General description

Module Loop Controller contains two loops. Each loop can support up to 210 addresable devices M series. Please see the User Manual 7000M for more information

Installing module on DIN rail
Instructions

Warning Icon After mounting on the DIN rail, slide carefully and connect with the front one module
Module Loop Controller

Installation
Installation
Dismantling
Dismantling
Dismantling
Module
LoopController
1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16
Loop 1″i-*
start
Earth Loop 1.•-•
start
Loop r+-
end
Earth Loop l’-‘
end
Loop 2’+’
start
Earth Loop 2″-
start
Loop 2’+’
end
Earth Loop 2′-‘
end
NOT
USED
NOT
USED
Earth Earth

Technical data

Connecting type DIN rail
Connecting line to loop two-wire shielded ­re rated cable (recommended 0,75 – 1.5mm²).Connecting line to loop
Loops per module 2
Modules per panel 5
Maximum resistance of a loop(incl. all contacts and build-in isolators) 28Ω (- wire) / (210 devices, 1.5mm², 2 100 m distance) 60Ω (+ wire)
Maximum Consumption from one loop 300mA/24VDC
Power supply (ensured by PSU module) (27,6 +1/-8) VDC
Total module outputs comsumption please see p.2.5 User Manual 7000M