Installation GuideGPL-DV4C/DC4C

LS GPL-DV4C Programmable Logic Controller - QR Code

10310000542

This installation guide provides simple function information or PLC control. Please read carefully this data sheet and manuals before using products. Especially read precautions then handle the products properly.

Safety Precautions

■ Meaning of warning and caution label
WARNING indicates a potentially hazardous situation which, if not avoided, could result in death or serious injury
CAUTION indicates a potentially hazardous situation which, if not avoided, may result in minor or moderate injury. It may also be used to alert against unsafe practices

warning - 1 WARNING
① Do not contact the terminals while the power is applied.
② Be sure there are no foreign metallic matters.
③ Do not manipulate the battery(charge, disassemble, hitting, short, soldering).
warning - 1 CAUTION
① Be sure to check the rated voltage and terminal arrangement before wiring
② When wiring, tighten the screw of terminal block with the specified torque range
③ Do not install the flammable things on surroundings
④ Do not use the PLC in the environment of direct vibration
⑤ Except expert service staff, do not disassemble or fix or modify the product
⑥ Use the PLC in an environment that meets the general specifications contained in this datasheet.
⑦ Be sure that external load does not exceed the rating of output module.
⑧ When disposing of PLC and battery, treat it as industrial waste.
⑨ I/O signal or communication line shall be wired at least 100mm away from a highvoltage cable or power line.

Operating Environment

■ To install, observe the below conditions.

No Item Specification Standard
1 Ambient temp. 0 ~ 55℃
2 Storage temp. -25 ~ 70℃
3 Ambient humidity 5 ~ 95%RH,  non-condensing
4 Storage humidity 5 ~ 95%RH,  non-condensing
5 Vibration Resistance Occasional vibration
Frequency Acceleration IEC 61131-2
5≤f<8.4㎐ 3.5mm 10 times in each direction for X, Y, Z
8.4≤f≤150㎐ 9.8㎨(1g)
Continuous vibration
Frequency Frequency Frequency
5≤f<8.4㎐ 1.75mm
8.4≤f≤150㎐ 4.9㎨(0.5g)

Accessories and Cable Specifications

■ Check Profibus Connector contained in the box

  1. Usage : Profibus Communication Connector
  2. Item : GPL-CON

■ When using Pnet communication, shielded twisted pair cable shall be used with consideration of communication distance and speed.

  1. Manufacturer : Belden or the maker of equivalent material specification below
  2. Cable Specification
Classification Description
AWG 22 LS GPL-DV4C Programmable Logic Controller - Fig 1
Type BC (Bare Copper)
Insulation PE (Polyethylene)
Diameter(inch) 0.035
Shield Aluminum Foil-Polyester, Tape/Braid Shield
Capacifance(pF/ft) 8.5
Characteristic impedance(Ω) 150Ω

Dimension (mm)

■ This is front part of the product. Refer to each name when operating the system. For more information, refer to user’s manual.

LS GPL-DV4C Programmable Logic Controller - Fig 2

■ LED Details

Name Description
RUN Displays the status of power
RDY Displays the communication status of Comm. Module
ERR Displays the abnormal err of comm.. module

Analog Performance Specification

■ This is analog performance specifications of the product. Refer to each name when driving the system. For more information, refer to user manual.

Item GPL-DV4C (Voltage output) GPL-DC4C (Current output)
Analog output channels 4 channels
Analog input 1~5V 0~4000 4~20mA 0~8000
0~5V
0~10V 0~8000 0~20mA
-10~10V -8000~8000
Resolution 1~5V 1.250mV 4~20mA 2.5µA
0~5V
0~10V 0~20mA
-10~10V
Accuacy(Ambient tem.) ±0.3% or less ±0.4% or less
Conversion speed 10ms/module + Update time
Absolute max. input ±15V ±25mA
Insulation method Photo-coupler insulation between input terminal and PLC power (no insulation between channels)
Terminal connected 38-point terminal
Internal consumed current DC24V, 210mA DC24V, 240mA
Weight 314g 322g

Terminal Block Layout for I/O Wiring

■ This is terminal block layout for I/O wiring. Refer to each name when driving the system.
For more information, refer to user manual.

LS GPL-DV4C Programmable Logic Controller - Fig 3

Wiring

■ Connector structure and wiring method

  1. Input line: green line is connected to A1, red line is connected to B1
  2. Output line: green line is connected to A2, red line is connected to B2
  3. Connect shield to clamp of shield
  4. In case of installing the connector at terminal, install the cable at A1, B1LS GPL-DV4C Programmable Logic Controller - Fig 4
  5. For more information about wiring, refer to user manual.

Warranty

■ The warranty period is 36 months from the date of manufacture.
■ The initial diagnosis of faults should be conducted by the user. However, upon request, LS
ELECTRIC or its representative(s) can undertake this task for a fee. If the cause of the fault is
found to be the responsibility of LS ELECTRIC, this service will be free of charge.
■ Exclusions from warranty

  1. Replacement of consumable and life-limited parts (e.g. relays, fuses, capacitors, batteries, LCDs, etc.)
  2. Failures or damages caused by improper conditions or handling outside those specified in the user manual
  3. Failures caused by external factors unrelated to the product
  4. Failures caused by modifications without LS ELECTRIC’s consent
  5. Use of the product in unintended ways
  6. Failures that cannot be predicted/solved by current scientific technology at the time of manufacture
  7. Failures due to external factors such as fire, abnormal voltage, or natural disasters
  8. Other cases for which LS ELECTRIC is not responsible

■ For detailed warranty information, please refer to the user’s manual.
■ The content of the installation guide is subject to change without notice for product performance improvement.

LS ELECTRIC Co., Ltd. www.ls-electric.com 10310000542 V4.5 (2024.6)
• E-mail: automation@ls-electric.com

• Headquarter/Seoul Office
• LS ELECTRIC Shanghai Office (China)
• LS ELECTRIC (Wuxi) Co., Ltd. (Wuxi, China)
• LS-ELECTRIC Vietnam Co., Ltd. (Hanoi, Vietnam)
• LS ELECTRIC Middle East FZE (Dubai, U.A.E.)
• LS ELECTRIC Europe B.V. (Hoofddorf, Netherlands)
• LS ELECTRIC Japan Co., Ltd. (Tokyo, Japan)
• LS ELECTRIC America Inc. (Chicago, USA)
Tel: 82-2-2034-4033,4888,4703
Tel: 86-21-5237-9977
Tel: 86-510-6851-6666
Tel: 84-93-631-4099
Tel: 971-4-886-5360
Tel: 31-20-654-1424
Tel: 81-3-6268-8241
Tel: 1-800-891-2941

• Factory: 56, Samseong 4-gil, Mokcheon-eup, Dongnam-gu, Cheonan-si, Chungcheongnamdo, 31226, Korea