40…180 °C | -40…356 °F | RH[%] | RH[%] | T[°C] | T[°F] | |||
8 | EE072 | RH | 0…100 % | 0…100 % | RH[%] | RH[%] | |||||||
EE074 | T | -40…80 °C | -40…176 °F | T[°C] | T[°F] | ||||||||
9 | EE872-M13 | CO2 | Range of probe | Range of probe | CO2[ppm] | CO2[ppm] | |||||||
EE072 | RH | 0…100 % | 0…100 % | RH[%] | RH[%] | T[°C] | T[°F] | ||||||
10 | EE872-M10 | CO2 | Range of probe | Range of probe | CO2[ppm] | CO2[ppm] | |||||||
EE072 | RH | 0…100 % | 0…100 % | RH[%] | RH[%] | T[°C] | T[°F] | ||||||
11 | EE671 | v | Range of probe | Range of probe | v[m/s] | v[ft/min] | |||||||
EE072 | RH | 0…100 % | 0…100 % | RH[%] | RH[%] | T[°C] | T[°F] | ||||||
12 |
EE680 | v | Range of probe | Range of probe | vn[m/s] | vn[ft/min] | |||||||
EE072 | RH | 0…100 % | 0…100 % | RH[%] | RH[%] | T[°C] | T[°F] | ||||||
13 |
EE872-M13 | CO2 | Range of probe | Range of probe | CO2[ppm] | CO2[ppm] | RH[%] | RH[%] | |||||
EE074 | T | -40…80 °C | -40…176 °F | T[°C] | T[°F] | ||||||||
14 |
EE872-M10 | CO2 | Range of probe | Range of probe | CO2[ppm] | CO2[ppm] | |||||||
EE074 | T | -40…80 °C | -40…176 °F | T[°C] | T[°F] | ||||||||
15 |
EE671 | v | Range of probe | Range of probe | v[m/s] | v[ft/min] | |||||||
EE074 | T | -40…80 °C | -40…176 °F | T[°C] | T[°F] | ||||||||
16 |
EE680 | vn | Range of probe | Range of probe | vn[m/s] | vn[ft/min] | |||||||
EE074 | T | -40…80 °C | -40…176 °F | T[°C] | T[°F] | ||||||||
17 |
EE872-M13 | CO2 | Range of probe | Range of probe | CO2[ppm] | CO2[ppm] | T[°C] | T[°F] | |||||
EE671 | v | Range of probe | Range of probe | v[m/s] | v[ft/min] | ||||||||
18 |
EE872-M13 | CO2 | Range of probe | Range of probe | CO2[ppm] | CO2[ppm] | T[°C] | T[°F] | |||||
EE680 | vn | Range of probe | Range of probe | vn[m/s] | vn[ft/min] | ||||||||
19 |
EE872-M10 | CO2 | Range of probe | Range of probe | CO2[ppm] | CO2[ppm] | |||||||
EE671 | v | Range of probe | Range of probe | v[m/s] | v[ft/min] | ||||||||
20 |
EE872-M10 | CO2 | Range of probe | Range of probe | CO2[ppm] | CO2[ppm] | |||||||
EE680 | vn | Range of probe | Range of probe | vn[m/s] | vn[ft/min] | T[°C] | T[°F] | ||||||
21 |
EE680 | vn | Range of probe | Range of probe | vn[m/s] | vn[ft/min] | T[°C] | T[°F] | |||||
EE671 | v | Range of probe | Range of probe | v[m/s] | v[ft/min] | ||||||||
22 HTP501 | RH | 0…100 % | 0…100 % | T | -40…120 °C | -40…248 °F | RH[%] | RH[%] | T[°C] | T[°F] | |||
23 |
HTP501 | RH | 0…100 % | 0…100 % | RH[%] | RH[%] | T[°C] | T[°F] | |||||
EE074 | T | -40…120 °C | -40…248 °F | T[°C] | T[°F] | ||||||||
24 MOP301 | aw | 0…1 | 0…1 | T | -40…120 °C | -40…248 °F | bona[-] | bona[-] | T[°C] | T[°F] | |||
25 |
MOP301 | aw | 0…1 | 0…1 | bona[-] | bona[-] | T[°C] | T[°F] | |||||
EE074 | T | -40…120 °C | -40…248 °F | T[°C] | T[°F] |
- E+E Elektronik Ges.mbH
- Langwiesen 7
- 4209 Engerwitzdorf
- Austria
- T +4372356050
- F+4372356058
- info@epluse.com
- www.epluse.com
- QG_Sigma_05
- Mofuta v2.0
- 06-2024
- Litokelo tsohle li sirelelitsoe
- 195001
LBH
- Q: Can I connect more than three probes to the Sigma 05?
- A: No, the Sigma 05 supports a maximum of three probes.
- Q: What happens if I use a supply voltage outside the recommended range?
- A: Ho sebelisa matla a phepelotage outside the range of 15 – 30 V DC may result in incorrect device operation or damage.
- Q: How do I change the Modbus settings?
- A: Use the PCS10 Product Configuration Software to select user-selectable values for Modbus settings.