E-Plus-E-LOGO

E Plus E Sigma 05 Modular Sensor Platform

E-Plus-E-Sigma-05-Modular-Sensor-Platform-PRODUCT

Specifications

  • Product Name: Sigma 05 – Sensor Hub / Modular Sensor Platform
  • Interface: RS485
  • Protocol: Modbus RTU
  • Maximum Number of Probes: 3
  • Supply Voltage Range: 15 – 30 V DC

Product Usage Instructions

Plug-and-Play Operation / Setup

Sigma 05 is designed to work with E+E plug-and-play probes. By default, the automatic discovery function is enabled.

Follow these steps for setup:

  1. Power off Sigma 05 before connecting or disconnecting probes.
  2. Sigma 05 will automatically recognize and configure the connected probes according to the predefined table.
  3. The assignment of measurands and output scaling is done automatically based on the connected probes.

Manual Operation / Setup

  1. Connect Sigma 05 to a personal computer running the PCS10 Product Configuration Software.
  2. Disable the automatic discovery function in the software.
  3. Assign measurands to outputs and configure output scaling as needed.

Voltage Supply and Outputs

  • Ensure correct installation and wiring to prevent overheating.
  • Follow the wiring diagram provided for your product version.
  • The supply voltage range is between 15 – 30 V DC.

Modbus Setup

The factory settings for Modbus communication are as follows.

  • Baud rate: 9 600
  • Data bits: 8
  • Parity: Even
  • Stop bits: 1
  • Modbus address: Not set for Sigma 05

Approval

The Sigma 05 has DNV maritime type approval. Refer to the User Manual for detailed information.

INTRODUCTION

PLEASE NOTE

Find this document and further product information on our website at www.epluse.com/sigma05.

General Information

  • Sigma 05 is a host device (Modbus master) for up to three E+E sensing probes/measurement devices with RS485 interface and Modbus RTU protocol.
  • This Quick Guide focuses on the Sigma 05 functionality with E+E plug-and-play probes. Please make sure to review the Sigma 05 user manual at www.epluse.com/sigma05 for manual setup and other Sigma 05 features.

Plug and Play Operation Setup

  • With enabled automatic discovery function (default setting), Sigma 05 automatically recognizes E+E plug-and-play probes and their combinations according to the table below, see “Probe Combinations and Automatic Discovery”.
  • Furthermore, the assignment of the measurands to the outputs and display, as well as the scaling of the outputs is performed automatically according to the table.
  • This setup can be changed subsequently by the user as required, see “Manual Operation / Setup” below.

PLEASE NOTE

The Sigma 05 must be powered off while connecting or disconnecting probes

Manual Operation Setup

  • For manual setup, connect Sigma 05 to a personal computer running PCS10 Product Configuration Software, free download from www.epluse.com/pcs10.
  • Disable the automatic discovery function and proceed with assigning measurands to the outputs and display as well as with the output scaling. See the user manual at www.epluse.com/sigma05.E-Plus-E-Sigma-05-Modular-Sensor-Platform-FIG-1

Pin number Function

1Supply voltage*)
2RS485 B (D-)
3GND
4RS485 A (D+)
  • The supply voltage at the probe connector is always equal to the supply voltage applied to Sigma 05. <
  • Important: Choose the Sigma 05 supply voltage (in the range 15 – 30 V DC) to match the probe supply requirements.

Voltage Supply and Outputs

  • WARNING Incorrect installation, wiring or power supply may cause overheating and therefore personal injuries or property damage.
  • For correct cabling of the device, always observe the presented wiring diagram for the product version used.
  • The manufacturer cannot be held responsible for personal injuries or damage to property as a result of incorrect handling, installation, wiring, power supply and maintenance of the device.E-Plus-E-Sigma-05-Modular-Sensor-Platform-FIG-2

Modbus Setup

 Factory settingsUser selectable values (via PCS10)
Baud rate9 6009 600, 19 200, 38 400, 57 600, 76 800, 115 200
Data bits88
ParityEvenNone, odd, even
Stop bits11, 2
Modbus addressSigma 05 has no Modbus address 
  • The recommended settings for multiple devices in a Modbus RTU network are 9600, 8, Even, 1.
  • The Sigma 05 represents 1 unit load in a Modbus network.

Approval

  • E-Plus-E-Sigma-05-Modular-Sensor-Platform-FIG-3DNV (Det Norske Veritas) maritime type approval.
  • For the scope of approval, please refer to the User Manual, chapter 9.4 DNV Type Approval.

Probe Combinations and Automatic Discovery

 Analogue Output 1Analogue Output 2Display line 1Display line 2Display line 3
ProbesUnitScale SIScale USUnitScale SIScale USSIUSSIUSSIUS
1  EE072RH0…100 %0…100 %T-40…80 °C-40…176 °FRH[%]RH[%]T[°C]T[°F]  
2  EE074T-40…80 °C-40…176 °F   T[°C]T[°F]    
3  EE872-M13CO2Range of probeRange of probeRH0…100 %0…100 %CO2[ppm]CO2[ppm]RH[%]RH[%]T[°C]T[°F]
4  EE872-M10CO2Range of probeRange of probe   CO2[ppm]CO2[ppm]    
5  EE671vRange of probeRange of probe   v[m/s]v[ft/min]    
6  EE680vnRange of probeRange of probeT0…50 °C32…122 °Fvn[m/s]vn[ft/min]T[°C]T[°F]  
7  HA010406RH0…100 %0…100 %T-40…180 °C-40…356 °FRH[%]RH[%]T[°C]T[°F]  
8EE072RH0…100 %0…100 %   RH[%]RH[%]    
EE074   T-40…80 °C-40…176 °F  T[°C]T[°F]  
9EE872-M13CO2Range of probeRange of probe   CO2[ppm]CO2[ppm]    
EE072   RH0…100 %0…100 %  RH[%]RH[%]T[°C]T[°F]
10EE872-M10CO2Range of probeRange of probe   CO2[ppm]CO2[ppm]    
EE072   RH0…100 %0…100 %  RH[%]RH[%]T[°C]T[°F]
11EE671vRange of probeRange of probe   v[m/s]v[ft/min]    
EE072   RH0…100 %0…100 %  RH[%]RH[%]T[°C]T[°F]
 

12

EE680vRange of probeRange of probe   vn[m/s]vn[ft/min]    
EE072   RH0…100 %0…100 %  RH[%]RH[%]T[°C]T[°F]
 

13

EE872-M13CO2Range of probeRange of probe   CO2[ppm]CO2[ppm]  RH[%]RH[%]
EE074   T-40…80 °C-40…176 °F  T[°C]T[°F]  
 

14

EE872-M10CO2Range of probeRange of probe   CO2[ppm]CO2[ppm]    
EE074   T-40…80 °C-40…176 °F  T[°C]T[°F]  
 

15

EE671vRange of probeRange of probe   v[m/s]v[ft/min]    
EE074   T-40…80 °C-40…176 °F  T[°C]T[°F]  
 

16

EE680vnRange of probeRange of probe   vn[m/s]vn[ft/min]    
EE074   T-40…80 °C-40…176 °F  T[°C]T[°F]  
 

17

EE872-M13CO2Range of probeRange of probe   CO2[ppm]CO2[ppm]  T[°C]T[°F]
EE671   vRange of probeRange of probe  v[m/s]v[ft/min]  
 

18

EE872-M13CO2Range of probeRange of probe   CO2[ppm]CO2[ppm]  T[°C]T[°F]
EE680   vnRange of probeRange of probe  vn[m/s]vn[ft/min]  
 

19

EE872-M10CO2Range of probeRange of probe   CO2[ppm]CO2[ppm]    
EE671   vRange of probeRange of probe  v[m/s]v[ft/min]  
 

20

EE872-M10CO2Range of probeRange of probe   CO2[ppm]CO2[ppm]    
EE680   vnRange of probeRange of probe  vn[m/s]vn[ft/min]T[°C]T[°F]
 

21

EE680vnRange of probeRange of probe   vn[m/s]vn[ft/min]  T[°C]T[°F]
EE671   vRange of probeRange of probe  v[m/s]v[ft/min]  
22 HTP501RH0…100 %0…100 %T-40…120 °C-40…248 °FRH[%]RH[%]T[°C]T[°F]  
 

23

HTP501RH0…100 %0…100 %   RH[%]RH[%]T[°C]T[°F]  
EE074   T-40…120 °C-40…248 °F    T[°C]T[°F]
24 MOP301aw0…10…1T-40…120 °C-40…248 °Faw[-]aw[-]T[°C]T[°F]  
 

25

MOP301aw0…10…1   aw[-]aw[-]T[°C]T[°F]  
EE074   T-40…120 °C-40…248 °F    T[°C]T[°F]
  • E+E Elektronik Ges.m.b.H.
  • Langwiesen 7
  • 4209 Engerwitzdorf
  • Austria
  • T +4372356050
  • F +4372356058
  • info@epluse.com
  • www.epluse.com
  • QG_Sigma_05
  • Version v2.0
  • 06-2024
  • All rights reserved
  • 195001E-Plus-E-Sigma-05-Modular-Sensor-Platform-FIG-4

FAQ

  • Q: Can I connect more than three probes to the Sigma 05?
    • A: No, the Sigma 05 supports a maximum of three probes.
  • Q: What happens if I use a supply voltage outside the recommended range?
    • A: Using a supply voltage outside the range of 15 – 30 V DC may result in incorrect device operation or damage.
  • Q: How do I change the Modbus settings?
    • A: Use the PCS10 Product Configuration Software to select user-selectable values for Modbus settings.

Documents / Resources

E Plus E Sigma 05 Modular Sensor Platform [pdf] User Guide
Sigma 05 Modular Sensor Platform, Sigma 05, Modular Sensor Platform, Sensor Platform

References

Leave a comment

Your email address will not be published. Required fields are marked *