Danfoss AKV 20 Electrically Operated Expansion Valve Type

Danfoss-AKV-20-Electrically-Operated-Expansion-Valve-Type-PRODUCT

Specifications

  • Model: AKV 20
  • Refrigerants: R744, R22/R407C, R404A/R507, R410A, R134a, R407A, R23
  • Max. Working Pressure: 28 barg (400 psig)
  • Max. Test Pressure: 31 barg (260 psig)
  • Max. Differential Pressure: 20 bar (290 psi)

Product Usage Instructions

Installation:

  1. Ensure the power is switched off before installing the valve.
  2. Mount the valve securely in place according to the manufacturer’s guidelines.
  3. If the valve is dismantled, make sure to exchange the gasket before reassembling.

Operation:
Make sure the coil is clipped onto the valve before turning on the power. Never energize the coil when it’s dismounted to prevent damage and potential injuries.

Maintenance:
Regularly inspect the valve for any signs of wear or damage. Replace any worn-out components promptly to ensure proper functioning.

 

Refrigerants:

R744, R22/R407C, R404A/R507, R410A, R134a, R407A, R23.

Note! AKV 20 are not suitable for R744 applications with media temperatures constantly below 0 °C, For other media temperatures, please contact Danfoss

Max. working pressure:            PS/MWP = 28 barg (400 psig)
Max. test pressure:                   Pe = 31 barg (260 psig)
Max. differential pressure:        MOPD = P1- P2= 20 bar (290 psi)
Ambient temperature range:   tamb   Min. -40 °C (-40 °F)

tamb Max. 50 °C (120 °F)

Media temperatur range:  tmedia  Min. -40 °C (-40 °F)

tmedia Max. 60 °C (140 °F)

Danfoss-AKV-20-Electrically-Operated-Expansion-Valve-Type-FIG- (1)  

Danfoss-AKV-20-Electrically-Operated-Expansion-Valve-Type-FIG- (3)

 

 

 

 

 

 

 

 

 

 

 

 

 

Danfoss-AKV-20-Electrically-Operated-Expansion-Valve-Type-FIG- (2)
 
 

 

 

 

Danfoss-AKV-20-Electrically-Operated-Expansion-Valve-Type-FIG- (4)

 Do not insulate

 

Danfoss-AKV-20-Electrically-Operated-Expansion-Valve-Type-FIG- (7)

 

 

 

Warning

Never switch on power to the coil when the coil is dismounted from the valve. Otherwise the coil may be damaged and there is risk of injuries and burns.

 

 

Danfoss-AKV-20-Electrically-Operated-Expansion-Valve-Type-FIG- (6)

 

Clip-on coil

 
 

Danfoss-AKV-20-Electrically-Operated-Expansion-Valve-Type-FIG- (8)

The gasket must be exchanged, if the valve is dismantled

Danfoss-AKV-20-Electrically-Operated-Expansion-Valve-Type-FIG- (9) Danfoss-AKV-20-Electrically-Operated-Expansion-Valve-Type-FIG- (10)

FAQS

Q: Can I use refrigerant R410A with this valve?
A: Yes, this valve is compatible with R410A refrigerant among others listed in the specifications.

Q: What is the recommended maximum working pressure for this valve?
A: The recommended maximum working pressure is 28 barg (400 psig).

Documents / Resources

Danfoss AKV 20 Electrically Operated Expansion Valve Type [pdf] Installation Guide
068R9523, AKV 20-1, AKV 20-2, AKV 20-3, AKV 20-4, AKV 20-5, AKV 20 Electrically Operated Expansion Valve Type, AKV 20, Electrically Operated Expansion Valve Type, Operated Expansion Valve Type, Expansion Valve Type, Valve Type