100W Single Output with PFC Function
RSP-100 series
Dimension
L * W * H
179 * 99 * 30 mm
7.05 * 3.90 * 1.18 inch
R33100 AS/NZS62368-1 UL62368-1 BS EN/EN62368-1
RoHS BS EN/EN61558-1
CNS14336-1 BS EN/EN61558-2-16
GB4943.1 TPTC004 IEC62368-1
Features
- Universal AC input / Full range
- Built-in active PFC function
- High efficiency up to 88%
- Cooling by free air convection
- Built-in remote ON-OFF control
- Protections: Short circuit / Overload / Over voltage / Over temperature
- LED indicator for power on
- 3 years warranty
Applications
- Factory control or automation apparatus
- Test and measurement instrument
- Laser related machine
- Burn-in facility
- RF application
GTIN CODE
MW Search: https://www.meanwell.com/serviceGTIN.aspx
Description
RSP-100 is a 100W single output enclosed type AC/DC power supply. This series operates for 85~264VAC input voltage and offers the models with the DC output mostly demanded from the industry. Each model is cooled by free air convection, working for the temperature up to 70°C.
Model Encoding / Order Information
- Output voltage (3.3V/5V/7.5V/12V/13.5V/15V/24V/27V/48V)
- Output wattage
- Series name
SPECIFICATION
MODEL | RSP-100-3.3 | RSP-100-5 | RSP-100-7.5 | |
OUTPUT | DC VOLTAGE | 3.3V | 5V | 7.5V |
RATED CURRENT | 20A | 20A | 13.5A | |
CURRENT RANGE | 0 ~ 20A | 0 ~ 20A | 0 ~ 13.5A | |
RATED POWER | 66W | 100W | 101.25W | |
RIPPLE & NOISE (max.) Note.2 | 100mVp-p | 100mVp-p | 100mVp-p | |
VOLTAGE ADJ. RANGE | 3.14 ~ 3.63V | 4.75 ~ 5.5V | 7.13 ~ 8.25V | |
VOLTAGE TOLERANCE Note.3 | ±2.0% | ±2.0% | ±2.0% | |
LINE REGULATION | ±0.5% | ±0.5% | ±0.5% | |
LOAD REGULATION | ±1.0% | ±1.0% | ±1.0% | |
SETUP, RISE TIME | 600ms, 30ms at full load | |||
HOLD UP TIME (Typ.) | 16ms at full load | |||
INPUT | VOLTAGE RANGE | 85 ~ 264VAC 120 ~ 370VDC | ||
FREQUENCY RANGE | 47 ~ 63Hz | |||
POWER FACTOR (Typ.) | PF>0.93/230VAC PF>0.98/115VAC at full load | |||
EFFICIENCY (Typ.) | 83% | 86% | 87% | |
AC CURRENT (Typ.) | 1.1A/115VAC 0.55A/230VAC | |||
INRUSH CURRENT (Typ.) | COLD START 30A/230VAC | |||
LEAKAGE CURRENT | <2mA / 240VAC | |||
PROTECTION | OVERLOAD | 105 ~ 135% rated output power | ||
Protection type : Constant current limiting, recovers automatically after fault condition is removed | ||||
OVER VOLTAGE | 3.63 ~ 4.46V | 5.5 ~ 6.75V | 8.25 ~ 10.13V | |
Protection type : Shut down o/p voltage, re-power on to recover | ||||
OVER TEMPERATURE | Shut down o/p voltage, recovers automatically after temperature goes down | |||
FUNCTION | REMOTE CONTROL | CN1: < 0~0.8VDC POWER ON , 4~10VDC POWER OFF | ||
ENVIRONMENT | WORKING TEMP. | -30 ~ +70°C (Refer to “Derating Curve”) | ||
WORKING HUMIDITY | 20 ~ 90% RH non-condensing | |||
STORAGE TEMP., HUMIDITY | -40 ~ +85°C, 10 ~ 95% RH non-condensing | |||
TEMP. COEFFICIENT | ±0.05%/°C (0 ~ 50°C) | |||
VIBRATION | 10 ~ 500Hz, 2G 10min./1cycle, 60min. each along X, Y, Z axes | |||
OVER VOLTAGE CATEGORY | III; According to EN61558, EN50178,EN60664-1, EN62477-1; altitude up to 2000 meters | |||
SAFETY & EMC (Note 4) | SAFETY STANDARDS | UL62368-1, TUV BS EN/EN62368-1, BS EN/EN61558-1, BS EN/EN61558-2-16, EAC TP TC 004, CCC GB4943.1, BSMI CNS14336-1 approved, Design refer to AS/NZS 62368.1 | ||
WITHSTAND VOLTAGE | I/P-O/P:4KVAC I/P-FG:2KVAC O/P-FG:0.5KVAC | |||
ISOLATION RESISTANCE | I/P-O/P, I/P-FG, O/P-FG:100M Ohms / 500VDC / 25°C/ 70% RH | |||
EMC EMISSION | Compliance to BS EN/EN55032 (CISPR32) Class B, BS EN/EN61000-3-2,-3, EAC TP TC 020, CNS13438, GB9254 Class B, GB17625.1 | |||
EMC IMMUNITY | Compliance to BS EN/EN61000-4-2,3,4,5,6,8,11, BS EN/EN55035, light industry level, EAC TP TC 020 | |||
OTHERS | MTBF | 2325.2K hrs min. Telcordia SR-332 (Bellcore) ; 288.5K hrs min. MIL-HDBK-217F (25°C) | ||
DIMENSION | 179*99*30mm (L*W*H) | |||
PACKING | 0.52Kg; 24pcs/14.5Kg/0.81CUFT | |||
NOTE |
|
MODEL | RSP-100-12 | RSP-100-13.5 | RSP-100-15 | |
OUTPUT | DC VOLTAGE | 12V | 13.5V | 15V |
RATED CURRENT | 8.5A | 7.5A | 6.7A | |
CURRENT RANGE | 0 ~ 8.5A | 0 ~ 7.5A | 0 ~ 6.7A | |
RATED POWER | 102W | 101.25W | 100.5W | |
RIPPLE & NOISE (max.) Note.2 | 100mVp-p | 100mVp-p | 100mVp-p | |
VOLTAGE ADJ. RANGE | 11.4 ~ 13.2V | 12.8 ~ 14.9V | 14.3 ~ 16.5V | |
VOLTAGE TOLERANCE Note.3 | ±1.0% | ±1.0% | ±1.0% | |
LINE REGULATION | ±0.5% | ±0.5% | ±0.5% | |
LOAD REGULATION | ±0.5% | ±0.5% | ±0.5% | |
SETUP, RISE TIME | 600ms, 30ms at full load | |||
HOLD UP TIME (Typ.) | 16ms at full load | |||
INPUT | VOLTAGE RANGE | 85 ~ 264VAC 120 ~ 370VDC | ||
FREQUENCY RANGE | 47 ~ 63Hz | |||
POWER FACTOR (Typ.) | PF>0.93/230VAC PF>0.98/115VAC at full load | |||
EFFICIENCY (Typ.) | 86% | 86.5% | 87% | |
AC CURRENT (Typ.) | 1.1A/115VAC 0.55A/230VAC | |||
INRUSH CURRENT (Typ.) | COLD START 30A/230VAC | |||
LEAKAGE CURRENT | <2mA / 240VAC | |||
PROTECTION | OVERLOAD | 105 ~ 135% rated output power | ||
Protection type : Constant current limiting, recovers automatically after fault condition is removed | ||||
OVER VOLTAGE | 13.2 ~ 16.2V | 14.85 ~ 18.23V | 16.5 ~ 20.25V | |
Protection type : Shut down o/p voltage, re-power on to recover | ||||
OVER TEMPERATURE | Shut down o/p voltage, recovers automatically after temperature goes down | |||
FUNCTION | REMOTE CONTROL | CN1: < 0~0.8VDC POWER ON , 4~10VDC POWER OFF | ||
ENVIRONMENT | WORKING TEMP. | -30 ~ +70°C (Refer to “Derating Curve”) | ||
WORKING HUMIDITY | 20 ~ 90% RH non-condensing | |||
STORAGE TEMP., HUMIDITY | -40 ~ +85°C, 10 ~ 95% RH non-condensing | |||
TEMP. COEFFICIENT | ±0.05%/°C (0 ~ 50°C) | |||
VIBRATION | 10 ~ 500Hz, 2G 10min./1cycle, 60min. each along X, Y, Z axes | |||
OVER VOLTAGE CATEGORY | III; According to EN61558, EN50178,EN60664-1, EN62477-1; altitude up to 2000 meters | |||
SAFETY & EMC (Note 4) | SAFETY STANDARDS | UL62368-1, TUV BS EN/EN62368-1, BS EN/EN61558-1, BS EN/EN61558-2-16, EAC TP TC 004, CCC GB4943.1, BSMI CNS14336-1 approved, Design refer to AS/NZS 62368.1 | ||
WITHSTAND VOLTAGE | I/P-O/P:4KVAC I/P-FG:2KVAC O/P-FG:0.5KVAC | |||
ISOLATION RESISTANCE | I/P-O/P, I/P-FG, O/P-FG:100M Ohms / 500VDC / 25°C/ 70% RH | |||
EMC EMISSION | Compliance to BS EN/EN55032 (CISPR32) Class B, BS EN/EN61000-3-2,-3, EAC TP TC 020, CNS13438, GB9254 Class B, GB17625.1 | |||
EMC IMMUNITY | Compliance to BS EN/EN61000-4-2,3,4,5,6,8,11, BS EN/EN55035, light industry level, EAC TP TC 020 | |||
OTHERS | MTBF | 2325.2K hrs min. Telcordia SR-332 (Bellcore) ; 288.5K hrs min. MIL-HDBK-217F (25°C) | ||
DIMENSION | 179*99*30mm (L*W*H) | |||
PACKING | 0.52Kg; 24pcs/14.5Kg/0.81CUFT | |||
NOTE |
|
MODEL | RSP-100-24 | RSP-100-27 | RSP-100-48 | |
OUTPUT | DC VOLTAGE | 24V | 27V | 48V |
RATED CURRENT | 4.2A | 3.8A | 2.1A | |
CURRENT RANGE | 0 ~ 4.2A | 0 ~ 3.8A | 0 ~ 2.1A | |
RATED POWER | 100.8W | 102.6W | 100.8W | |
RIPPLE & NOISE (max.) Note.2 | 150mVp-p | 150mVp-p | 250mVp-p | |
VOLTAGE ADJ. RANGE | 22.8 ~ 26.4V | 25.7 ~ 29.7V | 45.6 ~ 52.8V | |
VOLTAGE TOLERANCE Note.3 | ±1.0% | ±1.0% | ±1.0% | |
LINE REGULATION | ±0.5% | ±0.5% | ±0.5% | |
LOAD REGULATION | ±0.5% | ±0.5% | ±0.5% | |
SETUP, RISE TIME | 600ms, 30ms at full load | |||
HOLD UP TIME (Typ.) | 16ms at full load | |||
INPUT | VOLTAGE RANGE | 85 ~ 264VAC 120 ~ 370VDC | ||
FREQUENCY RANGE | 47 ~ 63Hz | |||
POWER FACTOR (Typ.) | PF>0.93/230VAC PF>0.98/115VAC at full load | |||
EFFICIENCY (Typ.) | 87% | 87% | 88% | |
AC CURRENT (Typ.) | 1.1A/115VAC 0.55A/230VAC | |||
INRUSH CURRENT (Typ.) | COLD START 30A/230VAC | |||
LEAKAGE CURRENT | <2mA / 240VAC | |||
PROTECTION | OVERLOAD | 105 ~ 135% rated output power | ||
Protection type : Constant current limiting, recovers automatically after fault condition is removed | ||||
OVER VOLTAGE | 26.4 ~ 32.4V | 29.7 ~ 36.45V | 52.8 ~ 64.8V | |
Protection type : Shut down o/p voltage, re-power on to recover | ||||
OVER TEMPERATURE | Shut down o/p voltage, recovers automatically after temperature goes down | |||
FUNCTION | REMOTE CONTROL | CN1: < 0~0.8VDC POWER ON , 4~10VDC POWER OFF | ||
ENVIRONMENT | WORKING TEMP. | -30 ~ +70°C (Refer to “Derating Curve”) | ||
WORKING HUMIDITY | 20 ~ 90% RH non-condensing | |||
STORAGE TEMP., HUMIDITY | -40 ~ +85°C, 10 ~ 95% RH non-condensing | |||
TEMP. COEFFICIENT | ±0.05%/°C (0 ~ 50°C) | |||
VIBRATION | 10 ~ 500Hz, 2G 10min./1cycle, 60min. each along X, Y, Z axes | |||
OVER VOLTAGE CATEGORY | III; According to EN61558, EN50178,EN60664-1, EN62477-1; altitude up to 2000 meters | |||
SAFETY & EMC (Note 4) | SAFETY STANDARDS | UL62368-1, TUV BS EN/EN62368-1, BS EN/EN61558-1, BS EN/EN61558-2-16, EAC TP TC 004, CCC GB4943.1, BSMI CNS14336-1 approved, Design refer to AS/NZS 62368.1 | ||
WITHSTAND VOLTAGE | I/P-O/P:4KVAC I/P-FG:2KVAC O/P-FG:0.5KVAC | |||
ISOLATION RESISTANCE | I/P-O/P, I/P-FG, O/P-FG:100M Ohms / 500VDC / 25°C/ 70% RH | |||
EMC EMISSION | Compliance to BS EN/EN55032 (CISPR32) Class B, BS EN/EN61000-3-2,-3, EAC TP TC 020, CNS13438, GB9254 Class B, GB17625.1 | |||
EMC IMMUNITY | Compliance to BS EN/EN61000-4-2,3,4,5,6,8,11, BS EN/EN55035, light industry level, EAC TP TC 020 | |||
OTHERS | MTBF | 2325.2K hrs min. Telcordia SR-332 (Bellcore) ; 288.5K hrs min. MIL-HDBK-217F (25°C) | ||
DIMENSION | 179*99*30mm (L*W*H) | |||
PACKING | 0.52Kg; 24pcs/14.5Kg/0.81CUFT | |||
NOTE |
|
Mechanical Specification
Case No.227A Unit: mm
- 4-M4(Both Sides) L=4mm
Terminal Pin No. Assignment
Pin No. |
Assignment | Pin No. | Assignment |
1 | AC/L | 4,5 |
DC OUTPUT -V |
2 |
AC/N | 6,7 | DC OUTPUT +V |
3 | FG ![]() |
Remote ON/OFF(CN1): JST S2B-XH or equivalent(optional)
Pin No. |
Assignment | Mating Housing | Terminal |
1 | RC+ | JST XHP or equivalent |
JST SXH-001T-P0.6 or equivalent |
2 |
RC- |
Block Diagram
PFC fosc : 100KHz
PWM fosc : 100KHz
- EMI FILTER & RECTIFIERS
- PFC CIRCUIT
- POWER SWITCHING
- RECTIFIERS & FILTER
- ACTIVE START CIRCUIT
- PWM & PFC CONTROL
- CONSTANT CURRENT & DETECTION CIRCUIT
- REMOTE CONTROL
Derating Curve
Output Derating VS Input Voltage
File Name:RSP-100-SPEC 2024-02-23
Downloaded from Arrow.com.
Documents / Resources
![]() |
MEAN WELL RSP-100 Series 100W Single Output with PFC Function [pdf] Owner's Manual RSP-100-3.3, RSP-100-5, RSP-100-7.5, RSP-100-12, RSP-100-13.5, RSP-100-15, RSP-100-24, RSP-100-27, RSP-100-48, RSP-100 Series 100W Single Output with PFC Function, 100W Single Output with PFC Function, Single Output with PFC Function, Output with PFC Function, PFC Function, Function |
![]() |