GEYA GRT8-At-Bt Single Function Time Relay
GEYA GRT8-At-Bt Single Function Time Relay

General

  • Applications
    • Suitable for applications where function and time requirements are know.
    • Time switch , possible to be used for pump decay time after switching heating off , switching of fans.
  • Function Features
    • Single-function relay with possibility of time setting by a potentiometer.
    • Choice of 2 functions:
      A:Delay ON
      B:Delay OFF
    • Time scale 0.1 s – 10 days divided into 10 ranges..
    • Relay status is indicated by LED.
    • 1-MODULE,DIN rail mounting.
  • Model and connotation

General

Technical parameters

Technical parametersGRT8-A1/B1GRT8-A2/B2GRT8-At/Bt
FunctionA:delay ON;B:delay OFF
Supply terminalsA1-A2
Voltage rangeW240AC/DC 12-240V(50-60Hz)
BurdenAC 0.09-3VA/DC 0.05-1.7W
Voltage rangeA230AC 230V(50-60Hz)
Power inputAC max.6VA/1.3WAC max.6VA/1.9W
Supply voltage tolerance-15%;+10%
Supply indicationgreen LED
Time ranges0.1s-10days,ON,OFF
Time settingpotentionmeter
Time deviation10%-mechanical setting
Repeat accuracy0.2%-set value stability
Temperature coecient0.05%/℃,at=20℃(0.05%℉,at=68℉)
Output1×SPDT2×SPDT1×SPDT(del)+1×SPDT(ins)
Current rating16A/AC1
Switching voltage250VAC/24VDC
Min.breaking capacity DC500mW
Output indicationred LED
Mechanical life1×10 (7)
Electrical life(AC1)1×10 (5)
Reset timemax.200ms
Operating temperature-20℃ to +55℃(-4℉ to 131℉)
Storage temperature-35℃ to +75℃(-22℉ to 158℉)
Mounting/DIN railDin rail EN/IEC 60715
Protection degreeIP40 for front panel/IP20 terminals
Operating positionany
Overvoltage cathegoryIII.
Pollution degree2
Max.cable size(mm²)solid wire max.1×2.5or 2×1.5/with sleeve max.1×2.5(AWG 12)
Tightening torque0.4Nm
Dimensions90×18×64mm
WeightW240-61g,A230-61gW240-81g,A230-80g
StandardsEN 61812-1,IEC60947-5-1

Panel Diagram

Panel Diagram

Wiring Diagram

Wiring Diagram

Functions Diagram

Functions Diagram

Time Setting

Time Setting

Knob 1: delay gear setting, “s” for second, “m” for minute, “h” for hour, “d” for day, “ON” for relay action (15-18/25-28 closed), “OFF” for relay open (15-18/25-28 open).

Time Setting

Knob 2: fine adjustment of delay time, 10% ~ 100% adjustable.
Delay time = knob 1 × knob 2.
Example 1: it needs to be set for 5 seconds. You can set knob 1 to 10s, knob 2 to 50%, and delay time = 10s × 50% = 5s.
Example 2: it needs to be set for 8 minutes. You can set knob 1 to 10m, knob 2 to 80%, and delay time = 10m × 80% = 8m.

Dimensions(mm)

Dimensions

Symbols Disposal of Electrical Waste
All electrical waste should be disposed of in compliance with current WEEE regulations.

Symbols Caution
The products must be installed by qualified electricians. All and any electrical connections of the product shall comply with the appropriate safety standards.

http://www.geya.net

GEYA ELECTRICAL CO.,LTD

Add:Wenzhou Brige Industrial Zone,Beibaixiang Town, Yueqing,Zhejiang,China 325603

Tel:0086-577-62771036
Fax:0086-577-62711079
E-mail: sale@cnyeya.com
Web: www.geya.net

Company Logo

Documents / Resources

GEYA GRT8-At-Bt Single Function Time Relay [pdf] Instruction Manual
GRT8-A1-B1, GRT8-A2-B2, GRT8-At-Bt, GRT8-At-Bt Single Function Time Relay, GRT8-At-Bt, Single Function Time Relay, Function Time Relay, Time Relay, Relay

References

Leave a comment

Your email address will not be published. Required fields are marked *