GEYA GRT8-At-Bt Single Function Time Relay
General
- Applications
- Suitable for applications where function and time requirements are know.
- Time switch , possible to be used for pump decay time after switching heating off , switching of fans.
- Function Features
- Single-function relay with possibility of time setting by a potentiometer.
- Choice of 2 functions:
A:Delay ON
B:Delay OFF - Time scale 0.1 s – 10 days divided into 10 ranges..
- Relay status is indicated by LED.
- 1-MODULE,DIN rail mounting.
- Model and connotation
Technical parameters
Technical parameters | GRT8-A1/B1 | GRT8-A2/B2 | GRT8-At/Bt |
Function | A:delay ON;B:delay OFF | ||
Supply terminals | A1-A2 | ||
Voltage range | W240 | AC/DC 12-240V(50-60Hz) | |
Burden | AC 0.09-3VA/DC 0.05-1.7W | ||
Voltage range | A230 | AC 230V(50-60Hz) | |
Power input | AC max.6VA/1.3W | AC max.6VA/1.9W | |
Supply voltage tolerance | -15%;+10% | ||
Supply indication | green LED | ||
Time ranges | 0.1s-10days,ON,OFF | ||
Time setting | potentionmeter | ||
Time deviation | 10%-mechanical setting | ||
Repeat accuracy | 0.2%-set value stability | ||
Temperature coecient | 0.05%/℃,at=20℃(0.05%℉,at=68℉) | ||
Output | 1×SPDT | 2×SPDT | 1×SPDT(del)+1×SPDT(ins) |
Current rating | 16A/AC1 | ||
Switching voltage | 250VAC/24VDC | ||
Min.breaking capacity DC | 500mW | ||
Output indication | red LED | ||
Mechanical life | 1×10 (7) | ||
Electrical life(AC1) | 1×10 (5) | ||
Reset time | max.200ms | ||
Operating temperature | -20℃ to +55℃(-4℉ to 131℉) | ||
Storage temperature | -35℃ to +75℃(-22℉ to 158℉) | ||
Mounting/DIN rail | Din rail EN/IEC 60715 | ||
Protection degree | IP40 for front panel/IP20 terminals | ||
Operating position | any | ||
Overvoltage cathegory | III. | ||
Pollution degree | 2 | ||
Max.cable size(mm²) | solid wire max.1×2.5or 2×1.5/with sleeve max.1×2.5(AWG 12) | ||
Tightening torque | 0.4Nm | ||
Dimensions | 90×18×64mm | ||
Weight | W240-61g,A230-61g | W240-81g,A230-80g | |
Standards | EN 61812-1,IEC60947-5-1 |
Panel Diagram
Wiring Diagram
Functions Diagram
Time Setting
|
Knob 1: delay gear setting, “s” for second, “m” for minute, “h” for hour, “d” for day, “ON” for relay action (15-18/25-28 closed), “OFF” for relay open (15-18/25-28 open). |
|
Knob 2: fine adjustment of delay time, 10% ~ 100% adjustable. |
Delay time = knob 1 × knob 2. Example 1: it needs to be set for 5 seconds. You can set knob 1 to 10s, knob 2 to 50%, and delay time = 10s × 50% = 5s. Example 2: it needs to be set for 8 minutes. You can set knob 1 to 10m, knob 2 to 80%, and delay time = 10m × 80% = 8m. |
Dimensions(mm)
Disposal of Electrical Waste
All electrical waste should be disposed of in compliance with current WEEE regulations.
Caution
The products must be installed by qualified electricians. All and any electrical connections of the product shall comply with the appropriate safety standards.
GEYA ELECTRICAL CO.,LTD
Add:Wenzhou Brige Industrial Zone,Beibaixiang Town, Yueqing,Zhejiang,China 325603
Tel:0086-577-62771036
Fax:0086-577-62711079
E-mail: sale@cnyeya.com
Web: www.geya.net
Documents / Resources
![]() |
GEYA GRT8-At-Bt Single Function Time Relay [pdf] Instruction Manual GRT8-A1-B1, GRT8-A2-B2, GRT8-At-Bt, GRT8-At-Bt Single Function Time Relay, GRT8-At-Bt, Single Function Time Relay, Function Time Relay, Time Relay, Relay |