Elimko E-72P Series Universal Advanced Digital Controllers - Quick Start Guide
Model: KY-72P-0825-1
1. Description
The E-72P Series are universal process controllers, designed as industrial devices with 72x72 mm IEC/TR 60668 dimensions. They utilize new-generation microcontrollers and support on/off, PID, and other control forms, with user-programmable inputs and outputs. The controllers feature two 4-digit displays capable of showing set and measured values from -1999 to 9999. General-purpose inputs (T/C, R/T, mV, mA) can be programmed.
2. Dimensions and Panel Cut-Out
Physical Dimensions: 72 mm (Length) x 72 mm (Height) x 100 mm (Width).
Panel Cut-Out: 68 mm (Length) x 68 mm (Height).
Minimum spacing required: 10 mm front, 35 mm rear.
3. Connection Diagram
Description of terminal connections:
- Power Supply: Terminals 5, 6, 7.
- Relay Outputs: RL1 (Terminal 1), RL2 (Terminal 2).
- SSR Outputs: SSR1 (Terminal 3), SSR2 (Terminal 4).
- Communication: RS-485 (Terminals 8, 9: GND, TRX+, TRX-).
- Analog Outputs: AO1 (Terminal 10), AO2 (Terminal 11).
- Analog Inputs: Terminals 12-21 for various input types (Thermocouple, Resistance Thermometer, Current, Voltage).
Note: 1st and 2nd control outputs can be selected as Relay (RL1, RL2) or SSR (SSR1, SSR2). Analog output (AO1, AO2) can be selected as mA or 0-10 V DC.
4. Warnings
- E-72P controller is designed for panel mounting and should be used in an industrial environment.
- The package of E-72P controller contains: Controller, 2 pieces of mounting clamps, User manual and Guarantee certificate.
- Before installing and operating the controller, please read the user manual thoroughly.
- The installation and configuration of the controller must only be performed by a person qualified in instrumentation.
- Keep the unit away from flammable gases, that could cause explosion.
- Do not use alcohol or other solvents to clean the controller. Use a clean cloth soaked in water tightly squeezed to gently wipe the outer surface of the controller.
- It is not used in medical applications.
EU Directive Compliance: Low Voltage Directive EN 61010-1, EMC Directive EN 61326-1.
5. Type Coding
The E-72P Series model number is structured as: E-72P - W - X - Y - Z
- W (Relay Outputs): None, 1 relay (RL1), 2 relays (RL1, RL2), 1 SSR (SSR1), 1 SSR (SSR1) + 1 relay (RL2), 2 SSR (SSR1, SSR2).
- X (Analog Outputs): None, 1x 0-20/4-20 mA (AO1), 2x 0-20/4-20 mA (AO1, AO2), 1x 0-10 V DC (AO1), 2x 0-10 V DC (AO1, AO2), 1x 0-20/4-20 mA (AO1) + 1x 0-10 V DC (AO2).
- Y (Communication): None, RS-485.
- Z (Operating Voltage): 85-265 V AC / 85-375 V DC, 20-60 V AC / 20-60 V DC.
* Analog outputs are isolated from each other.
** When E-72P Series devices are ordered with communication, the E-IB-11 USB-RS485 converter can be used for PC connection. There are various control and monitoring software provided by Elimko.
6. Technical Specifications
Parameter | Description |
---|---|
Control Type | On/Off, PID, Heat/Cool, Floating and Feedback Control of Valves |
Operating Voltage | 20..60 V AC / 20..60 V DC or 85..265 V AC / 85..375 V DC |
Relays / SSR | 2 pieces SPST - NO 250 V AC 5A relays or 24 V DC 25 mA (SSR) drives |
Dimensions (mm) | 72 (Length) x 72 (Height) x 100 (Width) |
Panel Cut-Out (mm) | 68 (Length) x 68 (Height) |
Analog Output | 2 x 0..20 / 4..20 mA (Max. Load 600 Ohm) or 0..10 V DC optional |
Analog Input | Universal (Note 1) |
Communication (RS-485) | Available (optional) |
Digital Input | Available (optional) |
Valve Feedback | None |
Transmitter Supply | Available |
Weight | 232 g |
Power Consumption | Max. 7 W (10 VA) |
Operating Temperature | -10 °C ... 55 °C |
Storage Temperature | -25 °C ... 65 °C |
Memory | Max. 100,000 writes |
Protection Class | IP-65 Front Panel, IP-20 Rear Case |
Note 1: Universal Input Types:
- Thermocouple: B, E, J, K, L, N, R, S, T, U
- Resistance Thermometer: Pt-100
- Current: 0-20 mA, 4-20 mA (Linear)
- Voltage: 0-50 mV, 0-1 V, 0.2-1 V (Linear), 0-10 V DC (must be specified in order)
Resolution: 16 bit
Accuracy:
- Thermocouple: Max. ±1.0 °C (Conversion and CJC error)
- Resistance Thermometer: Max. ±0.5 °C (Conversion and wire resistance compensation)
- Linear Input: Max. % 0.1
7. Parameter Table
Key parameters and their settings:
Parameter Group | Parameter | Description | Min | Max | Unit |
---|---|---|---|---|---|
INPUT SETTINGS | INP1 | Analog Input 1 Type | See Table 1 | ||
DP | Decimal Point | 0 | 3 | ||
SCLO | Analog Input 1 Linear Scale Lower Value | -199.9 | 999.9 | EU | |
SCHI | Analog Input 1 Linear Scale Upper Value | -199.9 | 999.9 | EU | |
UNIT | Temperature Unit | *C / *F | |||
OFST | Analog Input 1 Offset Value | -100.0 | 100.0 | EU | |
FLTR | Analog Input 1 Filter | 1 | 15 | s | |
CONTROL SET SETTINGS | SPSR | Control Set Point Source | See Table 2 | ||
SPLL | Control Set Point Lower Limit | -199.9 | 999.9 | EU | |
SPHL | Control Set Point Upper Limit | -199.9 | 999.9 | EU | |
SPRR | Control Set Point Ramping Rate | OFF | 60.0 | EU/min | |
S-1 | 1. Step Set Value | SPLL | SPHL | EU | |
T-1 | 1. Step Time | OFF | 999.9 | min | |
S-2 | 2. Step Set Value | SPLL | SPHL | EU | |
ALARM SETTINGS | A1TP | Alarm 1 Type | See Table 3 | ||
A1SP | Alarm 1 Set Point | -199.9 | 999.9 | EU | |
A1HY | Alarm 1 Hysteresis | 0.0 | 999.9 | EU | |
A1LT | Alarm 1 Lock | DSB / ENB | |||
OUTPUTS | CTYP | Control Type | See Table 4 | ||
CFRM | Control Form | DIR / REV | |||
CPRD | Control Period | 1 | 250 | s | |
TRTM | Floating Control Valve Travel Time | 10 | 2500 | s | |
DBND | Dead Band | 0.1 | 25.0 | % | |
OLL | Control Output Lower Limit | 0.0 | OHL | % | |
OHL | Control Output Upper Limit | OLL | 100.0 | % | |
OMR | Control Output Manual Reset | OLL | OHL | % | |
TRLL | Retransmission Scale Lower Value | -199.9 | TRHL | EU | |
TRHL | Retransmission Scale Upper Value | TRLL | 999.9 | EU | |
PID SETTINGS | AT | PID Auto Tune | OFF / ON | ||
PID | PID Parameter Type | STD / ADV | |||
PB-1 | Proportional Band + | 0.1 | 999.9 | EU | |
ITH | Integral Time + | 0.1 | 9999 | s | |
SECURITY | SCOD | Security Code | 0 | 9999 | |
DPRL | Parameter Access Level | 0 | 9 | ||
APRL | Parameter Setting Level | 0 | 9 | ||
FCST | Factory Settings | OFF / LOAD / SAVE / DFLT |
Table 1: Input Type Options
- Thermocouple: b (Type B), e (Type E), j (Type J), k (Type K), l (Type L), n (Type N), r (Type R), s (Type S), t (Type T), u (Type U)
- Resistance Thermometer: pt (Pt-100)
- Current: 0-20, 4-20 (mA)
- Voltage: 0-50 mV, 0-1 V, 0.2-1 V, 0-10 V (*), 2-10 V (*)
- (*) Custom specified volt input
Table 2: Control Set Options
- int: Internal adjustment with keys
- prfl: With Profile Control
Table 3: Alarm Options
- off: Off
- lo: Low Alarm
- hi: High Alarm
- loD: Low Deviation
- hiD: High Deviation
- lob: Band Alarm (In)
- hib: Band Alarm (Out)
Table 4: Control Type Options
- off: No Control
- sco: Single (Heat)
- Dco: Double (Heat/Cool)
- bnD: Floating Control of Valve
Table 5: Relay Output Options
- co-1: PID + (Heating)
- co-2: PID - (Cooling)
- Do-1: On-Off + (Heating)
- Do-2: On-Off - (Cooling)
- al-1: Alarm 1
- al-2: Alarm 2
- al-3: Alarm 3
- al-4: Alarm 4
Table 6: Analog Output Options
- co-1: PID + (Heating)
- co-2: PID - (Cooling)
- pvtr: Process Value
- sptr: Control Set Value
Table 7.1: Analog Output Range (mA)
- 0-20, 20-0, 4-20, 20-4
Table 7.2: Analog Output Range (V)
- 0-10, 10-0, 2-10, 10-2
8. Accessing Parameters
The parameter access process involves three steps:
- Step 1: Security Code Entry - Enter the security code (default: 10).
- Step 2: Configuration Page Selection and Entry - Select and enter the desired configuration page.
- Step 3: Parameter Selection and Configuration - Select and configure individual parameters.
Navigation is done using 'Enter', 'Return', and 'Menu Access' buttons.
9. Application Examples
Illustrative examples of controller configuration:
- Example 1: Input: Pt-100. Relay/Alarm1: 50 °C Low, Relay2/Alarm2: 55 °C High. AO1: 4-20 mA PID Control Output.
- Example 2: Input: TC Type J. Relay1: On-Off Control Output. Relay2/Alarm2: 350 °C High.
- Example 3: Input: TC Type K. Profile Control (Ramp up to 400°C in 10 minutes and wait for 60 minutes). Relay1: PID Control Output. AO1: Retransmission Output (4-20 mA, 0-1200 °C).