Ketotek Logo

KETOTEK Temperature Controller

Product

Overview

  • Wide range working voltage.
  • Support delay start and time shutdown.
  • Heating or cooling mode can be set.
  • All parameters setting can be saved after short circuit.
  • high Control precision 0.1 centigrade
  • Can be used for domestic freezer, water tanks, refrigerator, industrial chiller, steamer, industrial equipment and other temperature-controlled

Specification

  • Power Supply: AC90~250V 50/60HZ/ DC12V/ DC24V
  • Temperature control range:-50~110°C
  • Difference Set Value:0.1~30°C
  • Resolution Ratio:0.1°C(-9.9-99.9);1°C(other range)
  • Measurement accuracy: ±0.1°C
  • Control accuracy: 0.1°C
  • Measuring inputs: NTC (10K0.5%) Waterproof sensor
  • Output:RelayContactCapacity10A/220Vnormallyopen
  • Environmental requirements: -20 – 70°C, humidity 20% – 85% RH
  • Size: 75mm(L)*34mm (W)*85mm (Depth)
  • Hole size: 71(L)*29(W) mm
  • Power consumption: Static current: ≤35MA,attract current: ≤65MA

Wiring Diagram

Connection 1: Independent power supply for load.

Image 01

Connection 2: Same power supply for load.

Image 02

Key Instruction

S: Set key, Confirm the setting value, Entry and Set parameter. power on/off, or quit the setting.

Increase Value
Work: Output Indicator

Decrease Value
Set: Setting Indicator

Image 03

Key Operation Instruction

  • In normal working status, hold power button for 3 seconds to power off, hold same button for 3 seconds to power on.
  • In normal working status, press S. The led flash. Press UP or down to increase or decrease the setting temperature value. Press S to save it and back to normal screen.
  • In normal working status, press S for 3s to enter set mode.
  • Press UP + DOWN to switch from HC-A7. Press S to enter any code, press UP + DOWN to change code setting.
  • Both press UP + DOWN for 3 seconds to rest the controller.
Operation Instruction
  • In normal working status, the screen display RT (real time temperature value).
    • Cooling Mode: HC set to C. Use cooler as load. When RT≥ST (temperature set value)+ D (difference value), work indicator turn on. Output relay connect. Load start to work. When RT ≤ST, work indicator turn off, output relay disconnect, load stop working.
      For example, set10℃, difference 3℃, cooler work when RT≥13℃. Cooler stop when RT≤10℃.
    • Heating Mode: HC set to H, use heater as load. When RT≤ST-D, work indicator turn on. Output relay connect. load start to work. When RT≥ST, work indicator turn off, output relay disconnect, load stop working.
      For example, set 10 ℃, difference 3℃, heater work when RT≤7℃. Heater stop when RT≥10℃.

Code

Explain

Setting Range

Factory Setting

HC

Heating / Cooling

H/C

C

D

Return Difference

0.1-30

2.0

LS

Set Low Limit

-50

-50

HS

Set High Limit

+110

110

PU

Delay Start

0-90minute

0

CA

Temp Correction

-10-10

0.0

A7

Timing Stop Output

0-999minute

000

 

Ketotek Logo

Documents / Resources

KETOTEK Temperature Controller [pdf] User Manual
KETOTEK, KT1210W, Temperature Controller

References

Leave a comment

Your email address will not be published. Required fields are marked *