Unipos 7000M Loop Controller Instruction Manual
General description
Module Loop Controller contains two loops. Each loop can support up to 210 addresable devices M series. Please see the User Manual 7000M for more information
Installing module on DIN rail
After mounting on the DIN rail, slide carefully and connect with the front one module
Installation

Dismantling



Dismantling


Module LoopController |
1 | 2 | 3 | 4 | 5 | 6 | 7 | 8 | 9 | 10 | 11 | 12 | 13 | 14 | 15 | 16 |
Loop 1″i-* start |
Earth | Loop 1.•-• start |
Loop r+- end |
Earth | Loop l’-‘ end |
Loop 2’+’ start |
Earth | Loop 2″-– start |
Loop 2’+’ end |
Earth | Loop 2′-‘ end |
NOT USED |
NOT USED |
Earth | Earth |
Technical data
Connecting type | DIN rail |
Connecting line to loop | two-wire shielded re rated cable (recommended 0,75 – 1.5mm²).Connecting line to loop |
Loops per module | 2 |
Modules per panel | 5 |
Maximum resistance of a loop(incl. all contacts and build-in isolators) | 28Ω (- wire) / (210 devices, 1.5mm², 2 100 m distance) 60Ω (+ wire) |
Maximum Consumption from one loop | 300mA/24VDC |
Power supply (ensured by PSU module) | (27,6 +1/-8) VDC |
Total module outputs comsumption | please see p.2.5 User Manual 7000M |
The specifications described herein are subject to change without notice.
Documents / Resources
![]() |