Electrically Operated Expansion Valve Type AKV 20

PDF preview unavailable. Download the PDF instead.

AN10878641693201-000404
068R9523 068R9523

Installation Guide
Electrically Operated Expansion Valve Type AKV 20

Refrigerants: R744, R22/R407C, R404A/R507, R410A, R134a, R407A, R23.
Note! AKV 20 are not suitable for R744 applications with media temperatures constantly below 0 °C, For other media temperatures, please contact Danfoss
Ambient temperature range: tamb Min. -40 °C (-40 °F) tamb Max. 50 °C (120 °F)

Max. working pressure:

PS/MWP = 28 barg (400 psig)

Max. test pressure:

Pe = 31 barg (260 psig)

Max. differential pressure: MOPD = P1- P2= 20 bar (290 psi)
Media temperatur range: tmedia Min. -40 °C (-40 °F) tmedia Max. 60 °C (140 °F)

FFILIL 100 m

AKV 20

Max. 700 ºC (1300 ºF)
Min 5% Ag

Max. 150 ºC (300 ºF)

(en-gb) Do not insulate (da) Må ikke isoleres (de) Nicht isolieren (fr) Ne pas isoler (es) No encerrar para
evitar condensación
Clip-on coil
© Danfoss | DCS (az) | 2018.06

On
Off
Warning Never switch on power to the coil when the coil is dismounted from the valve. Otherwise the coil may be damaged and there is risk of injuries and burns.
DKRCC.PI.VA1.D4.53 | 1

75 Nm ± 5 Nm

Danfoss 42H33.14

EN
The gasket must be exchanged, if the valve is dismantled

DA
Pakningen skal skiftes, hvis ventilen adskilles

DE
Bei Zerlegung des Ventils muß die Dichtung ausgewechselt werden

FR
Changer le joint chaque fois que la vanne est démontée

ES
Es preciso cambiar la junta si se desmonta la válvula

AKV 20-1 AKV 20-2 AKV 20-3
AKV 20-4 AKV 20-5

AKV 20 = 1 = 2 = 3
= 4 = 5

12 Nm ± 2 Nm © Danfoss | DCS (az) | 2018.06