KETOTEK Temperature Controller

Overview
- Wide range working voltage.
- Support delay start and time shutdown.
- Heating or cooling mode can be set.
- All parameters setting can be saved after short circuit.
- high Control precision 0.1 centigrade
- Can be used for domestic freezer, water tanks, refrigerator, industrial chiller, steamer, industrial equipment and other temperature-controlled
Specification
- Power Supply: AC90~250V 50/60HZ/ DC12V/ DC24V
- Temperature control range:-50~110°C
- Difference Set Value:0.1~30°C
- Resolution Ratio:0.1°C(-9.9-99.9);1°C(other range)
- Measurement accuracy: ±0.1°C
- Control accuracy: 0.1°C
- Measuring inputs: NTC (10K0.5%) Waterproof sensor
- Output:RelayContactCapacity10A/220Vnormallyopen
- Environmental requirements: -20 – 70°C, humidity 20% – 85% RH
- Size: 75mm(L)*34mm (W)*85mm (Depth)
- Hole size: 71(L)*29(W) mm
- Power consumption: Static current: ≤35MA,attract current: ≤65MA
Wiring Diagram
Connection 1: Independent power supply for load.

Connection 2: Same power supply for load.

Key Instruction
S: Set key, Confirm the setting value, Entry and Set parameter. power on/off, or quit the setting.
Increase Value
Work: Output Indicator
Decrease Value
Set: Setting Indicator

Key Operation Instruction
- In normal working status, hold power button for 3 seconds to power off, hold same button for 3 seconds to power on.
- In normal working status, press S. The led flash. Press UP or down to increase or decrease the setting temperature value. Press S to save it and back to normal screen.
- In normal working status, press S for 3s to enter set mode.
- Press UP + DOWN to switch from HC-A7. Press S to enter any code, press UP + DOWN to change code setting.
- Both press UP + DOWN for 3 seconds to rest the controller.
Operation Instruction
- In normal working status, the screen display RT (real time temperature value).
- Cooling Mode: HC set to C. Use cooler as load. When RT≥ST (temperature set value)+ D (difference value), work indicator turn on. Output relay connect. Load start to work. When RT ≤ST, work indicator turn off, output relay disconnect, load stop working.
For example, set10℃, difference 3℃, cooler work when RT≥13℃. Cooler stop when RT≤10℃. - Heating Mode: HC set to H, use heater as load. When RT≤ST-D, work indicator turn on. Output relay connect. load start to work. When RT≥ST, work indicator turn off, output relay disconnect, load stop working.
For example, set 10 ℃, difference 3℃, heater work when RT≤7℃. Heater stop when RT≥10℃.
- Cooling Mode: HC set to C. Use cooler as load. When RT≥ST (temperature set value)+ D (difference value), work indicator turn on. Output relay connect. Load start to work. When RT ≤ST, work indicator turn off, output relay disconnect, load stop working.
|
Code |
Explain |
Setting Range |
Factory Setting |
|
HC |
Heating / Cooling |
H/C |
C |
|
D |
Return Difference |
0.1-30 |
2.0 |
|
LS |
Set Low Limit |
-50 |
-50 |
|
HS |
Set High Limit |
+110 |
110 |
|
PU |
Delay Start |
0-90minute |
0 |
|
CA |
Temp Correction |
-10-10 |
0.0 |
|
A7 |
Timing Stop Output |
0-999minute |
000 |

Documents / Resources
![]() | Temperature Controller |
References
- User Manualmanual.tools

I am looking for a clear Dutch description of the KETOTEK
temperature control manual
colour White
with below the display
mode_set_reset_up_down and above the reset the blue light
ik zoek een duidelijke Nederlandse beschrijving van de KETOTEK
themperatuur control manuel
kleur wit
met onder het display
mode_set_reset_up_down en boven de reset het blauwe lampje
temperature control manual
colour White
with below the display
mode_set_reset_up_down and above the reset the blue light<e/em>
ik zoek een duidelijke Nederlandse beschrijving van de KETOTEK
themperatuur control manuel
kleur wit
met onder het display
mode_set_reset_up_down en boven de reset het blauwe lampje
Where can I find a Dutch manual for the KETOTEK KT1210W temperature controller with Mode, Set, Reset, Up, and Down buttons?
Based on your description of the buttons (Set, Power/Reset, Up, Down) and the blue indicator light, you are likely using the KETOTEK KT1210W. While the official manual provided is in English, here is a summary of the instructions in Dutch to assist you:
Belangrijke menu-codes:
HC: Instellen op 'H' voor verwarmen of 'C' voor koelen.
D: Verschilwaarde (Hysteresis). Bepaalt wanneer het apparaat weer inschakelt.
Helaas is er op dit moment geen volledige officiële PDF in het Nederlands beschikbaar op deze pagina, maar u kunt de browser-vertaalfunctie van Google Chrome gebruiken om de tekst op deze pagina direct naar het Nederlands te vertalen.
Read the full Q&A page
Cannot find user manual for KT 3100
Går inte att hitta bruksanvisning till KT 3100
Går inte att hitta bruksanvisning till KT 3100
Where can I find the user manual for the KETOTEK KT3100 temperature controller?
While the manual currently displayed on this page is for the KT1210W, the KT3100 is a plug-and-play digital temperature controller often used for heating and cooling applications. If you are looking for the PDF or specific instructions for the KT3100, you can try the following:
Please note that the KT1210W manual provided in the context has different wiring and menu codes (HC, D, LS, HS) than the KT3100 plug-in model.
Read the full Q&A page
M.,/M., can I also receive a clear instruction manual from you for the ketotek temperature controller?
M.,/M., kan ik ook een duidelijke gebruiksaanwijzing van u ontvangen voor de ketotek temperatuurregelaar?
M.,/M., kan ik ook een duidelijke gebruiksaanwijzing van u ontvangen voor de ketotek temperatuurregelaar?
Where can I find a clear instruction manual for the KETOTEK KT1210W temperature controller?
You can find the operating instructions for the KETOTEK KT1210W Temperature Controller below. Key operations include:
For a full visual guide, you can refer to the manual image provided on this page or use the /deep-search feature on Manuals+ to find a downloadable PDF version.
Read the full Q&A page
meu medidor está medindo
LLL. o que pode ser?
LLL. o que pode ser?
What does the LLL error code mean on my KETOTEK temperature controller?
On KETOTEK temperature controllers like the KT1210W, the LLL error code typically indicates a problem with the temperature sensor (NTC probe). This usually means the sensor is not detected or there is a circuit failure.
Please check the following:
Read the full Q&A page