aspar logoaspar RS485 MODBUS Module 6RO 6 Temperature Inputs

aspar RS485 MODBUS Module 6RO 6 Temperature Inputs

Thank you for choosing our product. This manual will help you with proper support and proper operation of the device. The information contained in this manual have been prepared with utmost care by our professionals and serve as a description of the product without incurring any liability for the purposes of commercial law. This information does not release you from the obligation of own judgment and verification. We reserve the right to change product specifications without notice. Please read the instructions carefully and follow the recommendations contained therein.

WARNING!
Failure to follow instructions can result in equipment damage or impede the use of the hardware or software.

Safety rules

  • Before first use, refer to this manual
  • Before first use, make sure that all cables are connected properly
  • Please ensure proper working conditions, according to the device specifications (eg: supply voltage, temperature, maximum power consumption)
  • Before making any modifications to wiring connections, turn off the power supply

Module Features

Purpose and description of the module

The 6RO Module is an innovative device that provides a simple and cost-effective extension of the number of lines of output with high current-carrying capacity. The module has 6 relay outputs. Each relay has three terminals: common (COM), normally open (NO) or normally closed (NC), so that the unit is very flexible. This module is connected to the RS485 bus with twisted-pair wire. Communication is via MODBUS RTU or MODBUS ASCII. The use of 32-bit ARM core processor provides fast processing and quick communication. The baud rate is configurable from 2400 to 115200. The module is designed for mounting on a DIN rail in accordance with DIN EN 5002. The module is equipped with a set of LEDs used to indicate the status of inputs and outputs useful for diagnostic purposes and helping to find errors. Module configuration is done via USB by using a dedicated computer program. You can also change the parameters using the MODBUS protocol.

Technical Specifications

 

Power Supply

Voltage 10-38VDC; 10-28VAC
Maximum Current 410 mA @ 12V / 320 mA @ 24V
 

Outputs

No of outputs 6
The maximum current and voltage (resistive load) 5A 250V AC
10A 24V DC
 

Temperature

Work -10 °C – +50°C
Storage -40 °C – +85°C
 

 

 

Connectors

Power Supply 2 pins
Communication 3 pins
Outputs 2 x 10 pins
Quick connector IDC10
Configuration Mini USB
 

Size

Height 120 mm
Length 101 mm
Width 22,5 mm
Interface RS485 Up to 128 devices

Dimensions of the product

Look and dimensions of the module are shown below. The module is mounted directly to the rail in the DIN industry standard. Power connectors, communication and IOs are at the bottom and top of the module. USB connector configuration and indicators located on the front of the module.

aspar RS485 MODBUS Module 6RO 6 Temperature Inputs 1

Communication configuration

Grounding and shielding

In most cases, IO modules will be installed in an enclosure along with other devices which generate electromagnetic radiation. Examples of these devices are relays and contactors, transformers, motor controllers etc. This electromagnetic radiation can induce electrical noise into both power and signal lines, as well as direct radiation into the module causing negative effects on the system. Appropriate grounding, shielding and other protective steps should be taken at the installation stage to prevent these effects. These protective steps include control cabinet grounding, module grounding, cable shield grounding, protective elements for electromagnetic switching devices, correct wiring as well as consideration of cable types and their cross sections.

Network Termination

Transmission line effects often present a problem on data communication networks. These problems include reflections and signal attenuation. To eliminate the presence of reflections from the end of the cable, the cable must be terminated at both ends with a resistor across the line equal to its characteristic impedance. Both ends must be terminated since the direction of propagation is bi-directional. In the case of an RS485 twisted pair cable this termination is typically 120 Ω.

Setting Module Address in RS485 Modbus Network

The following table shows how to set switch to determine the address of the module. The module address is set with the switches in the range of 0 to 31. Addresses From 32 to 255 can by set via RS485 or USB.

Addr SW5 SW4 SW3 SW2 SW1
0 OFF OFF OFF OFF OFF
1 OFF OFF OFF OFF ON
2 OFF OFF OFF ON OFF
3 OFF OFF OFF ON ON
4 OFF OFF ON OFF OFF
5 OFF OFF ON OFF ON
6 OFF OFF ON ON OFF
7 OFF OFF ON ON ON
8 OFF ON OFF OFF OFF
9 OFF ON OFF OFF ON
10 OFF ON OFF ON OFF
Addr SW5 SW4 SW3 SW2 SW1
11 OFF ON OFF ON ON
12 OFF ON ON OFF OFF
13 OFF ON ON OFF ON
14 OFF ON ON ON OFF
15 OFF ON ON ON ON
16 ON OFF OFF OFF OFF
17 ON OFF OFF OFF ON
18 ON OFF OFF ON OFF
19 ON OFF OFF ON ON
20 ON OFF ON OFF OFF
21 ON OFF ON OFF ON
Addr SW5 SW4 SW3 SW2 SW1
22 ON OFF ON ON OFF
23 ON OFF ON ON ON
24 ON ON OFF OFF OFF
25 ON ON OFF OFF ON
26 ON ON OFF ON OFF
27 ON ON OFF ON ON
28 ON ON ON OFF OFF
29 ON ON ON OFF ON
30 ON ON ON ON OFF
31 ON ON ON ON ON

Types of Modbus Registers

There are 4 types of variables available in the module

Type Beginning address Variable Access Modbus Command
1 00001 Digital Outputs Bit

Read & Write

1, 5, 15
2 10001 Digital Inputs Bit Read 2
3 30001 Input Registers Registered Read 3
4 40001 Output Registers Registered Read & Write 4, 6, 16

Communication settings

The data stored in the modules memory are in 16-bit registers. Access to registers is via MODBUS RTU or MODBUS ASCII.

Default settings

You can restore the default configuration by the switch SW6 ( see 3.5.2 – Restore the default configuration)

Baud rate 19200
Parity No
Data bits 8
Stop bits 1
Reply Delay [ms] 0
Modbus Mode RTU

Restore the default configuration

  • turn off the power
  • turn on the switch SW6
  • turn on the power
  •  when power and communication LED flash turn off the switch SW6

Caution: After restoring the default configuration all values stored in the registers will be cleared as well.

Configuration registers

Modbus Dec Hex  

Name

 

Values

Address
 

 

 

40003

 

 

 

2

 

 

 

0x02

 

 

 

Baud rate

0 – 2400

1 – 4800

2 – 9600

3 – 19200

4 – 38400

5 – 57600

6 – 115200

other – value * 10

 

 

40005

 

 

4

 

 

0x04

 

 

Parity

0  – none

1  – odd

2  – even

3  – always 1

4  – always 0

40004 3 0x03 Stop Bits LSB 1 – one stop bit 2 – two stop bits
40004 3 0x03 Data Bits MSB 7  – 7 data bits

8  – 8 data bits

40006 5 0x05 Response delay Time in ms
40007 6 0x06 Modbus Mode 0  – RTU

1  – ASCII

Watchdog function

This 16-bit register specifies the time in milliseconds to watchdog reset. If module does not receive any valid message within that time, all Digital and Analog Outputs will be set to the default state.
This feature is useful if there is an interruption in data transmission and for security reasons. Output states must be set to the appropriate state in order to assure the safety of persons or property.
The default value is 0 milliseconds which means the watchdog function is disabled

Indicators

aspar RS485 MODBUS Module 6RO 6 Temperature Inputs 2

Indicator Description
Power supply LED indicates that the module is correctly powered.
Communication The LED lights up when the unit received the correct packet and sends the answer.
Outputs state LED indicates that the output is on.

Module Connection

aspar RS485 MODBUS Module 6RO 6 Temperature Inputs 3

Switches

aspar RS485 MODBUS Module 6RO 6 Temperature Inputs 4

Switch Function Description
1 Module address +1  

 

 

Setting module address from 0 to 31

2 Module address +2
3 Module address +4
4 Module address +8
5 Module address +16
 

6

 

Restoring default settings

Restoring default settings

(see 3.5.1 Default settings and 3.5.2 Restore the default configuration).

Modules Registers

Registered access

Modbus Dec Hex Register Name Access Description
30001 0 0x00 Version/Type Read Version and Type of the device
30002 1 0x01 Switches Read Switches state
40003 2 0x02 Baud rate Read & Write RS485 baud rate
40004 3 0x03 Stop Bits & Data Bits Read & Write No of Stop bits & Data Bits (see 3.5.3)
40005 4 0x04 Parity Read & Write Parity bit
40006 5 0x05 Response Delay Read & Write Response delay in ms
40007 6 0x06 Modbus Mode Read & Write Modbus Mode (ASCII or RTU)
40009 8 0x08 Watchdog Read & Write Watchdog
40013 12 0x0C Default outputs state Read & Write Default outputs state
40033 32 0x20 Received packets LSB Read & Write  

No of received packets

40034 33 0x21 Received packets MSB Read & Write
40035 34 0x22 Incorrect packets LSB Read & Write  

No of received packets with error

40036 35 0x23 Incorrect packets MSB Read & Write
40037 36 0x24 Sent packets LSB Read & Write  

No of sent packets

40038 37 0x25 Sent packets MSB Read & Write
40052 51 0x33 Outputs Read & Write Outputs state
Modbus Address Dec Address Hex Address Register name Access Description
193 192 0x0C0 Default output 1 state Read & Write Default output 1 state
194 193 0x0C1 Default output 2 state Read & Write Default output 2 state
195 194 0x0C2 Default output 3 state Read & Write Default output 3 state
196 195 0x0C3 Default output 4 state Read & Write Default output 4 state
197 196 0x0C4 Default output 5 state Read & Write Default output 5 state
198 197 0x0C5 Default output 6 state Read & Write Default output 6 state
817 816 0x330 Output 1 Read & Write Output 1 state
818 817 0x331 Output 2 Read & Write Output 2 state
819 818 0x332 Output 3 Read & Write Output 3 state
820 819 0x333 Output 4 Read & Write Output 4 state
821 820 0x334 Output 5 Read & Write Output 5 state
822 821 0x335 Output 6 Read & Write Output 6 state

Configuration software

Modbus Configurator is software that is designed to set the module registers responsible for communication over Modbus network as well as to read and write the current value of other registers of the module. This program can be a convenient way to test the system as well as to observe real-time changes in the registers. Communication with the module is done via the USB cable. The module does not require any drivers.

aspar RS485 MODBUS Module 6RO 6 Temperature Inputs 5

Configurator is a universal program, whereby it is possible to configure all available modules.

aspar RS485 MODBUS Module 6RO 6 Temperature Inputs 6

Manufactured for: Aspar s.c.
ul. Oliwska 112 80-209 Chwaszczyno Poland
ampero@ampero.eu
www.ampero.eu
tel. +48 58 351 39 89; +48 58 732 71 73