Elimko E72P Universal Process Controllers User Guide

E72P Universal Process Controllers

Product Information

Specifications

  • Product Name: E-72P Series Universal Advanced Controller
  • Dimensions: 72×72 mm
  • Inputs: T/C, R/T, mV, mA
  • Outputs: Relay, SSR, Analog (mA and V)
  • Operating Voltage: 85-265 V AC / 85-375 V DC
  • Communication: RS-485

Product Usage Instructions

1. Unboxing and Inspection

Upon receiving the package, check that it contains the
controller, mounting clamps, user manual, and guarantee
certificate. Contact the vendor if any items are missing or there
are visible defects.

2. Installation

Install the controller in a panel in an industrial environment.
Ensure that the installation and configuration are done by a
qualified person in instrumentation.

3. Cleaning and Maintenance

Avoid using alcohol or solvents to clean the controller. Use a
clean cloth soaked in water to gently wipe the outer surface. Keep
the unit away from flammable gases.

4. Display and Programming

The controller features two 4-digit displays that can show set
and measured values. Inputs can be easily programmed for different
control forms.

Frequently Asked Questions (FAQ)

Q: What are the dimensions of the E-72P Series controller?

A: The controller dimensions are 72×72 mm.

Q: What inputs are supported by the controller?

A: The controller supports inputs such as T/C, R/T, mV, mA.

Q: How should I clean the controller?

A: Use a clean cloth soaked in water to gently wipe the outer
surface of the controller. Avoid using alcohol or solvents.

“`

KY-72P-0825-1

4. WARNINGS

E-72P Series
200.0 R1 Universal Advanced R2 Digital Controllers 200.0 PR MN Quick Start Guide

Elimko

Manufacturer / Technical Support

SET

Elimko Elektronik malat ve Kontrol Ltd. ti.

8. Cadde 21. Sokak No:16 Emek 06510 Ankara / TÜRKYE

72P

Telefon: + 90 312 212 64 50 Faks: + 90 312 212 41 43

www.elimko.com.tr · e-mail:elimko@elimko.com.tr

1. DESCRIPTION
E-72P Series universal process controllers are industrial devices at 72×72 mm IEC/TR 60668 dimensions designed using new generation microcontrollers with on/off, PID and other control forms, where inputs and outputs can be easily programmed by the user.

E-72P controller is designed for panel mounting and should be used in an industrial environment.
m The package of E-72P controller contans; Controller, 2 peces of mountng clamps, User manual and Guarantee certfcate.
m After openng the package, please check the contents wth the above lst. If the delvered product s wrong type, any tem s mssng or there are vsble defects, contact the vendor from whch you purchased the product.
m Before nstallng and operatng the controller, please read the user manual thoroughly.
m The nstallaton and confguraton of the controller must only be performed by a person qualfed n nstrumentaton.
m Keep the unt away from flamable gases, that could cause exploson.
m Do not use alcohol or other solvents to clean the controller. Use a clean cloth soaked n water tghtly squeezed to gently wpe the outer surface of the controller.
m It s not used n medcal applcatons.

EU DIRECTIVE COMPLIANCE
Low Voltage Drectve EN 61010-1 EMC Drectve EN 61326-1

K – Q TSE-ISO-EN
9000
TS EN ISO 9001 Quality Management System Certificate

In E-72P Series controllers, the set value and measured value can be displayed from -1999 to 9999 on two 4-digit displays; general purpose inputs (T/C, R/T, mV, mA) can be programmed.

5. TYPE CODING

2. DIMENSIONS and PANEL CUT-OUT

200.0 R1 R2 200.0 PR MN

Elimko

SET
72P

Elimko
Kontrol Edilmitir
2

TP

: E72P

SKALA :

GR :

ÇIKI :

SER NO : 22/10391

Elimko
Tel: +90 3122126450 Fax: +90 3122124143
TÜRKYE

-0.0 68 x 68 mm
+0.5 10 mm min.

35 mm min.

Panel Cut-Out and Minimum Spacing

3. CONNECTION DIAGRAM

E-72P Series Universal Advanced Controller

E-72P – W – X – Y – Z

Relay Outputs

None

0

1 relay (RL1)

1

2 relays (RL1, RL2)

2

1 SSR (SSR1)

3

1 SSR (SSR1) + 1 relay (RL2)

4

2 SSR (SSR1, SSR2)

5

Analog Outputs *

None

0

1 x 0-20 / 4-20 mA (AO1)

1

2 x 0-20 / 4-20 mA (AO1, AO2) *

2

1 x 0-10 V DC (AO1)

3

2 x 0-10 V DC (AO1, AO2) *

4

1 x 0-20 / 4-20 mA (AO1) + 1 x 0-10 V DC (AO2)

5

Communication

None

0

RS-485 **

1

Operating Voltage

85-265 V AC / 85-375 V DC

0

20-60 V AC / 20-60 V DC

1

* Analog outputs are isolated from each other. ** When E-72P Series devices are ordered with communication, the E-IB-11 USB-RS485 converter can be used for PC connection. There are various control and monitoring software provided by Elimko.

RL1

15

1

8

6. TECHNICAL SPECIFICATIONS

Analog Outputs AO1

SSR1 AO2

Relay and SSR Outputs

Thermocouple / miliVolt 0-20 mA / 4-20 mA
Resistance Thermometer 2-Wire Transmitter Volt

Operating voltage suitable for the device type shall be applied.

2 RL2
3 4
5
6
7

Power Supply SSR2
RS-485 GND TRX + TRX –

9

16

10

17

Analog Inputs

11

18

12

19

13

20

14

21

1st and 2nd control outputs can be selected as either Relay (RL1, RL2) or SSR (SSR1, SSR2).
Analog output (AO1, AO2) mA or 0-10 V DC can be selected.

Analog Input

17

17

18

18

19

19

20

20

21

21

17

17

18

18

19

19

20

20

21

21

17

18

19

20

V

21

Parameter

Description

Control Type

On/Off, PID, Heat/Cool, Floating and Feedback Control of Valves

Operating Voltage

20..60 V AC / 20..60 V DC or 85..265 V AC / 85..375 V DC

Relays / SSR

2 pieces SPST – NO 250 V AC 5A relays or 24 V DC 25 mA (SSR) drives

Dimensions (mm)

72 (Lenght) x 72 (Height) x 100 (Width)

Panel Cut-Out (mm)

68 (Lenght) x 68 (Height)

Analog Output

2 x 0..20 / 4..20 mA (Max. Load 600 Ohm) or 0..10 V DC optional

Analog Input

Universal (Note 1),

Communication (RS-485) Available (RS-485)

Digital Input

Available (optional)

Valve Feedback

None

Transmitter Supply

Available

Weight

232 g

Power Consumption Max. 7 W (10 VA)

Operating Temperature – 10 °C … 55 °C

Storage Temperature – 25 °C … 65 °C

Memory

Maks. 100.000 write

Protection Class

IP-65 Front Panel, IP-20 Rear Case

Notes:

(1) Universal Input :

Thermocouple

: B, E, J, K, L, N, R, S, T, U

Resistance Thermometer : Pt-100

Current

: 0-20 mA, 4-20 mA (Linear)

Voltage

: 0-50 mV, 0-1 V, 0.2- 1 V (Linear),

0-10 V DC, must be specified in the order.

Resolution

: 16 bit

Accuracy

: Thermocouple, Max. ±1.0 °C (Conversion and CJC error)

Resistance Thermometer, Max. ±0.5 °C

(Conversion and wire resistance compensation)

Linear Input, Max. % 0.1

ALARM SETTINGS
ACNF

CONTROL SET SETTINGS
SETP

INPUT SETTINGS
gcnf

7. PARAMETER TABLE
Description INP1 Analog Input 1 Type
DP Decimal Point SCLO Analog Input 1 Linear Scale Lower Value SCHI Analog Input 1 Linear Scale Upper Value UNIT Temperature Unit OFST Analog Input 1 Offset Value FLTR Analog Input 1 Filter SNBR Analog Input 1 Sensor Broken Behaviour ADRS Modbus Adress BAUD Modbus Baud Rate [4.8, 9.6, 19.2, 38.4 kbaud] PRTY Modbus Parity [None, ODD, Even] SPSR Control Set Point Source SPLL Control Set Point Lower Limit SPHL Control Set Point Upper Limit SPRR Control Set Point Ramping Rate S-1 1. Step Set Value T-1 1. Step Time S-2 2. Step Set Value T-2 2. Step Time S-3 3. Step Set Value T-3 3. Step Time
A1TP Alarm 1 Type A1SP Alarm 1 Set Point A1HY Alarm 1 Hysteresis A1LT Alarm 1 Lock A2TP Alarm 2 Type A2SP Alarm 2 Set Point A2HY Alarm 2 Hysteresis A2LT Alarm 2 Lock

Min Maks Unit

Table 1

0

3

-199.9 999.9 EU

-199.9 999.9 EU

*C *F

-100.0 100.0 EU 1 15 s

LO HI

1 127

4.8 38.4

Table 2 -199.9 SPHL EU SPLL 999.9 EU
OFF 60.0 EU/min SPLL SPHL EU
OFF 999.9 min SPLL SPHL EU
OFF 999.9 min SPLL SPHL EU
OFF 999.9 min
Table 3 -199.9 999.9 EU
0.0 999.9 EU DSB ENB
Table 3 -199.9 999.9 EU
0.0 999.9 EU DSB ENB

8. ACCESSING PARAMETERS

STEP 1:

STEP 2:

Security Code Configuration

Entry Page Selection

(Default: 10) and Entry

STEP 3: Parameter Selection and Configuration

Process Screen
199.8 200.0

Selected Page

12 12

43 SCOD

3 PAGE

3 3 Parameters . . .

0

GCNF

4

4

4

Adjustment
12
Enter
3
Return
4
Menu Access
43

9. APPLICATION EXAMPLES
1) Input: Pt-100 Relay / Alarm1: 50 °C Low, Relay2 / Alarm2: 55 °C High AO1: 4-20 mA PID Control Output inp1 a1tp a1sp a2tp a2sp ctyp rl1D rl2D ao1D ao1r pt lo 50.0 hi 55.0 sco al-1 al-2 co-1 4-20
2) Input: TC Type J, Relay1: On-Off Control Output, Relay2 / Alarm2: 350 °C High inp1 a2tp a2sp ctyp rl1D rl2D
j hi 350.0 sco Do-1 al-2
3) Input: TC Type K, Profile Control (Ramp up to 400°C in 10 minutes and wait for 60 minutes), Relay1: PID Control Output, AO1: Retransmission Output (4-20 mA, 0-1200 °C)
inp1 spsr s-1 t-1 s-2 t-2 ctyp trll trhl rl1D rl2D ao1D ao1r k prfl 400 10.0 400 60.0 sco 0 1200 co-1 al-2 pvtr 4-20

OUTPUTS
OCNF

CTYP CFRM CPRD MNPR TRTM DBND OLL OHL OMR PONC TRLL TRHL RL1D RL2D AO1D AO1R AO2D AO2R

Control Type Control Form [DIR, REV] Control Period Manual Mode Selection Floating Control Valve Travel Time Dead Band Control Output Lower Limit Control Output Upper Limit Control Output Manual Reset PID Power On Behaviour Retransmission Scale Lower Value Retransmission Scale Upper Value
Relay 1 Function Relay 2 Function Analog Output 1 Function Analog Output 1 Type Analog Output 2 Function Analog Output 2 Type

AT PID PB-1 PB-2 ITH ITC DTH DTC HYS

PID Auto Tune PID Parameter Type
Proportional Band + Proportional Band Integral Time + Integral Time Derivative Time + Derivative Time Hysteresis

SCOD DPRL APRL FCST

Security Code Parameter Access Level Parameter Setting Level Factory Settings [OFF, LOAD, SAVE, DFLT]

Table 4

DIR REV

1 250 s

DSB ENB

10 2500 s

0.1 25.0 %

0.0 OHL %

OLL 100.0 %

OLL OHL %

0

4

-199.9 TRHL EU

TRLL 999.9 EU

Table 5

Table 5

Table 6

Table 7.1 ve Table 7.2

Table 6

Table 7.1 ve Table 7.2

OFF ON
STD ADV
0.1 999.9 EU 0.1 999.9 EU OFF 9999 s OFF 9999 s OFF 2500 s OFF 2500 s 0.0 999.9 EU

0 9999

0

9

0

9

Table 1. Input Type Options b Type B Thermocouple e Type E Thermocouple j Type J Thermocouple k Type K Thermocouple l Type L Thermocouple

n Type N Thermocouple

r Type R Thermocouple s Type S Thermocouple

t u pt 0-20

Type T Thermocouple Type U Thermocouple Pt-100 0-20 mA

4-20 4-20 mA 0-50 0-50 mV

0.0-1 0-1 V 0.2-1 0.2-1 V

0-10 0-10 V (*)

2-10 2-10 V (*)

(*) Custom specified volt input

Table 2. Control Set Options int Internal adjustment with
keys prfl With Profile Control

Table 3. Alarm Options off Off lo Low Alarm hi High Alarm loD Low Deviation hiD High Deviation lob Band Alarm (In) hib Band Alarm (Out)

Table 4. Control Type Options off No Control sco Single (Heat) Dco Double (Heat/Cool) bnD Floating Control of Valve
Tablo 5. Relay Output Options co-1 PID + (Heating) co-2 PID – (Cooling) Do-1 On-Off + (Heating) Do-2 On-Off – (Cooling) al-1 Alarm 1 al-2 Alarm 2 al-3 Alarm 3 al-4 Alarm 4
Table 6. Analog Output Options co-1 PID + (Heating) co-2 PID – (Cooling) pvtr Process Value sptr Control Set Value
Table 7.1. Analog Output Range 0-20 0-20 mA 20-0 20-0 mA 4-20 4-20 mA 20-4 20-4 mA
Table 7.2. Analog Output Range 0-10 0-10 V 10-0 10-0 V 2-10 2-10 V 10-2 10-2 V

PID SETTINGS
tUNE

SECURITY
PRTC

For detailed information, you can access the comprehensive user manual of the device under the heading “User Manuals” at www.elimko.com.tr. You can also use the QR Code on the front for this.
Elimko Elektronik malat ve Kontrol Ticaret Ltd. ti. Ankara Sanayi Odasi 2. Organize Sanayi Bölgesi Alci OSB Mahallesi 2001. Cad. No:14 Temelli 06909 Ankara / TURKYE
Tel: +90 312 212 64 50 (Pbx) · Fax: +90 312 212 41 43 · E-mail: elimko@elimko.com.tr · www.elimko.com.tr