KYORITSU-logo

KYORITSU KEW 6516,6516BT Multi Function Installation Tester

KYORITSU-KEW-6516-6516BT-Multi-Function-Installation-Tester-product

Specifications

  • Insulation Resistance Test Voltage: 100V, 250V, 500V, 1000V (Max. 1000V)
  • Measuring Ranges: 2.000/20.00/200.0M, 20.00/200.0/1000M, 20.00/200.0/2000M
  • Accuracy: Rated current 1.0 to 1.2mA, Short circuit current 1.5mA max.
  • Loop Impedance Function: LOOP ATT, LOOP HIGH, L-PE/L-N(3-wire), L-PE(2-wire), L-PE(0.01Res), L-PE(0.001Res), L-N/L-L
  • Rated Voltage: 100 to 260V (50/60Hz), 48 to 260V (50/60Hz), 48 to 500V (50/60Hz)
  • Impedance Range: 20.00/200.0/2000 (Auto-ranging)

Product Usage Instructions

Operation Steps

  1. Set the rotary dial to the desired testing range.
  2. Connect the instrument to the installation under test.
  3. Press the test button to begin testing.

Hands-Free Testing

  • Hands-free testing can be achieved by using a remote probe or utilizing the Lockdown function of the test button.

Anti-Trip Technology

  • The device features Anti-Trip Technology with 2 & 3 wires for no trip LOOP L-PE testing on all RCDs. Best accuracy readings are obtained with 3 wires (L, N, PE).

Loop Testing from a Wall Socket

  • With a high test current of 25A, the Loop Impedance Phase to Earth can be measured with a high resolution of 0.001 ohm, suitable for testing in the main switchboard closer to the transformer.

Continuity Check

  • The product allows for continuity check of equipotential bonding.

RCD Testing

  • A wide variety of RCDs can be tested including Type AC, A, F, B, EV, and Variable RCDs using different test modes like Single and Auto test, Ramp test, and Contact voltage.

SPD Test

  • The device can test Surge Protection Devices (SPD) containing varistors without causing damage by measuring the tripping voltage.

PAT Test

  • The PAT test functionality enables checking insulation resistance and earth bond continuity of portable appliances for class I and II.

Features

KYORITSU-KEW-6516-6516BT-Multi-Function-Installation-Tester-fig-27

Communication interface

USB

KYORITSU-KEW-6516-6516BT-Multi-Function-Installation-Tester-fig-1

Bluetooth

KYORITSU-KEW-6516-6516BT-Multi-Function-Installation-Tester-fig-2

Operation Instruction

Operation in 3 simple steps

KYORITSU-KEW-6516-6516BT-Multi-Function-Installation-Tester-fig-3

  • Set the rotary dial to your testing range.
  • Connect the instrument to the installation under test.
  • Press the test button.

Hands free testing

KYORITSU-KEW-6516-6516BT-Multi-Function-Installation-Tester-fig-4

By remote probe or using the Lockdown function of the test button.

Large LCD

KYORITSU-KEW-6516-6516BT-Multi-Function-Installation-Tester-fig-5

All the test data is shown in one large colored screen.

Anti-Trip Technology (with 2 & 3 wires)

  • KYORITSU-KEW-6516-6516BT-Multi-Function-Installation-Tester-fig-6For no trip LOOP L-PE testing on all RCDs.
  • With 3 wire (L, N, PE), to get the best accuracy readings.
  • With 2 wire only, very useful in case of no Neutral (i.e. 3-phase motor lines).

Loop test from a wall socket

KYORITSU-KEW-6516-6516BT-Multi-Function-Installation-Tester-fig-9

Continuity check of equipotential bonding

KYORITSU-KEW-6516-6516BT-Multi-Function-Installation-Tester-fig-10

HELP Key

KYORITSU-KEW-6516-6516BT-Multi-Function-Installation-Tester-fig-7

HELP function will show how to connect the instrument according to the function selected.

0.001 resolution

KYORITSU-KEW-6516-6516BT-Multi-Function-Installation-Tester-fig-8

Thanks to high test current of 25A, the Loop Impedance Phase to Earth is measured with high resolution of 0.001 ohm. This can be useful when testing in the main switchboard closer to the transformer.

Wide variety of RCDs can be tested

KYORITSU-KEW-6516-6516BT-Multi-Function-Installation-Tester-fig-11

Type AC, A, F, B (General & Selective) EV and Variable RCDs. Single and Auto test, Ramp test and Contact voltage.

SPD test

KYORITSU-KEW-6516-6516BT-Multi-Function-Installation-Tester-fig-12

SPD (Surge Protection Device) which contains varistor can be tested measuring the tripping voltage without damage it.

PAT test

KYORITSU-KEW-6516-6516BT-Multi-Function-Installation-Tester-fig-13PAT test (PAT = Portable Appliance Tester) It is possible to check the insulation resistance and earth bond continuity of portable appliances for class I and II.

Zs/Ra Limit

KYORITSU-KEW-6516-6516BT-Multi-Function-Installation-Tester-fig-14

The verification of safety requirement on an electrical installation is simplified by using Zs/Ra Limit function. This function will automatically check if the measured loop impedance for TN (or earth loop for TT) is low enough to trip (disconnect) the MCB / Fuse / RCD giving the result of PASS(V) or FAIL (x) on the display.

Connectivity

KYORITSU-KEW-6516-6516BT-Multi-Function-Installation-Tester-fig-15...

Accessories

KYORITSU-KEW-6516-6516BT-Multi-Function-Installation-Tester-fig-17

Optional accessories

MODEL7272

Precision measurement cord set

  • 2 cord reels with test leads.
  • 2 spikes.
  • an earth test lead.
  • a carrying case.

KYORITSU-KEW-6516-6516BT-Multi-Function-Installation-Tester-fig-18

Adapter for measurement terminal

  • [red, yellow, green/1set] KYORITSU-KEW-6516-6516BT-Multi-Function-Installation-Tester-fig-19

EVSE ADAPTEF

  • TYPE1 plugKYORITSU-KEW-6516-6516BT-Multi-Function-Installation-Tester-fig-20KYORITSU-KEW-6516-6516BT-Multi-Function-Installation-Tester-fig-22

EVSE ADAPTER

  • TYPE2 plugKYORITSU-KEW-6516-6516BT-Multi-Function-Installation-Tester-fig-21KYORITSU-KEW-6516-6516BT-Multi-Function-Installation-Tester-fig-23

MFT and EVSE ADAPTER Kits

  • KEW 6516-EV2: KEW 6516×1, KEW 8602×1
  • KEW 6516BT-EV2: KEW 6516BTx1, KEW 8602×1

Specification

MULTI FUNCTION TESTER KEW 6516 / 6516BT Specification

KYORITSU-KEW-6516-6516BT-Multi-Function-Installation-Tester-fig-26

*1 The following functions have been added to KEW 6516/6516BT main unit firmware version 2.10 or later.

*2 6516BT only Some countries regulate the compliance with their Radio Law of the products equipped with Bluetooth®.Please confirm it with your distributor before purchasing our products equipped with Bluetooth®.

*3 7187A:British plug, 7218A:(EU)European SCHUKO plug, 7221A(SA) South african plug, 7222A:(AU)Australian plug

Bluetooth® is a trademark or registered trademark of Bluetooth SIG. Inc.

Android is a trademark or registered trademark of Google LLC.

iOS is a trademark or registered trademark of Cisco Technology, Inc. in the United States and other countries.

KYORITSU-KEW-6516-6516BT-Multi-Function-Installation-Tester-fig-24Safety Warnings

Please read the “Safety Warnings” in the instruction manual supplied with the instrument thoroughly and completely for correct use. Failure to follow the safety rules can cause fire, trouble, electrical shock, etc. Therefore, make sure to operate the instrument on a correct power supply and voltage rating marked on each instrument.

For inquiries or orders

KYORITSU ELECTRICAL INSTRUMENTS WORKS, LTD.

2-5-20, Nakane, Meguro-ku, Tokyo, 152-0031 Japan

  • Phone: +81-3-3723-0131
  • Fax:+81-3-3723-0152

KYORITSU-KEW-6516-6516BT-Multi-Function-Installation-Tester-fig-25

www.kew-ltd.co.jp

FAQ

  • Q: What accessories are available for the KEW 6516 / 6516BT?
    • A: Optional accessories include Extension prod long (MODEL 8017A), Precision measurement cord set (MODEL7272), Adapter for measurement terminal [red, yellow, green/1set] (MODEL 8259), EVSE ADAPTER TYPE1 plug (KEW 8601), and EVSE ADAPTER TYPE2 plug (KEW 8602).

Documents / Resources

KYORITSU KEW 6516,6516BT Multi Function Installation Tester [pdf] Instruction Manual
6516, 6516BT, KEW 6516 6516BT Multi Function Installation Tester, KEW 6516 6516BT, Multi Function Installation Tester, Function Installation Tester, Installation Tester

References

Leave a comment

Your email address will not be published. Required fields are marked *