Danfoss-logo

Danfoss Filter Drier Shell

Danfoss-Filter-Drier-Shell- product

Fa'amatalaga

  • Refrigerants: CO2 (sub critical and trans critical system)
  • Media Temperature: -55 to 100 °C / -67 to 212 °F
  • Maximum working pressure (PS/MWP): 90bar / 1305 psig

Fuafuaga

Danfoss-Filter-Drier-Shell- (2)

Danfoss-Filter-Drier-Shell- (3)

Fa'apipi'i

Danfoss-Filter-Drier-Shell- (4)

Ituaiga L aupito maualalo
[mm] [i totonu]
DCR 048 250 9.8
DCR 096 400 15.8

Fa'aeteete i mailei fa'aa'aisa vai i totonu o le masini e ono i'u ai i le maualuga tele o omiga i totonu a'o vevela. Ia mautinoa lelei pamu i lalo a'o le'i aveese le ufiufi o le DCR Fa'amama uma fo'i le pusaaisa o totoe a'o le'i aveese fa'amau ufi.

Fa'asalaina

Danfoss-Filter-Drier-Shell- (5)

Uelo

Danfoss-Filter-Drier-Shell- (6)

Danfoss-Filter-Drier-Shell- 9

O le a manaʻomia pea faiga faʻapitoa a tagata faʻatau:

  • Aveese le ufiufi fa'apipi'i a'o le'i fa'aulu/uelo.
  • Aua ne'i aveese le 'au autu mai le ufiufi.
  • Fa'amauina/Uloina o so'oga e faia e le uelo fa'amaonia.
  •  Tuu i latou e maalili.
  • Clean the brazing /welding area after the instal-lation (remove remaining flux with a brush).
  • Ose ta'aloga taua ma e mana'omia le faia ma le fa'aeteete tele e aveese uma ai le fe'avea'i o totoe.
  • O le pito i fafo o loʻo i ai le TLP (Zink) faʻapipiʻi e puipuia ai le pala, ae matou te fautuaina le valiina o le DCR pe a uma ona faʻapipiʻi mo le maualuga o le puipuiga o le pala.
  • A maeʻa le faʻamalosi / uelo faʻaoga faʻapipiʻi talafeagai i luga o le mea faʻapipiʻi e aloese ai mai soʻo se ele i totonu o le fanua.

Gasket

Danfoss-Filter-Drier-Shell- (7)

Aua ne'i fa'apipi'i fa'aofi DCR a'o le'i fa'apalaina/uelo

Fa'aaliga: Fa'amaonia le sa'o o le ufiufi ufiufi pito i luga ua filifilia mo le DCR
Aua ne'i toe fa'aogaina le kesi
Aua ne'i fa'aogaina le Suau'u/Su'u ile Gasket

Danfoss-Filter-Drier-Shell- (8)

Fa'afefea ona fa'amau fa'amau

Danfoss-Filter-Drier-Shell- (1)

DCR Bolts M12*1.75
Laasaga 1 Faamaumau tamatamailima uma faamau
Laasaga 2 10 Nm/7.4 lbf.ft
Laasaga 3 20 Nm/15 lbf.ft
Laasaga 4 40 Nm/30 lbf.ft
Laasaga 5 80 Nm /59 lbf.ft

* Toe fai seʻia oʻo ina atoatoa le fufusi.

Vaega Tele Torque (N.m/ lbf.ft)
Ufiufi faamau M12*1.75 80/59
Polo* 1/4” NPT 50/37
Polo* 1/2” G 50/37
A'ai Autu M10 30/22
Nutini faiapaau M8 1.5 /1.10

(Hand tight)

Fa'aaliga:
** Sui le palaka mo example with schrader/Needle valve etc..
© Danfoss | Fofo o le Tau | 2024.12

FAQ

Can I reuse the gasket for the DCR cover?

No, do not reuse the gasket. Ensure to select the correct top cover gasket for DCR and do not use Oil/Grease on the gasket.

What should I do with the rubber bush during assembly?

Remove the rubber bush while making assembly.

What type of connector and brazing material should be used?

Use Steel material with Silver-flo 55 + Easy-flow flux for brazing.