SENECA logo

INSTALLATION MANUAL
Z-D-IN

PRELIMINARY WARNINGS

The word WARNING preceded by the symbol Warning icon indicates conditions or actions that put the user’s safety at risk.
The word ATTENTION preceded by the symbol Warning icon indicates conditions or actions that might damage the instrument or the connected equipment. The warranty shall become null and void in the event of improper use or tampering with the module or devices supplied by the manufacturer as necessary for its correct operation, and if the instructions contained in this manual are not followed.

Warning icon WARNING: The full content of this manual must be read before any operation. The module must only be used by qualified electricians. Specific documentation is available via QR-CODE shown on page 1.
SENECA Z-D-IN Digital Input or Output Modules - sambol2 The module must be repaired and damaged parts replaced by the Manufacturer. The product is sensitive to electrostatic discharges. Take appropriate measures during any operation.
Dustbin Icon Electrical and electronic waste disposal (applicable in the European Union and other countries with recycling). The symbol on the product or its packaging shows the product must be surrendered to a collection center authorized to recycle electrical and electronic waste.

MODULE LAYOUT

SENECA Z-D-IN Digital Input or Output Modules - fig1

SIGNALS VIA LED ON FRONT PANEL

LED STATUS LED meaning
PWR Green ON The device is powered correctly
FAIL yellow ON Anomaly or fault
FAIL yellow Flashing Wrong setup
RX Red ON Connection check
RX Red Flashing Receipt of packet completed
TX Red Flashing Transmission of packet completed

TECHNICAL SPECIFICATIONS

CERTIFICATIONS SENECA Z-D-IN Digital Input or Output Modules - qr2
https://www.seneca.it/products/z-d-in/doc/CE_declaration
INSULATION SENECA Z-D-IN Digital Input or Output Modules - fig2
POWER SUPPLY Voltage: 10 ÷ 40Vdc; 19 ÷ 28Vac; 50 ÷ 60Hz
Absorption: Typical: 1.5W @ 24Vdc, Max: 2.5W
USE Use in environments with pollution degree 2.
The power supply unit must be class 2.
ENVIRONMENTAL CONDITIONS Temperature: -10÷ + 65°C
Humidity: 30%÷ 90% at 40°C noncondensing.
Altitude: Up to 2,000 m above sea level
Storage temperature: -20÷ + 85°C
Degree of protection: IP20.
ASSEMBLY IEC EN60715, 35mm DIN rail in vertical position.
CONNECTIONS 3-way removable screw terminals, 5mm pitch, 2.5mm2 section
Rear connector IDC10 for DIN bar 46277
INPUTS
Type of supported
inputs:
Reed, Contatto, proximity PNP, NPN (with external resistance)
A number of channels: 5 (4+ 1) self-powered at 16Vdc
Totalizer maximum
frequency
100 Hz for channels from 1 to 5
10 kHz only for input 5 (after setting)
UL (Status OFF) 0 ÷ 10 Vdc, I < 2mA
UH (status ON) 12 ÷ 30 Vdc; I > 3mA
Absorbed current 3mA (for each active input)
Protection By means of transient TVS suppressors of 600 W/ms.

CONFIGURATION OF FACTORY SETTINGS

All DIP-switches in OFFSENECA Z-D-IN Digital Input or Output Modules - icon1
Communication parameters of Modbus protocol: 38400 8, N, 1 Address 1
Input status inversion: DISABLED
Digital filter 3ms
Totalizers Counting to increment
Channel 5 at 10 kHz Disabled
Modbus latency time 5ms

Modbus CONNECTION RULES

  1. Install the modules in the DIN rail (120 max)
  2. Connect the remote modules using cables of an appropriate length. The following table shows cable length data:
    – Bus length: maximum length of the Modbus network according to the Baud Rate. This is the length of the cables that connect the two farthest modules (see Diagram 1).
    – Derivation length: maximum length of a derivation 2 m (see Diagram 1).

Diagram 1

Bus length Derivation length
1200 m 2 m

SENECA Z-D-IN Digital Input or Output Modules - fig3

For maximum performance, it is recommended to use special shielded cables, such as BELDEN 9841.

IDC10 CONNECTOR

Power supply and Modbus interface are available using the Seneca DIN rail bus, via the IDC10 rear connector, or the Z-PC-DINAL2-17.5 accessory.

SENECA Z-D-IN Digital Input or Output Modules - fig4

Rear Connector (IDC 10)
The meaning of the various pins on the IDC10 connector is shown in the figure if you wish to supply signals directly via it.

SETTING THE DIP-SWITCHES

The position of the DIP-switches defines the Modbus communication parameters of the module: Address and Baud Rate
The following table shows the values of the Baud Rate and the Address according to the setting of the DIP switches:

DIP-Switch status
SW1 POSITION BAUD
RATE
SW1 POSITION ADDRESS POSITION TERMINATOR
1  2  3  4  5  6  7  8 3  4  5  6  7  8 10
SENECA Z-D-IN Digital Input or Output Modules - icon1SENECA Z-D-IN Digital Input or Output Modules - icon1————– 9600 SENECA Z-D-IN Digital Input or Output Modules - icon1SENECA Z-D-IN Digital Input or Output Modules - icon1SENECA Z-D-IN Digital Input or Output Modules - icon1SENECA Z-D-IN Digital Input or Output Modules - icon1SENECA Z-D-IN Digital Input or Output Modules - icon1SENECA Z-D-IN Digital Input or Output Modules - icon2 #1 SENECA Z-D-IN Digital Input or Output Modules - icon2 Disabled
SENECA Z-D-IN Digital Input or Output Modules - icon1SENECA Z-D-IN Digital Input or Output Modules - icon2———— 19200 SENECA Z-D-IN Digital Input or Output Modules - icon1SENECA Z-D-IN Digital Input or Output Modules - icon1SENECA Z-D-IN Digital Input or Output Modules - icon1SENECA Z-D-IN Digital Input or Output Modules - icon1SENECA Z-D-IN Digital Input or Output Modules - icon2SENECA Z-D-IN Digital Input or Output Modules - icon1 #2 SENECA Z-D-IN Digital Input or Output Modules - icon1 Enabled
SENECA Z-D-IN Digital Input or Output Modules - icon2SENECA Z-D-IN Digital Input or Output Modules - icon1———– 38400 ••••••• #…
SENECA Z-D-IN Digital Input or Output Modules - icon2SENECA Z-D-IN Digital Input or Output Modules - icon2———– 57600 SENECA Z-D-IN Digital Input or Output Modules - icon2SENECA Z-D-IN Digital Input or Output Modules - icon2SENECA Z-D-IN Digital Input or Output Modules - icon2SENECA Z-D-IN Digital Input or Output Modules - icon2SENECA Z-D-IN Digital Input or Output Modules - icon2SENECA Z-D-IN Digital Input or Output Modules - icon2 #63
——-SENECA Z-D-IN Digital Input or Output Modules - icon1SENECA Z-D-IN Digital Input or Output Modules - icon1SENECA Z-D-IN Digital Input or Output Modules - icon1SENECA Z-D-IN Digital Input or Output Modules - icon1SENECA Z-D-IN Digital Input or Output Modules - icon1SENECA Z-D-IN Digital Input or Output Modules - icon1 From
EEPROM
SENECA Z-D-IN Digital Input or Output Modules - icon1SENECA Z-D-IN Digital Input or Output Modules - icon1SENECA Z-D-IN Digital Input or Output Modules - icon1SENECA Z-D-IN Digital Input or Output Modules - icon1SENECA Z-D-IN Digital Input or Output Modules - icon1SENECA Z-D-IN Digital Input or Output Modules - icon1 From
EEPROM

Note: When DIP switches 3 to 8 are OFF, the communication settings are taken from programming (EEPROM).
Note 2: The RS485 line must be terminated only at the ends of the communication line.
The settings of the dip-switches must be compatible with the settings on the registers.
The description of the registers is available in the USER MANUAL.

ELECTRICAL CONNECTIONS

SENECA Z-D-IN Digital Input or Output Modules - fig5

Power supply:
The upper limits must not be exceeded in order to avoid serious damage to the module.
If the power supply source is not protected against overload, a safety fuse must be installed in the power supply line with a value suitable to what the situation requires.

SENECA Z-D-IN Digital Input or Output Modules - fig6

Modbus RS485
Connection for RS485 communication using the MODBUS master system as an alternative to the Z-PC-DINx bus.
N.B.: The indication of the RS485 connection polarity is not standardized and in some devices may be inverted.

INPUTS

SENECA Z-D-IN Digital Input or Output Modules - fig7

INPUT SETTINGS:
Default settings:
Input #1: 0 – 100 Hz (16BIT)
Input #2: 0 – 100 Hz (16BIT)
Input #3: 0 – 100 Hz (16BIT)
Input #4: 0 – 100 Hz (16BIT)
Input #5: 0 – 100 Hz (16BIT)
Input #5 can be set as a totalizer:
Input #5: 0 – 10 kHz (32BIT)

Warning icon ATTENTION

The upper power supply limits must not be exceeded, as this might cause serious damage to the module. Switch the module off before connecting inputs and outputs.

To meet the electromagnetic immunity requirements:

  • use shielded signal cables;
  • connect the shield to a preferential instrumentation earth system;
  • a fuse with a MAX. rating of 0,5 A must be installed near the module.
  • separate shielded cables from other cables used for power installations (inverters, motors, induction ovens, etc…).
  • make sure that the module is not supplied with a supply voltage higher than that indicated in the technical specifications in order not to damage it.

SENECA Z-D-IN Digital Input or Output Modules - qr1www.seneca.it/products/z-d-in

SENECA Z-D-IN Digital Input or Output Modules - sambol1

SENECA s.r.l.; Via Austria, 26 – 35127 – PADOVA – ITALY;
Tel. +39.049.8705359 –
Fax +39.049.8706287

CONTACT INFORMATION

Technical support
support@seneca.it
Product information
sales@seneca.it

This document is the property of SENECA srl. Copies and reproduction are prohibited unless authorized. The content of this document corresponds to the described products and technologies. Stated data may be modified or supplemented for technical and/or sales purposes.

Documents / Resources

SENECA Z-D-IN Digital Input or Output Modules [pdf] Instruction Manual
Z-D-IN, Digital Input or Output Modules, Z-D-IN Digital Input or Output Modules

References

Leave a comment

Your email address will not be published. Required fields are marked *