Payne 45MBFA Floor Console Unit Ductless System

Payne-45MBFA-Floor-Console-Unit-Ductless-System-product-image

Specifications

  • Model: 45MBFA
  • Type: Floor Console Unit Ductless System
  • Sizes: 9K to 16K

Product Information

The 45MBFA series ductless system is a matched combination of an outdoor condensing unit and an indoor fan coil unit connected only by refrigerant tubing and wires. It offers a perfect balance between budget limits, energy savings, and comfort.

NOTE: Images are for illustration purposes only. Actual models may differ slightly.Payne-45MBFA-Floor-Console-Unit-Ductless-System-image (1)

Product Data

INDUSTRY LEADING FEATURES / BENEFITS

A PERFECT BALANCE BETWEEN BUDGET LIMITS, ENERGY SAVINGS AND COMFORT
The 45MBFA series ductless system are a matched combination of an outdoor condensing unit and an indoor fan coil unit connected only by refrigerant tubing and wires.

The fan coil can be mounted on the floor or against the wall. This selection of fan coils permits creative solutions to design problems such as:

  • Add-ons to current space (an office or family room addition)
  • Special space requirements
  • When changes in the load cannot be handled by the existing system
  • When adding air conditioning to spaces that are heated by hydronic or electric heat and have no ductwork
  • Historical renovations or any application where preserving the look of the original structure is essential.
    • The ideal compliment to your ducted system when it is impractical or prohibitively expensive to use ductwork.
    • The compact indoor fan coil units take up very little space in the room and do not obstruct windows. The fan coils are attractively styled to blend with most room decors. Advanced system components incorporate innovative technology to provide reliable cooling performance at low sound levels.

LOW SOUND LEVELS
When noise is a concern, the ductless systems are the answer. The indoor units are whisper quiet. There are no compressors indoors, either in the conditioned space or directly over it, and there is none of the noise usually generated by air being forced through ductwork.

SECURE OPERATION
If security is an issue, outdoor and indoor units are connected only by refrigerant piping and wiring to prevent intruders from crawling through ductwork. In addition, since outdoor units can be installed close to an outside wall, coils are protected from vandals and severe weather.

SIMPLE SERVICING AND MAINTENANCE

  • Removing the top panel on the outdoor units provides immediate access to the control compartment, providing a service technician access to check the unit’s operation. In addition, the draw-thru design of the outdoor section means that dirt accumulates on the outside surface of the coil. Coils can be cleaned quickly from the inside using a pressure hose and detergent.
  • On all indoor units, service and maintenance expense is reduced due to easy-to-use cleanable filters. In addition, these console systems have extensive self-diagnostics and a refrigerant leak detection and mitigation system to assist in troubleshooting.

AN ELEGANT AND COMPACT DESIGN

  • The look of newly-upgraded console unit features flowing lines that is aesthetic enough.
  • Its unobtrusive design can easily fit into most interiors with different decorating-schemes.
  • The width of the machine has been reduced by 10mm, taking less space.

A PERFECT CHOICE FOR NEW BUILDINGS AND RENOVATION PROJECTS

  • Console unit can be installed standing on the floor, or wall-mounted
  • It is a great option for radiator replacement in order to save your space while provide more functions.Payne-45MBFA-Floor-Console-Unit-Ductless-System-image (2)

Dual Air Outlets With Larger Dimension
Efficiently improve air volume, providing constant, quick cooling and heating throughout whole year.Payne-45MBFA-Floor-Console-Unit-Ductless-System-image (3)

BUILT-IN RELIABILITY

  • Ductless system indoor and outdoor units are designed to provide years of trouble-free operation.
  • The console indoor units include protection against freeze-up and high evaporator temperatures on heat pumps.
  • The condensing units on heat pumps are protected by a three-minute time delay before the compressor starts the over-current protection and high temperature protection.

INDIVIDUAL ROOM COMFORT
Maximum comfort is provided because each space can be controlled individually based on usage pattern. The air sweep feature provided permits optimal room air mixing to eliminate hot and cold spots for occupant comfort. In addition, year-round comfort can be provided with heat pumps.

ECONOMICAL OPERATION
The ductless system design allows individual room heating or cooling when required. There is no need to run large supply-air fans or chilled water pumps to handle a few spaces with unique load patterns. In addition, because air is moved only in the space required, no energy is wasted moving air through ducts.

EASY-TO-USE CONTROLS
The console units have microprocessor-based controls to provide the ultimate in comfort and efficiency. The user friendly wireless remote control provides the interface between user and the unit.

ACCESSORIES
Customizing these ductless systems to your application is easily accomplished. Adding a condensate pump accessory to the console fan coil provides installation flexibility.

OPTIONAL WIRED CONTROLLER

AGENCY LISTINGS
All systems are listed with AHRI (Air Conditioning, Heating & Refrigeration Institute), and ETL.Payne-45MBFA-Floor-Console-Unit-Ductless-System-image (4)

Humidity Control: Efficiently dehumidifies the air to keep your indoors at comfortable humidity level.

MODEL NUMBER NOMENCLATURE

Payne-45MBFA-Floor-Console-Unit-Ductless-System-image (5)

STANDARD FEATURES AND ACCESSORIES

Table 1 – Features

EASE OF INSTALLATION
Mounting Brackets S
Low Voltage Controls S
Floor Mounting Installation S
Ceiling Installation S
COMFORT FEATURES
Microprocessor Controls S
Wired Remote Control A
Wireless Remote Control S
Humidity Sensor S
Wi-Fi Remote Control (Dongle Only with Built-In USB) A
Automatic Up-Down Air Sweep S
Air Direction Control S
Auto Restart Function S
Cold Blow Protection On Heat Pumps S
Freeze Protection Mode On Heat Pumps S
Turbo Mode S
Silence Mode S
Auto Changeover On Heat Pumps S
Follow Me S
ENERGY SAVING FEATURES
Sleep Mode S
Stop/Start Timer S
46° F Heating Mode (Heating Setback) S
SAFETY AND RELIABILITY
Indoor Coil Freeze Protection S
Aluminum Golden Hydrophilic pre-coated fins S
Indoor Coil High Temp Protection in Heating Mode S
EASE OF SERVICE AND MAINTENANCE
Cleanable Filters S
Diagnostics S
Liquid Line Pressure Taps S
APPLICATION FLEXIBILITY
Condensate Pumps A

Legend

  • S – Standard
  • A – Accessory

Table 2 – Accessories

MODEL NO. DESCRIPTION FOR MODELS
KSACN1201AAA Wired Non-Programmable Controller All Sizes
KSACN1401AAA Wired Programmable Controller All Sizes
KSAIF0701AAA Smart Kit, USB Dongle (Only with Built-In USB) All Sizes

DIMENSIONS AND CLEARANCES

Payne-45MBFA-Floor-Console-Unit-Ductless-System-image (6)

Table 3 – Dimensions and Weights

SYSTEM SIZE 09K 12K 16K
(208/230 V) (208/230 V) (208/230 V)
Height (H) in (mm) 24.45 (621) 24.45 (621) 24.45 (621)
Width (W) in (mm) 31.26 (794) 31.26 (794) 31.26 (794)
Depth (D) in (mm) 7.87 (200) 7.87 (200) 7.87 (200)
Weight – Net lbs. (kg) 32.85 (14.9) 32.85 (14.9) 32.85 (14.9)
PACKAGING
Height in (mm) 28.31 (719) 28.31 (719) 28.31 (719)
Width in (mm) 34.06 (865) 34.06 (865) 34.06 (865)
Depth in (mm) 11.02 (280) 11.02 (280) 11.02 (280)
Weight – Gross lbs. (kg) 41.89 (19) 41.89 (19) 41.89 (19)

SPECIFICATIONS

Table 4 – Specifications

Size 9K 12K 16K
Indoor Model Number 45MBFAQ09XA3 45MBFAQ12XA3 45MBFAQ16XA3
Power supply V;Ph;Hz 208/230V;1Ph;60HZ
INDOOR FAN SPECIFICATIONS Material Fiberglass+AS
Type GL-98*538-I
 Diameter inch 3.9 3.9 3.9
mm 98 98 98
 Height inch 21.2 21.2 21.2
mm 538 538 538
INDOOR MOTOR SPECIFICATIONS-LOWER Model ZKFP-13-8-104
Type DC
Input W 25.0 25.0 25.0
Max. input W 50.0 50.0 50.0
Output W 18.8 18.8 18.8
FLA A 0.5 0.5 0.5
Rated HP HP 0.025 0.025 0.025
Range of current Amps 0.1~0.42 0.1~0.42 0.1~0.42
Rated current Amps 0.22 0.22 0.22
Speed rev/min 980/860/620 980/860/620 1100/1000/900
Rated RPM rev/min 980 980 1100
Insulation class E
Safe class IPX0
INDOOR MOTOR SPECIFICATIONS-UPPER Model ZKFP-13-8-136
Type DC
Input W 20.5 20.5 20.5
Max. input W 39.6 39.6 39.6
Output W 15.4 15.4 15.4
FLA A 0.5 0.5 0.5
Rated HP HP 0.021 0.021 0.021
Range of current Amps 0.2~0.38 0.2~0.38 0.2~0.38
Rated current Amps 0.20 0.20 0.20
Speed rev/min 980/860/620 980/860/620 1100/1000/900
Rated RPM rev/min 980 980 1100
Insulation class B
Safe class IP20
Size 9K 12K 16K
Indoor Model Number 45MBFAQ09XA3 45MBFAQ12XA3 45MBFAQ16XA3
 INDOOR REFRIGERANT COIL SPECIFICATIONS Number of rows Rows 2 2 2
Tube outside dia. inch 0.276 0.276 0.276
mm 7 7 7
Nominal Tube Wall Inch (mm) 0.00905 (0.23) 0.00905 (0.23) 0.00905 (0.23)
Tube Enhancement (Yes/No) Yes
Tube Material Copper
Tube pitch (a) x row pitch (b) inch 0.83×0.53 0.83×0.53 0.83×0.53
mm 21×13.37 21×13.37 21×13.37
Fin Spacing FPI 20 20 20
mm 1.3 1.3 1.3
Fin type Louvered
Fin Material Gold hydrophilic aluminum
Coil length x height x width inch 21.65×14.88×1.05 21.65×14.88×1.05 21.65×14.88×1.05
mm 550x378x26.74 550x378x26.74 550x378x26.74
Face area ft2 2.24 2.24 2.24
Number of circuits # 2 2 2
MOISTURE REMOVAL Dehumidifying Volume L/h 0.81 1.48 2.18

COMPATIBILITY TABLE

Table 5 – Compatibility

UNIT MODEL
Single Zone Compatible 37MARA
37MAHA
Multi Zone Compatible 37MGHA
37MGRA

APPLICATION DATA

Unit Selection

  • Select equipment to either match or is slightly less than the anticipated peak load. This provides better humidity control, fewer unit cycles, and less part-load operation.
  • For units used in spaces with high sensible loads, base equipment selection on unit sensible load, not on total anticipated load. Adjust for anticipated room wet bulb temperature to avoid undersizing equipment.

Unit Mounting (Indoor)
Refer to the unit’s installation instructions for further details.

  • Unit leveling – For reliable operation, units should be level in all planes.
  • Clearance – Provide adequate clearance for airflow (Fig. 4).
  • Unit location – Select a location which provides the best air circulation for the room.

These units should be positioned on the floor, against the wall for the best air circulation. The unit return and discharge should not be obstructed by furniture, curtains, or anything which may cause unit short cycling or air recirculation. Place the unit in the middle of the selected wall (if possible). Use an outside wall, if available, to make piping easier, and place the unit so it faces the normal location of room occupants.

Mounting Template

  • Refer to the unit’s installation instructions for further details.
  • The fan coil units are furnished with mounting to mark the location of the wiring, and refrigeration line hole locations.

Support
Adequate support must be provided to support the weight of the
fan coil. Refer to “DIMENSIONS AND CLEARANCES” on page 5 and “SPECIFICATIONS” on page 6 for the fan coil weight, and the base unit dimensional drawings (in the installation instructions) for the mounting brackets location.

Table 6 – System Operating Conditions

OPERATING RANGE MIN/MAX °F (°C)
COOLING HEATING
INDOOR DB 60 / 90 (17 / 32) 32 / 86 (0 / 30)

NOTE: Reference the product installation instructions for more information.

Drain Connections

Install drains to meet the local plumbing codes. If adequate gravity drainage cannot be provided, the unit should be equipped with an accessory condensate pump. Drain size is 5/8 in (16mm).

Refrigerant Lines

General Refrigerant Line Sizing:

  1. The outdoor units are shipped with a full charge of r454b refrigerant.
  2. Refrigerant lines should not be buried in the ground. If it is necessary to bury the lines, not more than 36-in (914 mm) should be buried. Provide a minimum 6-in (152 mm) vertical rise to the service valves to prevent refrigerant migration.
  3. Both lines must be insulated. Use a minimum of 1/2-in. (12.7 mm) thick insulation. Closed-cell insulation is recommended in all long-line applications.
  4. Special consideration should be given to isolating the interconnecting tubing from the building structure. Isolate the tubing so that vibration or noise is not transmitted into the structure.

WIRING
All wires must be sized per NEC (National Electrical Code) or CEC (Canadian Electrical Code) and local codes. Use Electrical Data table MCA (minimum circuit amps) and MOCP (maximum over current protection) to correctly size the wires and the disconnect fuse or breakers respectively.

Recommended Connection Method for Power and Communication Wiring:

  • The main power is supplied to the outdoor unit. The field supplied 14/3 stranded wire with ground with a 600 volt insulation rating, power/communication wiring from the outdoor unit to indoor unit consists of four (4) wires and provides the power for the indoor unit. Two wires are line voltage AC power, one is communication wiring (S) and the other is a ground wire. Wiring between indoor and outdoor unit is polarity sensitive. The use of BX wire is NOT recommended.
  • If installed in a high Electromagnetic field (EMF) area and communication issues exists, a 14/2 stranded shielded wire can be used to replace L2 and (S) between outdoor unit and indoor unit landing the shield onto ground in the outdoor unit only.

EQUIPMENT DAMAGE HAZARD

  • Failure to follow this caution may result in equipment damage or improper operation.
  • Wires should be sized based on NEC and local codes.
  • Failure to follow this caution may result in equipment damage or improper operation.
  • Be sure to comply with local codes while running wire from the indoor unit to the outdoor unit.
  • Every wire must be connected firmly. Loose wiring may cause the terminal to overheat or result in unit malfunction. A fire hazard may also exist. Ensure all wiring is tightly connected.
  • No wire should touch the refrigerant tubing, compressor or any moving parts.
  • Disconnecting means must be provided and shall be located within sight and readily accessible from the air conditioner.
  • Connecting cable with conduit shall be routed through the hole

CONTROL SYSTEM

The unit is equipped with a microprocessor control to perform two functions:

  1. Provide safety for the system
  2. Control the system and provide optimum levels of comfort and efficiency.
  • The main microprocessor is located on the control board of the fan coil unit (outdoor units have a microprocessor too) with thermistors located in the fan coil air inlet and on the indoor coil.
  • Heat pump units have a thermistor on the outdoor coil. These thermistors monitor the system operation to maintain the unit within acceptable parameters and control the operating mode.

Wireless Remote ControlPayne-45MBFA-Floor-Console-Unit-Ductless-System-image (7)

  1. A wireless remote control is supplied for system operation of the console units.
  2. Each battery operated wireless (infrared) remote control may be used to control more than one unit.

Wired Remote Control (Optional)Payne-45MBFA-Floor-Console-Unit-Ductless-System-image (8)

  1. Optional wired remote controller used for system operation of all console units.
  2. Kit includes a wired remote controller and a connecting cable.
  3. Connect the wire terminal between the remote controller and the indoor unit.
  4. Displays in °F or °C and temperature increments every 1°F increment/0.5°C increment.

NOTE: Extension wire available through RCD

Part Number: 17401204000769

SOUND PRESSURE

Table 7 – Sound Pressure

SYSTEM SIZE 09K 12K 16K
Indoor Sound Pressure Level Turbo/High/Medium/Low/Silent 45/41.0/37.5/25.5/22.00 44/40.5/37.0/26.5/24.00 47/43.5/40.5/30.5/25.5

SOUND PRESSURE TESTING METHODPayne-45MBFA-Floor-Console-Unit-Ductless-System-image (9)

AIR FLOW DATA

Table 8 – Air Flow Data

SYSTEM SIZE 09K 12K 16K
Indoor (CFM) Turbo/High/Medium/Low/Silent 441.45 / 376.70 / 323.73 / 441.45 / 376.70 / 323.73 / 500.31 / 441.45 / 382.59 /
188.35 / 129.49 188.35 / 129.49 323.73 / 206.01

NC Curves

Payne-45MBFA-Floor-Console-Unit-Ductless-System-image (10) Payne-45MBFA-Floor-Console-Unit-Ductless-System-image (11)

AIR VELOCITY AND TEMPERATURE DISTRIBUTIONS
Discharge Angle 70°(Upper)/ 0°(Lower)

NOTE: Air Velocity and Temperature Plots will be updated in Imperial Units in next revision of this document.Payne-45MBFA-Floor-Console-Unit-Ductless-System-image (12) Payne-45MBFA-Floor-Console-Unit-Ductless-System-image (13)

Discharge Angle 20°(Upper)/ 0°(Lower)Payne-45MBFA-Floor-Console-Unit-Ductless-System-image (14) Payne-45MBFA-Floor-Console-Unit-Ductless-System-image (15)

WIRING DIAGRAM

Payne-45MBFA-Floor-Console-Unit-Ductless-System-image (16)

Table 9 – Wiring Connections

System Size 9K 12K 16K
V-Ph-Hz 208/230-1-60
Power Supply 4-Wire: includes ground wire (Outdoor); 208/230V-1Ph-60Hz
Interconnection to Indoor Unit Yes
Shielded Wire (Yes/No) Yes

REFRIGERANT SYSTEM DIAGRAM

Payne-45MBFA-Floor-Console-Unit-Ductless-System-image (17)

DISPLAY FUNCTION

NEW CONSOLE TYPEPayne-45MBFA-Floor-Console-Unit-Ductless-System-image (18)

Table 10 – Console IndicatorsPayne-45MBFA-Floor-Console-Unit-Ductless-System-image (19)

SAFETY FEATURES

  • Compressor three-minute delay at restart
    Compressor functions are delayed for up to ten seconds upon the first startup of the unit, and are delayed for up to three minutes upon subsequent unit restarts.
  • Automatic shutoff based on discharge temperature
    If the compressor discharge temperature exceeds a certain level for nine seconds, the compressor ceases operation.
  • Inverter module protection
    The inverter module has an automatic shutoff mechanism based on the unit’s current, voltage, and temperature. If automatic shutoff is initiated, the corresponding error code appears on the indoor unit and the unit ceases operation.

Indoor fan delayed operation

  • When the unit starts, the louver is automatically activated and the indoor fan operates after a period of setting time or the louver is in place.
  • If the unit is in heating mode, the indoor fan is regulated by the anti-cold wind function.

Compressor preheating
Preheating is automatically activated when T4 sensor is lower than setting temperature of outdoor air (35°F / 2°C).

Sensor redundancy and automatic shutoff

  • If one temperature sensor malfunctions, the air conditioner continues operation and displays the corresponding error code, allowing for emergency use.
  • When more than one temperature sensor is malfunctioning, the air conditioner ceases operation.

BASIC FUNCTIONS

Table 11 – Cases

Functions AUTO MODE
Cases Case 3
Models 09K-16K Ö

Table 12 – Unit Element Abbreviations

ABBREVIATION ELEMENT
T1 Indoor room temperature
T2 Coil temperature of evaporator
T3 Coil temperature of condenser
T4 Outdoor ambient temperature
TP Compressor discharge temperature
Tsc Adjusted setting temperature
CDIFTEMP Cooling shutdown temperature
HDIFTEMP2 Heating shutdown temperature

NOTE: Within this manual, CDIFTEMP, HDIFTEMP2…etc., are EEPROM parameters.

FAN MODE
When fan mode is activated:

  • The outdoor fan and compressor stop.
  • Temperature control is disabled and no temperature setting is displayed.
  • The indoor fan speed can be set to 1%~100% and auto.
  • The louver operations are identical to those in the COOLING mode.
  • AUTO fan: In fan-only mode, AC operates the same as AUTO fan in COOLING mode with the temperature set at 75°F(24°C).

COOL MODE

Indoor Fan Control

  1. In the COOLING mode, the indoor fan operates continuously. The fan speed can be set to 1%-100%, or low, medium, high and auto.
  2. Auto fan action in the COOLING mode:
  • Descent curve
    When T1-Tsc is lower than to 6.3°F/3.5°C, fan speed reduces to 80%; When T1-Tsc is lower than to 1.8°F/1°C, fan speed reduces to 60%; When T1-Tsc is lower than to 0.9°F/0.5°C, fan speed reduces to 40%; When T1-Tsc is lower than to 0°F/0°C, fan speed reduces to 20%;; When T1-Tsc is lower than to -0.9°F/-0.5°C, fan speed reduces to 1%;.
  • Rise curve
    When T1-Tsc is higher than or equal 0°F/0°C, fan speed increases to 20%;; When T1-Tsc is higher than or equal 0.9°F/0.5°C/, fan speed increases to 40%;
    When T1-Tsc is higher than or equal 1.8°F/1°C,, fan speed increases to 60%; When T1-Tsc is higher than or equal 2.7°F/1.5°C, fan speed increases to 80%; When T1-Tsc is higher than or equal 7.2°F/4°C, fan speed increases to 100%.

CONDENSER TEMPERATURE PROTECTIONPayne-45MBFA-Floor-Console-Unit-Ductless-System-image (20)

When the condenser temperature exceeds a configured value, the compressor ceases operation.

EVAPORATOR TEMPERATURE PROTECTIONPayne-45MBFA-Floor-Console-Unit-Ductless-System-image (21)

  • Off: Compressor stops.
  • Decrease: Decrease the running frequency to the lower level per 1 minute.
  • Hold: Keep the current frequency.
  • Resume: No limitation for frequency.

HEATING MODE (HEAT PUMP UNITS)

Indoor Fan Control:

  1. In the HEATING mode, the indoor fan operates continuously. The fan speed can be set to 1%-100% and auto.
    • Anti-cold air function
    • If the temperature difference of T2 changes during AUTO fan and causes the fan speed to change, run the current fan speed for 30 seconds first, the default interval is the interval before the fan speed changes, and then judge T2 according to the current interval after 30 seconds to get the final anti-cold air interval.Payne-45MBFA-Floor-Console-Unit-Ductless-System-image (22)ΔTE1=0
  2. Auto fan action in the HEATING mode:
    • Rise curve
      When T1-Tsc is higher than -2.7°F/-1.5°C,, fan speed reduces to 80%; When T1-Tsc is higher than 0°F/0°C, fan speed reduces to 60%; When T1-Tsc is higher than 0.9°F/0.5°C, fan speed reduces to 40%; When T1-Tsc is higher than 1.8°F/1°C, fan speed reduces to 20%.
    • Descent curve
      When T1-Tsc is lower than or equal to 0.9°F/0.5°C, fan speed increases to 40%;
      When T1-Tsc is lower than or equal to 0°F/0°C, fan speed increases to 60%; When T1-Tsc is lower than or equal to – 2.7°F/-1.5°C/,, fan speed increases to 80%;
      When T1-Tsc is lower than or equal to -5.4°F/-3°C, fan speed increases to 100%.

EVAPORATOR COIL TEMPERATURE PROTECTIONPayne-45MBFA-Floor-Console-Unit-Ductless-System-image (23)

  • Off: Compressor stops.
  • Decrease: Decrease the running frequency to the lower level per 20 seconds.
  • Hold: Keep the current frequency.
  • Resume: No limitation for frequency.

AUTO-MODE

  • AUTO-MODE can be selected with the remote controller and the temperature setting can be adjusted between 60°F/16°C~86°F/30°C.
  • In AUTO-MODE, the unit selects COOLING, HEATING or
  • FAN-ONLY mode on the basis of T1,Ts, outdoor ambient temperature(T4) and relative humidity (φ).Payne-45MBFA-Floor-Console-Unit-Ductless-System-image (24)

GUIDE SPECIFICATIONS

FLOOR CONSOLE UNIT DUCTLESS SYSTEM
Size Range: 0.75 to 1.33 Ton Nominal Cooling and Heating Capacity Model Number:45MBFA

Part 1 – GENERAL

  1. System Description
    Indoor console, direct-expansion fan coils are matched with a cooling only or heat pump outdoor unit.
  2. Agency Listings
    Unit is rated per AHRI Standards 210/240 and listed in the AHRI directory as a matched system.
  3. Delivery, Storage, And Handling
    Units stored and handled per the unit manufacturer’s recommendations.
  4. Warranty (For Inclusion By Specifying Engineer)

Part 2 – PRODUCTS

Equipment

  • General:
    Indoor, direct-expansion, floor-mounted fan coil. Unit is complete with a cooling/heating coil, fan, fan motor, piping connectors, electrical controls, microprocessor control system, and integral temperature sensing. Unit is furnished with an integral mounting bracket and mounting hardware.
  • Unit Cabinet:
    Cabinet discharge and inlet grilles are attractively styled, high-impact polystyrene. Cabinet is fully insulated for improved thermal and acoustic performance.
  • Fans:
    1. Fan is the tangential direct-drive blower type with an air intake in the center of the unit and discharge at the top and bottom front. An automatic, motor-driven vertical air sweep is provided standard.
    2. Air sweep operation is user selectable. The vertical sweep may be adjusted (using the remote control) and the horizontal air direction may be set manually.
  • Coil:
    Coil is a copper tube with aluminum fins and galvanized steel tube sheets. Fins are bonded to the tubes by mechanical expansion and specially golden hydrophilic pre-coated for enhanced wet-ability. A drip pan under the coil has a drain connection for hose attachment to remove condensate. The condensate pan has an internal trap.
  • Motor:
    The motor has an open drip-proof, permanently lubricated ball bearing with inherent overload protection. The fan motor has 4-speeds.
  • Controls:
    Controls consist of a microprocessor-based control system which controls the space temperature, determines the optimum fan speed, and runs self diagnostics. The temperature control ranges from 62°F to 86°F (17°C to 30°C) in increments of 1°F or 1°C, and have 46°F Heating Mode (Heating Setback). The wireless remote controller has the ability to act as the temperature sensing location for room comfort.

The unit has the following functions as a minimum:

  1. An automatic restart after power failure at the same operating conditions as at failure.
  2. A timer function to provide a minimum 24-hour timer cycle for system Auto Start/Stop.
  3. Temperature-sensing controls to sense the return air temperature.
  4. Indoor coil freeze protection.
  5. Wireless infrared remote control to enter set points and operating conditions.
  6. Automatic air sweep control to provide on or off activation of air sweep louvers.
  7. Dehumidification mode to provide increased latent removal capability by modulating system operation and set point temperature.
  8. Fan-only operation to provide room air circulation when no cooling is required.
  9. Diagnostics to conduct continuous checks of unit operation and warn of possible malfunctions. Error messages appear on the unit.
  10. Fan speed control is user-selectable: high, medium, low, or microprocessor controlled automatic operation during all operating modes.
  11. Automatic heating-to-cooling changeover in heat pump mode. Control includes a deadband to prevent rapid mode cycling between heating and cooling.
  12. Indoor coil high temperature protection is provided to detect excessive indoor discharge temperature when the unit is in heat pump mode.
  • Filters:
    Unit has a filter track with factory-supplied cleanable filters.
  • Electrical Requirements:
    Indoor fan motor to operate on 208-230V as specified. Power is supplied from the outdoor unit.
  • Operating Characteristics:
    The 45MBFA system has a minimum SEER (Seasonal Energy Efficiency Ratio) and HSPF at AHRI conditions, as listed on the specifications table of the outdoor unit.
  • Refrigerant Lines:
    All units should have refrigerant lines that can be oriented to connect from the left, right or back of unit. Both refrigerant lines need to be insulated.
  • Refrigerant Leak Detection and Mitigation
    System comes with a Refrigerant Leak Protection System.

Use of the AHRI Certified

TM Mark indicates a manufacturer’s participation in the program For verification of certification for individual products, go to www.ahridirectory.org.

FAQ

  • Q: Can the ductless system be used in both new buildings and renovation projects?
    • A: Yes, the 45MBFA series is an elegant and compact design, making it a perfect choice for both new construction and renovation projects.
  • Q: How do I reduce noise levels with the ductless system?
    • A: The indoor units are whisper quiet, eliminating noise generated by traditional ductwork systems. Ensure proper installation and maintenance for optimal performance.